Steril-Aire Unitary Kit for Small Air Handlers User manual

1
Installation and Operation Instructions
Unitary Kit for Small Air Handlers
and UVC Kit for Air Handlers
Patents 5,334,347/ 5,817,276,/ 5,866,076/ 6,245,293/ 6,267,924,/ 6,280,686/ 6,313,470/ 6,372,186/
6,423,882,/6,500,267//6,589,476,/6,627,000/ 6,783,578/ 7,140,749,/7,282,728/ 7,459,694 & others pending
Made in USA
NOTE: Read this entire instruction sheet before starting the installation.
IMPORTANT CONSIDERATIONS
Improper installation, adjustment, alteration, service,
maintenance, or use can cause fire, electrical shock, or
other conditions which may cause personal injury or
property damage. Consult your supplier or Steril-Aire for
information or assistance.
Understand the signal words DANGER, WARNING, or
CAUTION. These words are universally used for overall
safety. DANGER identifies the most serious hazards
which will result in severe personal injury or death.
WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify
unsafe practices resulting in minor personal injury or
product and property damage.
WARNING: Before performing maintenance or
service on fixture, ensure unit is unplugged.
Electrical shock can cause injury or death.
CAUTIONS:
Never expose eyes or skin to UVC light.
Wear gloves, face shield/glasses (per ANSI
Z87.1) and cover all exposed skin.
Do not touch Emitter glass without gloves.
Damage to Emitter may result. Oil from
fingerprints will permanently etch glass of
Emitter and weaken structure. If necessary,
clean Emitter using a Steril-Aire cleaning kit
(isopropyl alcohol and a lint-free wipe may
be substituted).
Voltages outside of the range designed for
the unit will void the warranty and do
permanent damage to the entire unit.
Emitter contains a small quantity of mercury.
If an Emitter breaks, clean and dispose of
with care.
UVC energy may cause damage to non-
metallic components except for UV-rated and
HVAC-style drain pans. Select mounting
locations that prevent exposure to
vulnerable components. If mounting
locations are limited, such components shall
be protected with UV resistant material such
as aluminum foil, aluminum duct tape,
metallic shields, etc.
The qualified installer must use factory kits
and accessories when installing this
product.
INSTALLATION &OPERATION
NOTE: ENSURE THAT EMITTER IS INSTALLED BEFORE
POWER IS APPLIED. INSTALLING EMITTER AFTER
POWER HAS BEEN APPLIED WILL TRIGGER THE “END-
OF-LAMP-LIFE CIRCUIT” AND THE EMITTER MAY FAIL TO
LIGHT. IF THIS HAPPENS, SHUT OFF POWER FOR 10
SECONDS AND THEN TURN POWER BACK ON. EMITTER
WILL THEN LIGHT.
1. Consult all applicable codes before installing.
Check fixture label(s) for the correct power
requirements and supply the correct voltage
from a suitable, protected (fused), and grounded
power source.
2. For unitary air conditioners and smaller air
handler units, disconnect power from unit. For
larger units, the Emitter access door or panel
should be interlocked with the power source to
turn Emitter(s) off when the system is opened. It
should have signs (provided) in appropriate
languages alerting maintenance personnel to

