Sunx LS-400 SERIES User manual

1. Functional Description
1-1. Functional Description.........................P. 1
1-2. Setting Procedure ...............................P. 1
2. Diagram of Functions and Settings
2-1. Diagram of Functions and Settings.....P. 2
3. Others
3-1.
Precautions When Selecting Settings
...P. 3
3-2. Factory Settings ..................................P. 4
3-3. Error Display Indicator Readings ........P. 5
4. Settings for NAVI Mode
4-1. NAVI Mode Functions and Settings....P. 6
4-2. Teaching Mode
(when using normal mode)................P. 11
4-3. Teaching Mode
(when using window comparator mode)
...P. 14
4-4. Teaching Mode
(when using hysteresis mode) ..........P. 18
4-5. Output Operation Setting Mode........P. 22
4-6. Timer Setting Mode...........................P. 23
5. PRO1 Mode
5-1.
PRO1 Mode Functions and Settings
...P. 24
5-2. Response Time Change Function.....P. 25
5-3. Hysteresis Function...........................P. 26
5-4. Shift Function....................................P. 27
5-5. M.G.S. Function ................................P. 28
5-6. Emission Halt Function .....................P. 29
6. PRO2 Mode
6-1.
PRO2 Mode Functions and Settings
...P. 30
6-2. Display Switching Function...............P. 32
6-3. Display Turning Function...................P. 33
6-4. ECO Mode Function..........................P. 34
6-5. Period Holding Function....................P. 35
6-6. Current Value Storage Function........P. 36
6-7.
Stored Value Comparison Function
...P. 37
7. PRO3 Mode
7-1.
PRO3 Mode Functions and Settings
...P. 38
7-2. Data Bank Load Function .................P. 39
7-3. Data Bank Save Function.................P. 40
8. PRO4 Mode
8-1.
PRO4 Mode Functions and Settings
...P. 41
8-2. Copy Function...................................P. 42
8-3. Selection for Transmission Change
to Permit / Not to Permit ...................P. 43
8-4.
External Input Switch Setting Function
...P. 44
8-5. Backup Setting Function...................P. 45
9. PRO5 Mode
9-1.
PRO5 Mode Functions and Settings
...P. 46
9-2. Code Setting Function.......................P. 48
9-3. 0-Adjust Setting Function..................P. 49
9-4. Setting Reset Function......................P. 50
9-5. CUSTOM Mode Display Function.....P. 51
10.PRO6 Mode
10-1.
PRO6 Mode Functions and Settings
...P. 52
10-2. Output 1 Sensing Mode Settings....P. 53
10-3. Output 2 Sensing Mode Settings....P. 55
11.Others
11-1. Key Lock Function...........................P. 56
PRO Mode Operation Guide
LS-400SERIES
DIGITAL LASER SENSOR

Cancel: If the [MODE key] is pressed, the amplifier will return to the previous settings status, immediately before
the [Jog switch] was pressed (the selected setting has been confirmed).
Functional Description
1-1. Functional Description
1-2. Setting Procedure
1
The use [MODE key] and [Jog switch] are utilized to configure various settings.
Press the [MODE key]
(mode selection / cancellation)
1
Turn the [Jog switch] in the ‘’ or
‘’ direction (chooses setting for selection)
2Press the [Jog switch]
(confirms the selected setting)
3
1Output 1 operation
indicator (Orange)
3Laser emission
indicator (Green)
2Select 1 indicator
(Yellow)
1Output 2 operation
indicator (Orange)
2Select 2 indicator
(Yellow) Digital display (Green, Red)
4MODE indicators
6MODE key
5Jog switch
, and are in the correct order for selecting settings.
1
Output 1, 2 operation indicator (Orange)
……
2
Select 1, 2 indicator (Yellow)
……………
3
Laser emission indicator (Green)
………
4
MODE indicators
…………………………
5
Jog switch
…………………………………
6
MODE key
…………………………………
: Lights up during normal sensing operation.
:
When this indicator lights up, in normal mode, the ‘threshold
value’ can be set by utilizing either ‘2-level teaching’, ‘limit
teaching’ or ‘full-auto teaching’. In window comparator mode
and hysteresis mode, the ‘threshold value’ can be set by either
‘1-level teaching’, ‘2-level teaching’ or ‘3-level teaching’
whenever this indicator lights up. Span adjustment can be carried
out when using rising differential and trailing differential modes.
:
When this indicator lights up, the output operation setting can be done.
: When this indicator lights up, timer operation and timer period
setting can be done.
: When this indicator lights up, function is stored in the CUSTOM
mode, can be set.
: When this indicator lights up, further advanced functions, such
as the copying and memory functions, can be set.
Lights up when output 1 or output 2 is ON.
Lights up when output 1 or output 2 is selected.
Lights up when laser is emitted.
RUN (Green)
TEACH (Yellow)
L/D ON (Yellow)
TIMER (Yellow)
CUST (Yellow)
PRO (Yellow)
Moving this switch in the ‘’ or ‘’ direction, allows different items to be viewed
for selection and pressing the switch then confirms the selected setting.
This key is used to select operating modes and to cancel settings while they are
being configured.
Selection and confirmation of settings are performed according to the order of the numbers, as shown on the amplifier:
1
,
2
and
3
.
1

