Tatsuta Electric Wire & Cable AD-AS-1AM User manual

Warnings
Strict Prohibitions
Checkpoints
Do not install the detector in the following locations!
Water Leakage Detector
AD-AS-1AM
Instruction Manual
We thank you for using our Model AD-AS-1AMWater Leakage Detector.
Be sure to read the following instructions before installing, adjusting and using the detector.
 Use the detector in a working environment with a temperature range between -10˚C, and 50˚C and a
humidity range between 35%RH and 85%RH.
 Avoid using the detector near sources of vibration, harmful gas, or strong electromagnetic induction.
 For connection to the power supply, avoid using receptacles (sockets); use fixed wiring connection.
 Use our products for sensors and break detection terminals (excepting AD-LS sensors and ZT-L2
products).
 Be sure to affix the insulating sheet to the terminal block, fix the outer cover and check detector operation.
 Smoke or abnormal sound occurrence with the power indication LED turned off indicates detector failure.
Switch off the main power breaker, stop using the detector and contact us.
 Check at least once every six months to confirm that detector is operating normally. At the same time,
check to see that screws on different parts of the detector are tightened properly.
 Be careful of water-repellant substances, such as oil, adhering to sensor surface and interior; this may
interfere with correct detector operation.
 If a sensor is stained with dirty water, replace it with a new one.
This detector is delivered to customers after strict quality control and inspection. Should it fail under normal
usage, we will repair it free of charge or replace it during the warranty period (within one year of delivery).
* Detector failure due to natural disaster, fire, unauthorized repair, dropping or damage after purchase is not
covered by the warranty.
Ask place of purchase for the guarantee document.
When asking for the guarantee document, provide detector serial number (indicated on label on right-side
face of the right-side terminal block).
Handling Method
 Typical Configuration of Water Leakage Detection System
* Using vinyl tape or similar material, insulate the connections of water leakage sensor break detection
terminals and instrumentation wires (it is recommended that they be housed in a box.), and fix them at a
location above the floor to keep them from getting wet.
 Operating the Detector and Checking Detector Operations
 Checking power-on
Power-on causes the power indicator LED (yellow) to light.
 Checking water leakage detection function
 Checking water leakage detection test function:
Pressing buzzer stop and reset buttons simultaneously for three seconds or more causes output of
simulated water leakage alarms (water leakage indicator LED flashing output, buzzer sounding
output,and water leakage alarm contact output).
 Checking water leakage detection function with water:
By allowing tap water to drip on the sensor, you can check how well the sensor detects water
leakage. Wipe off water with dry cloth after check to restore sensor to operational state for water
leakage detection.
 Checking of the break detection function
 Checking break detection test function:
You can check break detection function without removing break detection terminal or sensor.
Pressing buzzer stop and reset buttons simultaneously for three seconds or more causes output of
simulated water leakage alarm; pressing both of them for three seconds after this causes output of
simulated break alarms (break indicator LED (green) flashing output; buzzer sounding output; break
alarm contact output).
Note: Break alarm is also output when the break detection function is “not activated.”
 Checking actual break detection function:
Remove outer cover, insulating sheet and the terminals connected to sensor (I) on the terminal block
to check actual break detection function.
After checking, reattach terminals, insulating sheet and outer cover.
 Buzzer stop button
If this button is pushed while buzzer is sounding, buzzer stops sounding until next alarm.
 Reset button
 If reset button is pushed while the alarm is being held with alarm hold setting activated, alarm output is
reset.
 If reset button is pushed with alarm hold setting not activated or under normal conditions, lamp test can
be performed.
All LEDs are lit and buzzer is sounds (with monotonous tone). Under this condition, control output
contacts do not operate.
<<<Important safety instructions>>>
Erroneous operation of this water leakage detector not complying with the warning labels or the following
warnings may lead to fatal accident, serious injury, electric shock, fire, or detector failure.
 Never modify or disassemble the detector.
 Observe ratings of power supply voltage and contact capacity.
 Allow only persons responsible for handling this product to perform installation work on it or to adjust
or inspect it with the outer cover opened.
 After the detector is installed, do not leave it with the cover open, except for inspection and
maintenance purposes.
 Do not touch any internal component with wet hands.
 When performing maintenance on the product, avoid using organic solvent. Use dry wiping rags or a
small amount of diluted neutral detergent.
Note: Be careful not to allow detergent solution to remain on the sensor.
 Check detector supply voltage and rated voltage before installing.
 When installing and electrically connecting the detector, follow the instructions in the instruction
manual.
 When inspecting and maintaining the detector, follow the instructions in the instruction manual.
 When using control output contacts, check the contact rated load in the instruction manual.
 Locations easily accessible to the general public
 Locations close to sources of vibration, organic gas or strong electromagnetic induction.
 Locations with much waste and dust
 Locations where there is possibility of water leakage and temperature and humidity are high
 Detector Specification
Rated voltage AC 100 V to 240 V (common to 50 Hz/60 Hz); voltage fluctuation: within ±10%
Sensor interelectrode
voltage
Break detection terminal not provided: AC 2.8 V or less
Break detection terminal provided: AC 1.5 V or less
Interelectrode
short-circuit current AC 0.13 mA or less
Power consumption 3 VA or less
Working ambient
temperature and
humidity
-10˚C to 50˚C (no icing); 35%RH to 85%RH (no condensation)
Outside dimensions,
weight and color W120 ´ H124 ´ D55 mm; 300 g ± 20 g; ivory white
Number of sensor
circuits One
Water leakage
detection and recovery
levels
Factory default setting: Break detection function “activated”
Detection level: 5.0 kΩ*1/recovery level: 6.7 kΩ ± 20%
*1: Combined resistance of 6.7 kΩ for an isolated sensor and 20 kΩ for a break detection
terminal (ZT-2)
* Sensor with break detection terminal or break detection terminal (ZT-1) must be
connected.
