D2610-01-03 CN5819 DM650LP User guide Page 1of 2
DM650LP USER GUIDE
LOOP POWERED DIGITAL DISPLAY WITH RELAY AND USB/NFC
INTERFACE LOGGING FUNCTION. USER GUIDE
Important - Please read this document before installing.
Every effort has been taken to ensure the accuracy of this document; however, we do
not accept responsibility for damage, injury, loss or expense resulting from errors and
omissions, and we reserve the right of amendment without notice.
IMPORTANT – CE, UKCA & SAFETY REQUIREMENTS.
The instrument is designed to be either directly attached to a sensor probe assembly or
surface mounted. The user must ensure all sensor and cable entries maintain
environmental protection to at least IP65 rating.
Battery - Fire Explosion and Severe Burn Hazard. Do not attempt to re-charge, Crush,
Incinerate, Disassemble, Heat above 100 °C (212 °F) or expose to water.
Disposal of the battery must conform with the regulations applicable for the area
of use.
The product contains no serviceable parts, or internal adjustments. No attempt must be
made to repair this product. Faulty units must be returned to supplier for repair.
This product must be installed by a qualified person. All electrical wiring must be carried
out in accordance with the appropriate regulations for the place of installation.
Before attempting any electrical connection work, please ensure the battery is removed
ABSOLUTE MAXIMUM CONDITIONS: To exceed may cause damage to the
device.
Battery voltage
3.7 Vdc (Protected for reverse connection)
Input current
± 50 mA
Relay
50 Vdc, 40 Vac rms
Ambient
Temperature (-30 to 70) °C,
Humidity (10 to 95) % RH noncondensing)
Important – Read this
document before installing.
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
1~DESCRIPTION.
The DM650LP loop powered indicator with battery backup accepts a (4 to 20) mA signal
and provides a powerful display interface based on a 6-digit 14-segment LCD display.
User-set scaling is provided to allow the user to set process ranges between -999999
and 999999. Maths functions are provided working on the actual (4 to 20) mA signal for
requirements such as square root extraction.
A 22-segment user-set linearisation/correction function is offered, as well as advanced
messaging, allowing the user to display custom messages for pre-set input ranges.
2~RECEIVING AND UNPACKING.
Please inspect the packaging and instrument thoroughly for any signs of transit
damage. If the instrument has been damaged, please notify your supplier immediately.
3~SPECIFICATION.
Refer to data sheet for full specification.
Configuration
Factory default
(4 to 20) mA = (0 to 100) °C, Relay off
4~ INSTALLATION AND WIRING.
4.1~MECHANICAL.
The instrument is a high accuracy digital (4 to 20) mA loop powered display. In order to
ensure correct operation, the following must be observed:
The product must be stored in a dry clean environment and remain in original
packaging prior to installation.
The instrument must not be installed adjacent to electro-mechanical starters,
controllers, thyristor power units or electrical switch gear.
Any cleaning of the instrument must be done using a mild detergent and soft cloth. No
solvents or abrasive cleaners should be used.
Stated ambient operating conditions must not be exceeded. Battery life will reduce with
higher ambient temperature operating conditions.
4.2~ELECTRICAL.
For a wiring diagram please refer to the rear panel of the DM650LP inside the
case housing.
Screw connectors are used for input and relay connections, allowing the unit to be used
with some in head temperature transmitters (refer to sales for details). On insertion of
battery the unit will run through a power-up check; during this time the relay may
change state.
IMPORTANT: Always remove battery before any wiring takes place. Gain access to the
connectors and battery holder by twisting cap to release front panel assembly from
case.
INPUT: The SEM650LP is to be wired in series on a (4 to 20) mA loop. The battery is
not required for basic display operation, however for datalogging operation the battery
will be required. The connections are marked “+” and “-“.
RELAY CONNECTION: A relay with changeover contacts is available. Screw terminals
are provided for connection for wire size 16 to 20 AWG. The relay contacts are rated at
48 VDC 28 VAC RMS @ 1 A (5 mA minimum current) see DM650LP data sheet.
The relay connections are marked “NO” for normally open, “NC” for normally closed and
“C” for common.
BATTERY: To remove battery, use screwdriver to ease the positive end of the battery
out of holder. Insert new battery negative end first then press into place. (Observe
polarity). Battery type 3.6 V Lithium (2.4 A/Hr) CR14505 (IEC) AA case style. Please
dispose of the battery in a responsible way.
WARNING
For configuring, reading live data or reading logged data if using a grounded loop on the
input, it is important not to connect the programming USB lead to a mains-powered
computer. It is possible to damage the instrument if connected in this way.
To avoid damage, use one of the following methods:
•Disconnect the loop before configuration, reconnect the loop after configuration.
•Ensure any sensor connected and DM650 housing are not in contact with any
conductive parts during configuration.
•Use a laptop-type computer running from its battery power supply, not connected
to a mains supply. This is recommended for reading lived data or offsetting a unit if
already installed in the field.
•Use a USB isolator between the computer and the DM650.
5~USER CONFIGURATION.
IMPORTANT READ COMPLETE SECTION BEFORE ATTEMPTING
CONFIGURATION.