P. 41l
The amplifier of LS-400 series features and settings are generally classified into two main modes; the
‘
NAVI
’
mode
for items and settings that are frequently reconfigured, and the
‘
PRO
’
mode that contains more detailed settings.
Diagram of Functions and Settings
2-1. Diagram of Functions and Settings
2
NAVI
mode
PRO
mode
mFor output 1
Refer to
p. 53l.
mFor
output 2
Refer to
p. 55.
PRO5
PRO4
PRO3
PRO2
PRO1
PRO6
This indicates normal sensing
operation. The threshold value
can be fine-adjusted as well.
Run
RUN
Allows various detailed settings to be
configured, such as optical communications,
save / load and other settings.
Pro
PRO
Shows stored settings for functions.
(Refer to p. 10.)
Custom
CUST
The threshold value can be set by utilizing
either ‘2-level / limit / full-auto teaching’. When
the sensor is in window comparator / hysteresis
mode, the threshold value can be set by either
‘1-level / 2-level / 3-level teaching’. When using
rising / trailing differential mode, ‘span
adjustment’is carried out. (Refer to p. 11.)
Teaching
TEACH Sets output operation either
Light-ON, or Dark-ON. (Refer to
p. 22.)
L-ON / D-ON
L/D ON
Configures operation and period
of the timer. (Refer to p. 23.)
Timer
TIMER
Switches among response
times. (Refer to p. 25.)
Response time change
Sets hysteresis. (Refer to p. 26.)
Hysteresis
Shifts the ‘threshold value’by a
certain percentage increment in
‘limit teaching’. (Refer to p. 27.)
Shift
Selects laser emission to
execute or halt. (Refer to p. 29.)
Emission halt
Sets the digital display to turn
ON / OFF. (Refer to p. 34.)
ECO mode setting
Selects to display peak / bottom
values in the hold condition or
peak / bottom values in the digital
display refleshing condition.
(Refer to p. 35.)
Period hold
Saves current incident light
intensity. (Refer to p. 36.)
Sets the viewing orientation of the
digital display. (Refer to p. 33.)
Display turning
P. 30l
This selects whether the digital display
is fixed at digits, % or peak hold / bottom
hold display, or whether the display can
be selectable. (Refer to p. 32.)
Display switching
This simultaneously displays the saved incident
light intensity and the current incident light
intensity for checking things such as drops in
incident light intensity. (Refer to p. 37.)
Stored value comparison
P. 38l
Loads configuration setting from the data
bank. Select only one amplifier to load or all
amplifiers connected on the right side of the
main unit to load in a single step by using
optical communications. (Refer to p. 39.)
Data bank load
Saves configuration setting from the data
bank. Select only one amplifier to save or all
amplifiers connected on the right side of the
main unit to save in a single step by using
optical communications. (Refer to p. 40.)
Data bank save
Using optical communications,
configuration settings from the
main unit are copied to units
connected on the right side of
the main unit, in a single step.
(Except data bank load / save,
0-adjust function setting and
transmission change to permit /
not to permit.) (Refer to p. 42.)
Copy
mCable type only
mCable type only
Allows not to save the threshold
value, by teaching via external
input, in EEPROM. (Refer to p. 45.)
Backup setting
P. 46l
Allows basic configuration
information to be set in a single
step, by inputting a 8-digit code.
(Refer to p. 48.)
Coding
Forces the numerical value for
incident light intensity to ‘0’on the
digital display. (Refer to p. 49.)
0-adjust setting
All settings, except for data
bank, revert to factory settings.
(Refer to p. 50.)
Reset
Sensing mode that cancels out
slight changes in light intensity so
that only sudden increases in
incident light intensity are sensed.
Rising differential mode
Judges if set two threshold values
are within the required range or not.
This can be selected in 1-level /
2-level / 3-level teaching.
Window comparator mode
Sets a threshold value for ON /
OFF operation.
Normal mode
Changes hysteresis to ignore
small change of incident light
intensity. This can be selected in
1-level / 2-level / 3-level teaching.
Hysteresis mode
Sensing mode that cancels out
slight changes in light intensity so
that only sudden decreases in
incident light intensity are sensed.
Trailing differential mode
Set to OFF when not using
output 2.
Output 2 OFF
Sets receiving light sensitivity
in 3 level (U-LG mode: 4-level).
(Refer to p. 28.)
M.G.S.
Using external input wire,
‘emission halt’, ‘full-auto
teaching’or ‘limit teaching’is
selected. (Refer to p. 44.)
Selects a function in CUSTOM
mode to display. (Refer to p. 51.)
CUSTOM mode display
Allows to ignore copy / load /
save operations in a single step
used by optical communications.
(Refer to p. 43.)
Transmission change
to permit / not to permit
External input
switch setting
() ()
P. 24l
P. 52l
Current value
storage
2