2
the possible hazard of looking at or exposing
skin to UVC energy. Service accesses may be
equipped with a glass or Lexan® window
(viewport) to view Emitters. UVC energy does
not penetrate common glass or Lexan®.
3. If applicable, remove outer cover of unitary air
conditioner or air handler.
4. UVC energy may damage some plastics except
HVAC-style drain pans. Wrap suspect items with
aluminum tape; use metallic conduit or use other
appropriate shielding where these items may be
in "line of sight" of the UVC energy.
6. Determine location of the Emitter. (Many types
of unitary air conditioners have a removable
shroud/heating coil assembly that may
adequately accommodate the Emitter.) The
Emitter shall:
oBe at least 1” away from the heating coil.
oNot make contact with the blower.
oProvide direct light onto the cooling coil and
drain pan.
oBe positioned so there is no direct, visible
light from outside of the unitary air
conditioner. A baffle may be installed to
provide any needed light blockage.
CAUTION: Do not drill into coil, refrigerant lines
or other mechanical equipment.
7. Determine an appropriate flat-surfaced location
for mounting the power supply with the provided
screws. Make sure that the power supply’s lead
socket (with extension cord, if applicable) can
reach the pins of the Emitter and that its wires
can reach the power source; mount the power
supply.
3.50
2.08
1.54
3.88 Ø .14
6 INCH
4 PIN
CIRCLINE
SOCKET
10 INCH
UP TO 24 INCH LAMPS
120V P/N 40000121
INSULATED FEMALE
0.25" QUICK-DISCONNECT
9.2
9.8
6-1/2" LONG
POWER SUPPLY 120 TO 230 V
12 TO 42" LAMPS P/N 10000166
1.6
32" LONG
POWER IN
4 PIN CIRCLINE
SOCKET
8. Based on the mounting option selected, use the
following instructions for installation. Install the
Mounting Bracket(s) and Emitter.
oSpring Clips: Mount clips on existing panel
facing the coil. The clips should be attached to
the Emitter on both ceramic ends. If the spring
clips must contact the Emitter glass, 3 wraps of
electrical tape are recommended at the points
of contact to prevent the spring clips from
damaging the Emitter wires along the lamp. If
the wires running the length of the lamp have
been damaged, the warranty is void.
Short Hooks: Remove spine/top plate between
the two upper coils. Cut spine/top plate in order
to accommodate the support wire. Insert the
short hooks over the top of the cooling coils
such that its right angle leg slides between the
fins of the front coil (see below). Ensure that
Emitter ceramic ends rest on the Short Hooks
(see below).
Reinstall the spine/top plate pieces. In some
cases, one Short Hook may be sufficient where
1.25"
2.4"
.98 Ø .18
.60
or 230 V P/N 40000124
6 in. for 120 V, 14 in. for 230 V
Unitary Kit Power
Supply
Air Handler Kit
Power Supply

3
the collared Emitter end can rest in a 13/16” or
7/8” hole drilled on a panel between the coils
and blower wheel on the end of unit (see photo
below).
oFlat Plate Lamp Holder (for metal):
Connect the socket from the power supply
or extension cord to the Emitter pins. Plug
power supply’s power cord into outlet.
Reconnect power and replace outer cover
of the unit. Refer to the images below for
guidance.
oFlat Plate Lamp Holder (for plastic)
Make a ¾” hole in the plastic external
housing or internal plastic plate in the unit.
oInsert Lamp Holder: Drill 1-1/4” hole on a
panel to accommodate component A and
secure A with screws. Slide Emitter partially
through A. Slide component B (collared end
first) onto power supply’s cord or extension
cord and install cord onto Emitter pins (see
Photo 1). Slide Emitter and component B
through A, and twist and lock B under A’s
tabs (see Photo 2).
oU Bracket:
Connect the socket from the power supply to
the Emitter. Snap the Emitter’s ceramic ends
into the spring clips of the U Bracket. Lower
the bracket and Emitter into the desired space
until the Emitter is appropriately facing the
cooling coil. Affix the bracket’s straps onto the
mounting surface with the provided hex
screws.
Component B
Component A
Photo 1
Photo 2
1.25 1.63
2.00
1.50
2.00
2.50
.81
1.62
3/4" HOLE
1.44
2.00
1-1/4" HOLE
O-RING
16
16
12 or 16