The instrument is provided with a USB interface for direct connection to a PC. Free
software USBSpeedLink is available. Please refer to the USBSpeedLink software for
further information on configuration. The software can be downloaded from
www.status.co.uk.
DISPLAY: The display provides six 14-segment characters for display of temperature
and alpha-numeric messages, together with an 8-segment bar graph and six icons. The
display can operate in an ambient temperature range of (-30 to 70) °C, but at
temperatures lower than -5 °C (due to the slower LCD speed) scrolled messaging is not
practical for screen updates.
The display’s high contrast, coupled with a digit height of 7.9 mm, offers clear readouts
at low as well as high ambient light and direct sunlight.
The display layout is as follows:
D2610-01-03 CN5819 DM650LP User guide Page 2of 2
5~USER CONFIGURATION (continued).
1. NFC - The Symbol is on when an NFC field is detected. When a detected field is lost the symbol
will turn off after a few seconds.
2. TRANSMIT/RECEIVE: Symbol on when either NFC or USB communication is active.
3. USB: Symbol on when USB port is connected to a PC. Please note battery is not required during
configuration.
4. LOG: Not used
5. mA: On when bar graph is set to display % mA input range, off when bar graph shows % log fill.
6. BAR GRAPH: Indicates the state of the logger. The condition is dependent on the selected logger
mode, either Single or Rolling mode.
Single Mode (Log to the maximum number of logs then stop)
Start of Log Mid Log End of Log (alternating)
Rolling Mode (Log to the maximum number of logs then as each new log is taken the oldest log is
discarded)
Start of Log Mid Log Rolled over Log (max bar toggles)
7. DEG: Degree symbol “°” used to indicate either °C, °F, °R or K on the last digit.
8. DIGITS: Six-digit 14-segment display with – sign, range 9999.9 to -9999.9. Advanced mode offers
two process value-dependent 32-character message options.
9. WARNING ICON: This symbol will toggle on and off to indicate a warning. The warning symbol
will be active either when the sensor signal is out of range or not connected.
!
USBSLogLink DATA LOGGER SOFTWARE*
LIVE DEVICE READING TAB
Display
Live process value
RETRIEVE LOGGED DATA TAB
Download and graph recorded logged data
CONFIGURE LOGGER
Set new log (rolling or fixed), interval time, number of logs, delay start
Enter (tag and contact), reset (max and min) Sync clock
USBSpeedLink CONFIGURATION SOFTWARE*
PROCESS SCALING TAB
Select
Linear or maths, decimal place, engineering units, display range, user
linearisation table, null least significant digit(s) if required.
If display type = Temperature then °C, °F, °R, K units can be selected otherwise
the advanced messaging TAB can be used to add an engineering unit.
Pre-set Sensor Signal to Set-Point the input value can be fixed to a pre-
determined value, the messaging display and relay will respond accordingly.
RELAY OPTIONS TAB
Select
Select relay operation, set-point, dead band, relay name
BASIC DISPLAY OPTIONS TAB
Select
Bar graph function to % of mA input or % of log fill
Select
LED alert for, relay
ADVANCED DISPLAY OPTIONS TAB
Select
Message bands, custom messages
Use this software tab to set up advanced scrolling user messaging
OTHER DEVICE OPTIONS TAB
Enter
Tag, contact details
Enter
Android passkey (protect logged data)
Enter
Device location
Read/clear
Maximum and minimum reading
Synchronise
Clock
*Logging and configuration software can be downloaded from www.status.co.uk
Status Instruments Ltd, Status Business Park, Gannaway Lane, Tewkesbury,
Gloucestershire, UK, GL20 8FD
Web Page: www.status.co.uk, Email: sales@status.co.uk
Technical Support: support@status.co.uk
Tel: +44 (0) 1684 296818, Fax: +44 (0) 1684 293746
MULTI-FUNCTION ALERT LED
The alert LED normal state is off, on alert the LED will emit a intense
white light pulse every 5 seconds. The LED can be programmed to
pulse on any of the following combined events:
Mode Description
No events The LED never operates, extending battery life.
(Factory default setting).
Trip Alert when relay 1 trip is on.
Process In advanced mode only the alert LED can be made to
alert in any one of eight user-set process value bands. Example, to
alert operator when process value is outside a safe operating range.
The function of the alert LED can be further enhanced with the option
of displaying an alert message in advanced display mode.
NFC LOGGER INTERFACE
The NFC interface allows the instrument to communicate with an
Android device using NFC connectivity.
The prime function of the interface is to read logged data from the
device using a free app, which is available for downloading to
Android devices.
The app allows the user to read existing logs, change the log
manifest, start a new log, synchronise the instrument clock and reset
the maximum/minimum/average readings. Logs can run to a fixed
number and stop or continually roll over; up to 5000 log points can
be recorded. The start of the log can be delayed up to one month.
Note: For larger logs the data may take over a minute to fully
download via the NFC interface.
USB LOGGER INTERFACE (connector inside housing)
The USB interface allows the instrument to communicate with a PC
running the USBLogLink software
The prime function of the interface is to read logged data from the
device using free software available to download.
The software allows the user to read existing logs, change the log
manifest, start a new log, synchronise the instrument clock and reset
the maximum/minimum readings.
USBLogLink is available from the manufacturer or supplier.