Be sure to set each item after selecting output 1 or output 2.
The items that can be set in output 1 and output 2 respectively are only 1Threshold value, 2Output
operation, 3Timer operation and Timer period, and 4Sensing mode (Output 2 can only be selected in
normal mode). The items other than those are common. (However, in case of setting with the direct code, a
combination of the output 1 / 2 can be set only for output operation. The items other than output operation are
valid only for the output 1.)
To cancel any operation, press the [MODE key]. If the [MODE key] is pressed once, the amplifier will return to
the previous settings status, immediately before the [Jog switch] was pressed and the selected setting has
been confirmed.
Others
3
Press the MODE
key once.
Example: When operating in PRO mode.
Press the Jog
switch once.
When changing the status of any setting, ensure that the selected setting is subsequently confirmed.
If confirmation is not performed, the new setting will not take effect.
Canceling operations
3-1. Precautions When Selecting Settings
Confirming settings
1Select ‘PRO mode’.
1Select ‘response time change’.
2If the [Jog switch] is pressed, the current mode (red) will be
displayed.
* The factory setting is ‘STD (standard)’.
3If the [Jog switch ] is turned, the digital display (red) will blink.
Select the desired mode.
3To cancel the ‘response time change’operation, press the
[MODE key] once.
4
The display will return to the previous [PRO1 mode] selection
screen.
H-SP
(ultra high-speed)
Example: When setting response time change.
FAST
(high-speed)
Press the Jog switch.
Press the Jog switch.
The digital display will quickly blink to confirm the setting.
STD (standard) U-LG
(ultra long-range)
Select the desired mode
by turning the Jog switch.
To cancel
2If the [Jog switch] is pressed once, the amplifier enter the
‘response time change’state.
[ move left side (Green)]
4If the [Jog switch] is pressed, the digital display (red) will
quickly blink, confirming the setting.
The digital display will not blink if the setting has not been
changed.
()
3

Note: Equipped with cable type only.
3-2. Factory Settings
NAVI mode
PRO mode
Item
Response time
Hysteresis
Amount of shift during limit teaching
M.G.S.
Emission halt
Display switching
Display turning
ECO mode
Period hold
Selection for transmission change to permit / not to permit
External input switch setting (Note)
Backup setting (Note)
Code setting
0-adjust setting
Output 1 / 2 sensing mode
Settings
STD (standard)
H-02 (standard)
15 %
Level 3
Laser emission ON
Incident light intensity display only
Digital display turning OFF
ECO OFF
Hold OFF
Lock OFF
Emission halt
OFF
00000000
OFF
Normal mode
Digital display
Item
Threshold value
Output operation
Timer operation
CUSTOM mode display
Settings
Output 1: 40, Output 2: 60
L-ONL-ON (Output 1Output 2)
Without timer (Output 1Output 2)
Response time change
Output 1: , Output 2:
Digital display
Factory settings for the LS-400 series are indicated below:
If the amplifier is reset using the ‘9-4 Setting Reset Function’from ‘PRO5 Mode’on p. 50, the resulting settings
will be those indicated below:
Operation protection
You can use the ‘key lock function’to protect these operations. (Refer to p. 56.)
Key lock function
This function can be used to prevent the operator from accidentally changing the sensor settings.
Automatic interference prevention function
To operate the automatic interference prevention function, you need to install the amplifiers so that they are
directed against each other and carry out optical communication.
The automatic interference prevention function allows up to four sensor heads to be installed so that they are
directed against each other.
(However, the automatic interference prevention function cannot be used in H-SP mode.)
Output switching
Set the sensing mode (PRO6) for output 1 to normal mode beforehand.
In modes other than normal mode, this is fixed at output 1.
Press the MODE key for more than 2 seconds when in NAVI mode. If Output 1
has been selected, the Select 1 indicator (yellow) lights up. If Output 2 is being
selected, the Select 2 indicator (yellow) lights up.
Select 1 indicator
(Yellow) Select 2 indicator
(Yellow)
4

3-3. Error Display Indicator Readings
Digital display Error description Measures
Turn off the power, then check
the load.
The load has short-circuited
and excess current is flowing.
Confirm that all amplifiers are
properly connected to each other.
Communication error has
occurred at time of connection.
Check the sensor head connection
status.
Disconnected sensor head
wire error.
In case of errors, attempt the following measures:
5

Settings for NAVI Mode
4-1. NAVI Mode Functions and Settings
4
RUN :
Normal Sensing Operation
TEACH : Teaching Mode
This indicates normal sensing operation. Threshold value (green) and incident light
intensity (red) are displayed in real time. Manual fine adjustment of the ‘threshold
value’can be performed during normal sensing operation.
The ‘threshold value’can be set with any of the 3 teaching methods, ‘2-level
teaching’, ‘limit teaching’and ‘full-auto teaching’.
This mode sets the ‘threshold value’by utilizing teaching.
When using normal mode
Turn the jog switch to either ‘’(left) or ‘’(right) to increase / decrease the
threshold value.
If there are no key operations after a certain period of time or if the MODE key is
pressed (to change to TEACH), the digital display (green) will blink and the setting
will be confirmed.
2-level teaching is a method of setting the threshold value by teaching the
amplifier two different status conditions - sensing object present and sensing
object absent.
The ‘threshold value’is usually set using this method.
Refer to p. 11 ~ for setting procedure
P. 11
2-level Teaching
Retroreflective type
Retroreflective type
Reflective type
Reflective type
*The incident light intensity display can
display a maximum value of 4,000 in
H-SP (ultra high-speed) mode and
FAST (high-speed) mode. In STD
(standard) mode and U-LG (ultra long-
range) mode, it can display up to a
maximum value of 9,999.
Confirmed
Confirmed
Automatic
AutomaticAutomatic
Turn to ''
Turn
* When you turn the jog switch to ‘’or ‘’in window comparator mode or hysteresis mode, the threshold
value will increase or decrease after the threshold value 1 ‘’or the threshold value 2 ‘’is displayed.
Each time the jog switch is pressed, the display switches between the ‘’threshold value 1 and ‘’
threshold value 2.
After ‘’or ‘’is displayed, the respective threshold value will be displayed.
If you turn the jog switch to ‘’when the output 1 ‘’is displayed, the following will be displayed.
Change
Turn
Threshold value Incident light
intensity
Threshold value fine adjustment function
Teaches only the status condition in which no sensing object is within sensing
range (status in which incident light intensity is stable). This method is used to set
a ‘threshold value’for conducting sensing in the presence of a background, or
when extremely small objects are to be detected.
P. 12
Limit Teaching
Very small object
In [NAVI mode], frequently changed settings can be easily configured.
Settings for four functions can be configured.
6

