4.2. Measuring voltage and current (0 to 50 mV, 0 to 1 V, 0 to 2 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA)
This section describes how to configure the PTI-PM for measuring voltage or current signals from an external
transducer. You must select “U”or “I”as your desired input type, as explained in Section 4.1. The display has
to show “InP.”
■Press Button 1. The display shows “SEnS.”
■Select the desired input signal using button 2 or button 3.
Display Input Signal
(Voltage Measuring)
10.00 0 to 10 V
0 to 2 V
0 to 1 V
0 to 50 mV
1.00
2.00
0.050
Display Input Signal
(Current Measuring)
4 to 20 4 to 20 mA
0 to 20 mA0-20
■Confirm the selected input signal by pressing button 1. The display shows “SEnS”again.
■Press button 1 again. The display will show “dP”(decimal point).
■Select the desired decimal point place by pressing button 2 or button 3.
■Confirm the selected decimal point by pressing button 1. The display shows “dP”again.
■Press button 1 again. The display will show “di.Lo”(Display Low = low display value).
■Use button 2 or button 3 to select the desired value the device should display when a 0 mA, 4 mA, or 0 V
input signal is attached.
■Confirm the selected value by pressing button 1. The display shows “di.Lo”again.
■Press button 1 again. The display will show “di.Hi”(Display High = high display value).
■Use button 2 or button 3 to select the desired value the device should display when a 20 mA, 50 mV,
1 V, 2 V, or 10 V input signal is attached.
■Confirm the selected value by pressing button 1. The display shows “di.Hi”again.
■Press button 1 again. The display will show “Li”(Limit = measuring range limit).
■Use button 2 or button 3 to select the desired measuring range limit.
Display Measuring Input Limit Note
Off Deactivated
Active (displays error)
Active (displays the
selected limit)
Exceeding the measuring range limit is tolerable for about 10 % of the selected
input signal.
On.er
On.rg The measuring range limit is bound by the input signal. When outside the input
signal, the device will display the selected lower / upper display value.
The measuring range limit is bound by the input signal. When outside the input
signal, the device will display an error message.
Note: When exceeding the measuring range limit greater than 10 % independently from the setting, the device will always
display an error message (“Err.1“ or “Err.2“).
■Press button 1 to confirm the selection. The display shows “Li”again.