Popular Monitor manuals by other brands

HP L1502 Service manual

HP

HP L1502 Service manual

MAXFREE X2 user guide

MAXFREE

MAXFREE X2 user guide

JTL TA210 user guide

JTL

JTL TA210 user guide

Axis T8412 user manual

Axis

Axis T8412 user manual

Planar PL201M manual

Planar

Planar PL201M manual

Memorex MT1701 user guide

Memorex

Memorex MT1701 user guide

Furuno TZT19F installation manual

Furuno

Furuno TZT19F installation manual

ViewSonic G70F - 17" CRT Display user guide

ViewSonic

ViewSonic G70F - 17" CRT Display user guide

Samsung SyncMaster 323T user manual

Samsung

Samsung SyncMaster 323T user manual

Lenovo D19270QP1 user guide

Lenovo

Lenovo D19270QP1 user guide

Samsung S27E332H user manual

Samsung

Samsung S27E332H user manual

Gateway VX760 user guide

Gateway

Gateway VX760 user guide

Philips 200P4MG/00 Specifications

Philips

Philips 200P4MG/00 Specifications

CTX PR1400F user guide

CTX

CTX PR1400F user guide

Iiyama ProLite X436S user manual

Iiyama

Iiyama ProLite X436S user manual

Samsung PN17K Series Service manual

Samsung

Samsung PN17K Series Service manual

NEC LCD2090UXI - MultiSync - 20.1" LCD Monitor user manual

NEC

NEC LCD2090UXI - MultiSync - 20.1" LCD Monitor user manual

ViewSonic PT770 - 17" CRT Display Schematic diagrams

ViewSonic

ViewSonic PT770 - 17" CRT Display Schematic diagrams

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.