ON
A
1_SL
2_SL
B
C
0
OFF
P. 16 l
3-level Teaching
This carries out 3-level teaching (P-1, P-2, P-3) and sets the threshold value
(1_SL) between A and B and the threshold value (2_SL) between B and C as
shown in the diagram below.
After teaching, P-1, P-2 and P-3 are automatically assigned in ascending order to
‘A’, ‘B’, and ‘C’.
Time
Incident light
intensity
9,999
Output
(L-ON)
TEACH : Teaching Mode
Refer to p. 14 ~ for setting procedure
P. 14
1-level Teaching
This sets the shift value to any desired value, and sets the threshold values (1_SL,
2_SL) by means of 1-level teaching.
P. 15
2-level Teaching
This carries out 2-level teaching (P-1, P-2) and sets the threshold values (1_SL,
2_SL).
Time
ON
P-11_SL
P-22_SL
0
OFF
Time
Shift value
Shift value
ON
1_SL
2_SL
P-1
0
OFF
Incident light
intensity
9,999
Incident light
intensity
9,999
Output
(L-ON)
Output
(L-ON)
Output
(L-ON)
* In this figure, the incident light intensity of
P-1 is less than that of P-2.
P. 13
Full-auto Teaching
This method is used to set the threshold value while the sensing objects are still
moving on the production line, without stopping the production line.
When using window comparator mode
The ‘threshold value’can be set with any of the 3 teaching methods (‘1-level
teaching’, ‘2-level teaching’and ‘3-level teaching’). By setting two ‘threshold
values’, both ON and OFF can occur between the two threshold value levels.
Hysteresis
9,999 Incident light
intensity
ON
1_SL 2_SL
OFF
7

P. 18
1-level Teaching
This sets the shift value to any desired value, and sets the ON level / OFF level
(1_SL, 2_SL) by means of 1-level teaching (P-1).
Output
(L-ON)
Time
Time
Time
Shift value
Shift value
Incident light
intensity
9,999
Incident light
intensity
9,999
Incident light
intensity
9,999
Output
(L-ON)
Output
(L-ON)
Output
(L-ON)
* In this figure, the incident light intensity of
P-1 is less than that of P-2.
TEACH : Teaching Mode
Refer to p. 18 ~ for setting procedure
When using hysteresis mode
A
1_SL
2_SL
B
C
0
P-11_SL
P-22_SL
0
ON
1_SL
2_SL
P-1
0
OFF
ON
OFF
ON
OFF
9,999 Threshold value
ON
1_SL 2_SL
OFF
P. 19
2-level Teaching
This carries out 2-level teaching (P-1, P-2) and sets the ON level / OFF level
(1_SL, 2_SL).
P. 20 l
3-level Teaching
This carries out 3-level teaching (P-1, P-2, P-3) and sets the ON level / OFF level
(1_SL, 2_SL) between A and B as shown in the diagram below.
After teaching, P-1, P-2 and P-3 are automatically assigned in ascending order to
‘A’‘B’, and ‘C’.
This sets the ON / OFF levels with any of the 3 teaching methods (‘1-level
teaching’, ‘2-level teaching’and ‘3-level teaching’) and sets the hysteresis.
By adjusting the hysteresis, the irregular sections of sensing objects with
irregularities are canceled out so that stable sensing is possible.
8

Span adjustment during differential mode
Time
Threshold
value
d-01
When setting differential mode in PRO mode, the maximum sensitivity (minimum
threshold value) is set.
If the response time is changed in differential
mode, the maximum sensitivity (minimum threshold
value) for that response time is set automatically.
Span adjustment for differential mode can be set
as follows in teaching mode. The threshold value
can be changed using the threshold value fine adjustment function. Refer to
‘threshold value fine adjustment function (P. 6)’ for details.
Changed intensity Turn
Turn
Changed intensity
Changed intensity
Turn
Turn
Short span
(Sudden change) Long span
(Gradual change)
(Note) (Note) (Note)
d-02 d-03 d-04 d-05 d-06 d-07 d-08
ONOFF OFF
OFFON ON
0Threshold value
Threshold
value 1
(1_SL)
Threshold
value 2
(2_SL)
Incident light
intensity
Incident light
intensity
9,999
ONOFF
OFFON
Output
operation
L-ON
D-ON
Output
operation
L-ON
D-ON
* The factory setting is ‘L-ON (Light-ON)’.
0 9,999
L/D ON :
Output Operation Setting Mode
Refer to p. 22 for setting procedure
This mode allows the selection of output operation from either Light-ON, or Dark-ON.
* Products manufactured up until June 2004 (~ Lot No.: 4F□) are set in 5 steps (d-01 to d-05).
When using differential (rising or trailing) mode
For L-ON, the output turns ON when the incident light intensity is greater than the
ON level (2_SL), and the output turns OFF when the incident light intensity is less
than the OFF level (2_SL).
For D-ON, the output turns OFF
when the incident light intensity
is greater than the OFF level
(2_SL), and the output turns ON
when the incident light intensity
is less than the ON level (1_SL).
When using hysteresis mode
When using normal mode
When using window comparator mode
Incident
light
intensity
Changed intensity
Changed intensity
ON level or OFF level
(2_SL)
OFF level or ON level
(1_SL)
ON or OFFOFF ON
OFF or ONON OFF
Output
operation
L-ON
D-ON
0 9,999
Incident
light
intensity
Only sudden changes in the light intensity are sensed, so that objects such as
glass edges can also be sensed with stability.
When set to ‘L-ON’, the output will be ON if the incident light intensity becomes
greater than the ‘threshold value’.
When set to ‘D-ON’, the output will be ON if the incident light intensity becomes
less than the ‘threshold value’.
When set to ‘L-ON’, if the incident light intensity is between the two ‘threshold
value’ levels, the output will be ON. If the incident light intensity is outside of the
two threshold value levels, the output will be OFF.
When set to ‘D-ON’, if the incident light intensity is between the two ‘threshold
value’ levels, the output will be OFF. If the incident light intensity is outside of the
two threshold value levels, the output will be ON.
TEACH : Teaching Mode
9