4
9. Connect the socket from the power supply or
extension cord to the Emitter pins.
10. Complete all power connections.
11. Reconnect power to the air conditioner. The
Emitter should emit a bright blue hue, indicating
that it is working properly.
12. Replace outer cover of air conditioner.
MAINTENANCE
Emitters need to be periodically replaced to maintain
design output. The change-out basis depends upon
the application, number of times switched on/off per
day, and the hours of operation. Emitters are to be
replaced when output falls to 50% of initial output (or
as specified) by actual radiometer measurements. A
Steril-Aire UVC Radiometer Kit may be used for
such measurements. If a radiometer is unavailable,
Emitters should be replaced after 9,000 hours of
use.
TROUBLESHOOTING
Symptom
Possible Causes
Corrective Action
Emitter does not light
Momentary loss of power
Reset Power Turn off power for 10 Seconds, and then
turn power on.
Poor connection
Check connection to Emitter. Check wiring
connections. Reset Power.
Incorrect wiring
Inspect circuit to wiring diagram.
Dirty pins
Clean pins. Reset Power.
System malfunction
Check system components, interlock door switches,
relays, motion detectors, etc.
Emitter reaching end of life
Replace with new Emitter. Reset Power.
Defective Power supply
Replace Power Supply.
Low Radiometer Reading
or Visibly Weak Emitter
Light
Dirty Emitter or Radiometer
Clean Emitter. Clean Radiometer lens.
Bad Wiring
Check wiring to Emitter.
Emitter reaching end of life
Replace Emitter.
Emitter too Cold
If emitter is at or below 35°F (1°C), Emitter is too cold
to operate properly.
Red/Orange Emitter
Emitter reaching end of life
Replace Emitter.
REPLACEMENT OF EMITTERS
1. Turn off power to the kit.
2. Carefully pull and slide out the Emitter from the
black shrink wrap. Carefully remove Emitter. DO
NOT CUT THE BLACK SHRINK WRAP.
3. Single Ended Emitters must be installed with
silicone grease applied to the female lead
socket. Without silicone grease moisture can
enter the socket and damage the socket, voiding
the warranty.
4. Using a new Emitter and grasping only the
ceramic ends, align the Emitter pins with the
slots on the inside of the black shrink wrap and
carefully push the pins into the slots until seated.
The Emitter is now safely locked into place.
5. Once the kit is powered, the Emitter should emit
a bright blue hue.

5
SPARE OR REPLACEMENT PARTS
DESCRIPTION
PART No’s
Power Supply
Unitary Kit for Small Air Handlers Replacement Power Supply 110 V
40000121
Unitary Kit for Small Air Handlers Replacement PS 208/230 V
40000124
UVC Kit Air Handlers Power Supply Replacement 110-230 V
10000166
Mounting Replacement Parts
Spring Clips Kit
90000832
Short Hooks Kit
11002209
Flat Plate Lamp Holder Kit (for metal)
90000222
Flat Plate Lamp Holder Kit (for plastic)
90000220
Insert Lamp Holder Kit
11005004
U-Bracket 16" Kit
40000133
Emitter Extension Wires for Unitary Kits for Small Air Handlers and
Air Handler Kits
11” Emitter Ext. Wire
50000111-11
32” Emitter Ext. Wire
50000111-32
EMITTERS for Unitary Kits for Small Air Handlers
RGTS 7.5 HO - 7.5" Replacement Emitter for Unitary Kit
22000500
RGTS 10 HO - 10" Replacement Emitter for Unitary Kit
22000400
RGTS 16 HO - 16" Replacement Emitter for Unitary Kit
22000300
RGTS 20 HO - 20" Replacement Emitter for Unitary Kit
22000100
RGTS 24 HO - 24" Replacement Emitter for Unitary Kit
22000200
EMITTERS for Air Handler Kits
GTS 12 VO - 12" Replacement Emitter for Air Handler Kit
21000700
GTS 16 VO - 16" Replacement Emitter for Air Handler Kit
21000100
GTS 20 VO - 20" Replacement Emitter for Air Handler Kit
21000200
GTS 24 VO - 24" Replacement Emitter for Air Handler Kit
21000300
GTS 30 VO - 30" Replacement Emitter for Air Handler Kit
21000400
GTS 36 VO - 36" Replacement Emitter for Air Handler Kit
21000500
GTS 42 VO - 42" Replacement Emitter for Air Handler Kit
21000600
_________________________________________________________________________________________________
Thank you for choosing Steril-Aire, #1 “UVC for HVAC” solution provider worldwide. Please contact your local supplier or Steril-Aire
directly if we can provide any further information or service. Call 1-800-2-STERIL or visit www.steril-aire.com. Your satisfaction is
very important to us.
The health aspects associated with the use of this product and its ability to aid in disinfection of environment air have not been
investigated by UL.
© 2014 Steril-Aire, Inc. All rights reserved. C1678
This manual suits for next models
1
Table of contents
Popular Air Handler manuals by other brands

BLAUBERG Ventilatoren
BLAUBERG Ventilatoren KOMFORT EC S200 user manual

IV Produkt
IV Produkt Envistar Top Series Operation and maintenance manual

Dettson
Dettson SMH-1-DE Installation instructions and homeowner's manual

Nortek
Nortek PAH4VMX installation instructions

Trane
Trane American Standard 4MXD8509A10N0 Installer manual

Vents-us
Vents-us Airvents RH user manual