This sets timer operation and the timer period. The setting can be selected from
Without timer / OFF-delay / ON-delay / ONE-SHOT timer. The factory setting is
‘Without timer’.
Timer period: Approx. 1 to 9,999 ms
* When using rising / trailing differential mode, the timer is set automatically to
ONE-SHOT timer.
* For products manufactured up until June 2004 (~ Lot No.: 4F□) timer modes
other than ONE-SHOT timer cannot be used in differential modes.
When using rising differential mode
Output
operation
L-ON
D-ON
Time
ON
Output
operation
L-ON
D-ON
ON
TT
OFF
When using trailing differential mode
Time
ON
OFF
OFF
ON
OFF
TT
Incident
light
intensity
Incident
light
intensity
*The output time ‘T’can be set by changing
the timer period in timer setting mode
(initial value: 10 ms).
*The output time ‘T’can be set by changing
the timer period in timer setting mode
(initial value: 10 ms).
This is used to make detailed settings for functions selected in PRO5 mode. Out of
the response time change function, M.G.S. function, emission halt function, data
bank function and code setting function, one of these functions selected in PRO5
mode can be set in detail. Refer to the pages for each function for details on the
setting methods.
CUST : CUSTOM Mode
TIMER :
Timer Setting Mode
Refer to p. 23 for setting procedure
Sensing condition
Beam-received
Beam-interrupted
Output operation
Timer operation ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
(Without Timer) Light-ON
(ON-delay)
Dark-ON
Light-ON
Dark-ON
Light-ON
Dark-ON
Light-ON
Dark-ON
(OFF-delay)
(ONE-SHOT)
T1
T1
T1
T1
T1
T1
Timer period T1Approx. 1 ms to 9,999 ms
* OFF-delay:
ON-delay:
ONE-SHOT:
Extends the output signal for a fixed period of time.
This function is useful if the output signal is so short that the connected device cannot
respond.
Neglects short output signals.
As only long signals are extracted, this function is useful for detecting if a line is clogged, or
for sensing only objects taking a long time to travel.
Outputs a fixed width signal upon sensing.
This function is useful when the input specifications of the connected device require a
signal of fixed width. Of course, it is also useful for extending a short width signal to a
desired width.
Time chart
For L-ON, output is ON for a constant period of time when the incident light
intensity is rising.
For D-ON, output is OFF for a constant period of time when the incident light
intensity is rising.
For L-ON, output is ON for a constant period of time when the incident light
intensity is trailing.
For D-ON, output is OFF for a constant period of time when the incident light
intensity trailing.
10

4-2. Teaching Mode (when using normal mode)
2-level teaching is a method of setting the ‘threshold value’by teaching the amplifier two different
status conditions - sensing object present and sensing object absent. The ‘threshold value’is
usually set using this method.
The ‘threshold value’can be set by utilizing three kinds of teaching, whichever ‘2-level teaching’, ‘limit teaching’or
‘full-auto teaching’.
* Select output 1 and output 2 and the sensing mode beforehand.
Place a sensor head within sensing range.
Press the
MODE key once.
Status condition - sensing object is present
Press the
Jog switch.
Press the
Jog switch.
()
Status condition - sensing object is absent
Difference between incident light
intensities is not great enough.
Stable sensing
Press the
MODE key 5 times.
2-level Teaching
1Select ‘TEACH mode’by pressing the [MODE key] once.
2Press the [Jog switch] when in the status condition of -
sensing object is present.
4Press the [Jog switch] when in the status condition of -
sensing object is absent.
7The incident light intensity (red) will again be displayed,
indicating that configuration is now complete.
8By pressing the [MODE key] 5 times, the amplifier will return
to ‘RUN mode’(normal sensing operation).
5The digital display will again blink the incident light intensity
reading (red) and the ‘threshold value’will be set to a value
midway between the incident light intensities when the
sensing object is present and when it is absent. The blinking
MODE indicator / TEACH will stop blinking and continuously
light up.
* Fine adjustment of the ‘threshold value’can be performed
in the RUN mode.
6The set ‘threshold value’(green) will indicate and the
sensing stability status will be displayed.
•When stable sensing can be performed
nThe digital display will blink the word ‘’(red).
• When stable sensing cannot be performed
n The digital display will blink the word ‘’(red).
3The digital display will indicate the incident light intensity
reading (green), then the MODE indicator / TEACH (yellow)
will blink.
This indicates that the second point item is now ready for
input.
11

Place a sensor head within sensing range.
Press the
MODE key once.
Press the
Jog switch.
Status condition - sensing object is absent
Press the
MODE key 5 times.
Shifting can be performed. Shifting cannot be performed.
Teaches only the status condition in which no sensing object is within sensing range (status in
which incident light intensity is stable). This method is used to set a ‘threshold value’for
conducting sensing in the presence of a background, or when extremely small objects are to be
detected.
Limit Teaching
The digital display
will scroll.
Turn the Jog switch
in the ‘’or ‘’
direction.
1Select ‘TEACH mode’by pressing the [MODE key] once.
2Press the [Jog switch] when in the status condition of -
sensing object is absent.
3The digital display will indicate the incident light intensity
reading (green), then the MODE indicator / TEACH (yellow)
will blink.
4Turn the [Jog switch] in either the ‘’or ‘’direction.
When using retroreflective type sensor head
When using reflective type sensor head
•If the switch is turned toward the ‘’direction, the digital
display will scroll from the left to the right and the threshold
value will be shifted down by approx. 15 %, to a value lower
than the incident light intensity displayed (high sensitivity).
•If the switch is turned toward the ‘’direction, the digital
display will scroll from the right to the left and the threshold
value will be shifted up by approx. 15 %, to a value higher
than the incident light intensity displayed (low sensitivity).
*
The initial factory-set value of the shift amount is approx. 15 %.
The shift amount can be changed by utilizing the ‘5-4. Shift
Function’from ‘PRO1 Mode’, described on p.27. (The
percentage adjustment is variable from approx. 5 % to 200 %,
in increments of 1 %.)
6
The incident light intensity (red) will again be displayed,
indicating that configuration is now complete.
7By pressing the [MODE key] 5 times, the amplifier will return
to ‘RUN mode’(normal sensing operation).
5The set ‘threshold value’(green) will indicate and the
judgement on whether the shift amount can be shifted or not
will be displayed.
•When the shifting can be performed
nThe digital display will blink the word ‘’.
•When the shift amount cannot be changed because the
setting exceeds the upper or lower display limit (the value
is reset to within the upper and lower limits)
nThe digital display will blink the word ‘’.
12

Full-auto teaching is used to set the threshould value while the sensing objects are still moving on
the production line, without stopping the production line.
Full-Auto Teaching
Place a sensor head within sensing range.
Press the
MODE key once.
Hold down the
Jog switch.
Status condition-moving the production line
Difference between incident light
intensities is not great enough.
Stable sensing
Press the
MODE key 5 times.
1Select ‘TEACH mode’by pressing the [MODE key] once.
2Hold down the [Jog switch] for 0.5 sec. or more when in the
status condition when the object moving on the production
line.
4Incident light intensity (red) will blink on the digital display,
and the ‘threshold value’will be set to a value midway
between the incident light intensities when the sensing
object is present and when it is absent.
5The set ‘threshold value’(green) will indicate and the
judgement on the stability of sensing will be displayed.
•When stable sensing can be performed
nThe digital display will blink the word ‘’(red).
• When stable sensing cannot be performed
n The digital display will blink the word ‘’(red).
3‘’(green) is displayed on the digital display, then the
MODE indicator / TEACH (yellow) will blink. Release the jog
switch when the object has passed.
7By pressing the [MODE key] 5 times , the amplifer will return
to ‘RUN mode’(nomal sensing operation).
6The incident light intensity (red) will again be displayed,
indicating that configuration is now complete.
13

This is the method of setting the threshold values
(1_SL, 2_SL) by one level (P-1) teaching. The shift
value can be set as desired.
* The shift value units can be selected from two units:
‘digit’or ‘%’.
* The shift value of the factory setting is set to ‘100’of
‘digit’units.
To set the shift value, refer to the section entitled ‘10-2.
Output 1 Sensing Mode Settings’from ‘PRO6 Mode’
on p. 53.
4-3. Teaching Mode (when using window comparator mode)
1-level Teaching
Time
Shift value
Shift value
ON
1_SL
2_SL
P-1
0
OFF
Incident light
intensity
9,999
Output
(L-ON)
The ‘threshold value’can be set using ‘1-level teaching’, ‘2-level teaching’or ‘3-level teaching’. In window
comparator mode, teaching is performed using the teaching methods described in the section entitled ‘10-2.
Output 1 Sensing Mode Settings’from ‘PRO6 Mode’on p. 53.
Change the teaching method using ‘10-2. Output 1 Sensing Mode Settings’from ‘PRO6 Mode’on p. 53
beforehand.
* Window comparator mode can be set done for output 1 only.
* The factory setting is ‘1-level teaching’.
Press the
MODE key once.
Blinking by turns.
The status condition when a sensing object is
present that can be used as a standard.
Upper limit value 2_SL
Press the
Jog switch.
Incident light
intensity for P-1.
Lower limit value 1_SL
The symbol ‘’will be
displayed repeatedly. Press the
MODE key 5 times.
If the shift value has
been set to 500. Upper and lower limits have
not been correctly set.
1Select ‘TEACH mode’by pressing the [MODE key] once.
2The current teaching method (green) and incident light
intensity (red) will be displayed and the amplifier will enter
the ‘P-1’setting state.
3If the [Jog switch] is pressed while in the status condition
when a sensing object is present that can be used as a
standard, then the display will blink the incident light intensity
reading (red).
6By pressing the [MODE key] 5 times, the amplifier will return
to ‘RUN mode’(normal sensing operation).
‘Lower limit value 1_SL’(green) and incident light intensity
(red) will be displayed.
5Then the setting for ‘upper limit value 2_SL’(green) will be
displayed.
4The display will indicate whether the upper and lower
threshold value limits have been correctly set and the setting
for ‘lower limit value 1_SL’(green) will be displayed.
• If ‘’(red) is blinking…the upper and lower limits have
been set correctly.
• If ‘’(red) is blinking…the upper and lower limits have
not been set correctly.
* The shift value of the factory setting is set to ‘100’of ‘digit’
units.
To set the shift value, refer to the section entitled ‘10-2.
Output 1 Sensing Mode Settings’from ‘PRO6 Mode’on
p. 53.
14

2-level Teaching This is a method of setting the threshold values
(1_SL, 2_SL) by two levels (P-1, P-2) teaching.
Time
ON
P-11_SL
P-22_SL
0
OFF
Incident light intensity
9,999
Output
(L-ON)
Press the
MODE key once.
Blinking by turns.
Press the
Jog switch.
Press the
Jog switch.
Incident light
intensity for P-1.
Incident light
intensity for P-2.
Upper limit value 2_SL
Lower limit value 1_SL
The symbol ‘’will be
displayed repeatedly. Press the
MODE key 5 times.
Upper and lower limits have
not been correctly set.
The status condition when a sensing object is present
that can be used as a standard for the lower limit.
The status condition when a sensing object is present
that can be used as a standard for the upper limit.
2The current teaching method (green) and incident light
intensity (red) will be displayed and the amplifier will enter
the ‘P-1’setting state.
4The amplifier has entered the ‘P-2’setting state and ‘’
(green) will blink.
7Then the setting for ‘upper limit value 2_SL’(green) will be
displayed.
8By pressing the [MODE key] 5 times, the amplifier will return
to ‘RUN mode’(normal sensing operation).
‘Lower limit value 1_SL’(green) and incident light intensity
(red) will be displayed.
6The display will indicate whether the upper and lower limits
have been correctly set and the setting for ‘lower limit value
1_SL’(green) will be displayed.
• If ‘’(red) is blinking…the upper and lower limits have
been set correctly.
• If ‘’(red) is blinking…the upper and lower limits have
not been set correctly.
5If the [Jog switch] is pressed while in the status condition
when a sensing object is present that can be used as a
standard for the upper limit, then the display will blink the
incident light intensity reading (red).
When using retroreflective type sensor head
•Press the [Jog switch] for the sensing object that has the
least amount of interrupted light.
When using reflective type sensor head
•Press the [Jog switch] for the sensing object with the
greatest incident light intensity.
3If the [Jog switch] is pressed while in the status condition
when a sensing object is present that can be used as a
standard for the lower limit, then the display will blink and
indicate the incident light intensity reading (red).
When using retroreflective type sensor head
•Press the [Jog switch] for the sensing object that has the
greatest amount of interrupted light.
When using reflective type sensor head
•Press the [Jog switch] for the sensing object with the lowest
intensity of incident light.
Note) Even if procedures
3
and
5
are reversed, teaching for a
sensing object with low intensity incident light will
automatically cause the setting of ‘lower limit value 1_SL’.
1Select ‘TEACH mode’by pressing the [MODE key] once.
15

ON
A
1_SL
2_SL
B
C
0
OFF
3-level Teaching This is a method of setting the threshold range by
three levels (P-1, P-2, P-3) teaching and set the
threshold values at the middle of ‘A’and ‘B’(1_SL) and
‘B’and ‘C’(2_SL).
After teaching, P-1, P-2 and P-3 are automatically
assigned in ascending order to ‘A’, ‘B’, and ‘C’.Time
Output
(L-ON)
Press the
MODE key once.
Blinking by turns.
Press the
Jog switch.
Press the
Jog switch.
Incident light
intensity for P-1.
Incident light
intensity for P-2.
The status condition when sensing object ‘A’is present
that has the lowest intensity of incident light.
The status condition when sensing object ‘B’is present
that has an incident light intensity in between that of
sensing object ‘A’and sensing object ‘C’.
Incident light intensity
9,999
1Select ‘TEACH mode’by pressing the [MODE key] once.
4The amplifier has entered the ‘P-2’setting state and ‘’
(green) will blink.
6
The
amplifier
has entered the ‘P-3’setting state and ‘’
(green) will blink.
2The current teaching method (green) and incident light
intensity (red) will be displayed and the amplifier will enter
the ‘P-1’settting state.
3If the [Jog switch] is pressed while in the status condition
when sensing object ‘A’is present that has the lowest
intensity of incident light, then the display will blink the
incident light intensity reading (red).
5If the [Jog switch] is pressed while in the status condition
when sensing object ‘B’is present that has an incident light
intensity in between that of sensing object ‘A’and sensing
object ‘C’, the display will blink the incident light intensity
reading (red).
16

The status condition when sensing object ‘C’ is present
that has the greatest intensity of incident light.
Press the
Jog switch.
Incident light
intensity for P-3.
Upper limit value 2_SL
Lower limit value 1_SL
Upper and lower limits have
not been correctly set.
The symbol ‘ ’ will be
displayed repeatedly.
Press the
MODE key 5 times.
7If the [Jog switch] is pressed while in the status condition
when sensing object ‘C’ is present that has the greatest
intensity of incident light, the display will blink the incident
light intensity reading (red).
8The display will indicate whether the upper and lower limits
have been correctly set and the setting for ‘lower limit value
1_SL’ (green) will be displayed.
• If ‘ ’ (red) is blinking…the upper and lower limits have
been set correctly.
• If ‘ ’ (red) is blinking…the upper and lower limits have
not been set correctly.
9Then the setting for ‘upper limit value 2_SL’ (green) will be
displayed.
0By pressing the [MODE key] 5 times, the amplifier will return
to ‘RUN mode’ (normal sensing operation).
‘Lower limit value 1_SL’ (green) and incident light intensity
(red) will be displayed.
17

This is the method of setting the ON Level / OFF Level
(1_SL, 2_SL) by one level (P-1) teaching. The shift
value can be set as desired.
* The shift value units can be selected from two units:
‘digit’or ‘%’.
* The shift value of the factory setting is set to ‘100’of
‘digit’units.
To set the shift value, refer to the section entitled
‘10-2. Output 1 Sensing Mode Settings’from
‘PRO6 Mode’on p. 53.
4-4. Teaching Mode (when using hysteresis mode)
1-level Teaching
Time
Shift value
Shift value
1_SL
2_SL
P-1
Incident light
intensity
9,999
Output
(L-ON)
The ‘ON Level / OFF Level’can be set using ‘1-level teaching’, ‘2-level teaching’or ‘3-level teaching’. In
hysteresis mode, teaching is performed using the teaching methods described in the section entitled ‘10-2.
Output 1 Sensing Mode Settings’from ‘PRO6 Mode’on p. 53
Change the teaching method using ‘10-2. Output 1 Sensing Mode Settings’from ‘PRO6 Mode’on p. 53
beforehand.
* Hysteresis mode can be set for output 1 only.
* The factory setting is ‘1-level teaching’.
OFF or ON level 1_SL
ON or OFF level 2_SL
Press the
MODE key once.
Blinking by turns.
The status condition as a standard.
Press the
Jog switch.
Incident light
intensity for P-1.
The symbol ‘’will be
displayed repeatedly. Press the
MODE key 5 times.
If the shift value has
been set to 200. ON or OFF level have
not been correctly set.
ON
0
OFF
1Select ‘TEACH mode’by pressing the [MODE key] once.
2The current teaching method (green) and incident light
intensity (red) will be displayed and the amplifier will enter
the ‘P-1’setting state.
3If the [Jog switch] is pressed while in the status condition as
a standard, then the display will blink the incident light
intensity reading (red).
5Then the setting for ‘ON or OFF level 2_SL’(green) will be
displayed.
6By pressing the [MODE key] 5 times, the amplifier will return
to ‘RUN mode’(normal sensing operation).
‘OFF or ON level 1_SL’(green) and incident light intensity
(red) will be displayed.
4The display will indicate whether the ON and OFF level have
been correctly set and the setting for ‘OFF or ON level 1_SL’
(green) will be displayed.
• If ‘’(red) is blinking…the ON and OFF level have
been set correctly.
• If ‘’(red) is blinking…the ON and OFF level have not
been set correctly.
* The shift value of the factory setting is set to ‘100’of ‘digit’
units.
To set the shift value, refer to the section entitled ‘10-2.
Output 1 Sensing Mode Settings’from ‘PRO6 Mode’
on p. 53.
18

2-level Teaching This is a method of setting the ON level / OFF
level (1_SL, 2_SL) by two levels (P-1, P-2)
teaching. Time
ON
P-11_SL
P-22_SL
OFF
Incident light intensity
9,999
Output
(L-ON)
0
Press the
MODE key once.
Blinking by turns.
The status condition as a standard for the OFF or ON level.
The status condition as a standard for the ON or OFF level.
Incident light
intensity for P-1.
Incident light
intensity for P-2.
Press the
Jog switch.
Press the
Jog switch.
OFF or ON level 1_SL
ON or OFF level 2_SL
Upper and lower limits have
not been correctly set.
The symbol ‘’will be
displayed repeatedly. Press the
MODE key 5 times.
1Select ‘TEACH mode’by pressing the [MODE key] once.
2The current teaching method (green) and incident light
intensity (red) will be displayed and the amplifier will enter
the ‘P-1’setting state.
4
The amplifier has entered the ‘P-2’setting state and ‘’
(green) will blink.
7Then the setting for ‘ON or OFF level 2_SL’(green) will be
displayed.
8By pressing the [MODE key] 5 times, the amplifier will return
to ‘RUN mode’(normal sensing operation).
‘OFF or ON level 1_SL’(green) and incident light intensity
(red) will be displayed.
6The display will indicate whether the ON and OFF level have
been correctly set and the setting for ‘OFF or ON level 1_SL’
(green) will be displayed.
• If ‘’(red) is blinking…the ON and OFF level have
been set correctly.
• If ‘’(red) is blinking…the ON and OFF level have not
been set correctly.
5If the [Jog switch] is pressed while in the status condition as
a standard for the ON level or OFF level, then the display will
blink the incident light intensity reading (red).
When using retroreflective type sensor head
•Press the [Jog switch] when the interrupted light is the least
amount.
When using reflective type sensor head
•Press the [Jog switch] when the incident light is the greatest
intensity.
3If the [Jog switch] is pressed while in the status condition as
a standard for the OFF level or ON level, then the display will
blink the incident light intensity reading (red).
When using retroreflective type sensor head
•Press the [Jog switch] when the interrupted light is the
greatest amount.
When using reflective type sensor head
•Press the [Jog switch] when the incident light is the lowest
intensity.
Note)
Even if procedures
3
and
5
are reversed, teaching in
condition of low intensity of incident light will automatically
cause the setting of ‘OFF level or ON level 1_SL’.
19
Table of contents
Other Sunx Measuring Instrument manuals