Alarm output
Buzzer; water leakage indicator LED (red) flashing; break indicator LED (green) flashing;
water leakage alarm contacts (no voltage, 1c); break alarm contacts (no voltage, 1c)
Resistive load Inductive load
Rated load AC 250 V, 6.0 A
DC 24 V 6.0 A
AC 250 V 3.0 A
DC 24 V 3.0 A
Relay contacts: FTR-LYCA005 according to catalog of Fujitsu Component Limited
 Detector Setting Method
 Dip switch (DIP-SW) setting
To select dip switch (DIP-SW) positions, use a thin flat-blade screwdriver to move tiny sliders.
Setting item Description Factory default setting
Break detection
setting
Break detection setting
activated/not activated
Break detection setting
activated DIP-SW-4 ON
Alarm hold setting
Alarm hold setting
activated/not activated
Alarm hold setting not
activated DIP-SW-3 OFF
Fail-safe setting Fail-safe output
activated/not activated
Fail-safe output not
activated DIP-SW-2 OFF
Buzzer sound
setting
Buzzer sound setting
activated/not activated
Buzzer sound setting
activated DIP-SW-1 ON
* “Alarm hold” denotes function of holding alarm until reset button is pressed.
* “Fail-safe setting” denotes setting to reverse contact logic so that system can judge detector power
supply OFF state to be an abnormality. This setting reverses action of N.O. (Normally Open) contacts
and N.C. (Normally Close) contacts. Under this setting, power-on causes contacts to operate.
 Knob adjustment
Use a thin flat-blade screwdriver to adjust VR-1 and VR-2.
Setting item Adjustment range Factory default setting
Buzzer volume
adjustment
Buzzer volume between
“low” and “high” Buzzer volume “high”
VR-1
Clockwise to
maximum
Detection level
adjustment
2k-5k-14 k
W
±20% 5.0 kW ±20% VR-2 Middle
position
* Factory default setting is value at which water leakage sensor*1 can properly detect the presence of
common city water.
*1: Line sensors (AD-S, AD-RS, AD-HS, and FR-AD): within 100 m; point sensor (AD-PA)
Our suggestions: When detecting a low conductivity liquid or using a low-sensitivity water leakage
sensor (such as AD-FH), raise detection level; conversely, when detecting a high conductivity liquid or
installing detector in a high-temperature, high-humidity environment, lower detection level.
Water leakage
detection/recovery level ±20%
With break detection setting
“activated”: (Factory default
setting)
With break detection setting
“not activated”
Adjuster position Detection level
Recovery level
Detection level
Recovery level
Adjuster at the minimum
setting 2.0 kW 2.8 kW 2.2 kW 3.3 kW
3.0 k
W
4.2 k
W
3.5 k
W
5.3 k
W
4.0 k
W
5.5 k
W
5.0 k
W
7.5 k
W
Adjuster at middle setting
(Factory default setting) 5.0 kW 6.7 kW 6.7 kW 10.1 kW
6.0 k
W
7.8 k
W
8.6 k
W
12.9 k
W
7.0 k
W
9.0 k
W
10.8 k
W
16.2 k
W
8.0 k
W
10.0 k
W
13.3 k
W
20.0 k
W
9.0 k
W
11.0 k
W
16.4 k
W
24.6 k
W
Adjuster at maximum setting
14.0 k
W
15.6 k
W
46.7 k
W
70.0 k
W
Cautions in installing and handling the detector
Maintenance and inspection
Guarantee
ON
12 3 4
AD-AS-1 AM-1
VR–1:
Buzzer volume
adjusting knob
VR–2:
Detection level
adjusting knob
DIP-SW:
Function-setting
switches
* After peeling off ins
ulating sheet and changing
settings, be sure to reattach sheet.
Insulating sheet
ON
1234
DIP-SW
VR
AC power supply
Instrumentation line for
control output contacts
Instrumentation line for sensors:
0.3 SQ or more, within 100 m
Water leakage sensor: within 100 m
Break detection
terminal
AD-AS-1AM
P O W E R
WATER LEAKAGE
CUT-OFF SENCOR
BUZZER STOP
R E S E T
WATER-LEAKAGE
DETECTOR
Connected to the
central monitor
panel and others
Tatsuta Electric Wire &cable Co., Ltd.
AD-AS-1AM
P O W E R
WATER LEAKAGE
CUT-OFF SENCOR
BUZZER STOP
R E S E T
WATER-LEAKAGE
DETECTOR
Break indicator
LED (green)
Buzzer stop button
Reset button
Power indicator
LED (yellow)
Water leakage
indicator LED (red)
Tatsuta Electric Wire & Cable Co., Ltd.
CN1
Break detection
Alarm hold
Fail-safe
Buzzer
VR1 VR2
Power
Water
leakage
Break Sensitivity
adjustment
ON OFF
Reset →
Buzzer stop
H
M
L
Buzzer
volume
Detection
sensitivity
Loud High
100V
200V
Ground
Sensor (I)
Sensor (O)
AC power input
NC
COM
NO
NC
COM
NO
!
■Electric shock!
* Do not remove this
protective sheet.
* Do not insert foreign
bodies into the
opening.
* Do not touch with wet
hands.
Caution
Long-pushing the buzzer stop
and reset bu ttons together
(for 2 sec.) allow s you to
check how the detector circui t
and relay opera te.
Water leak age
Break
If you have any questions about handling the detector, contact:
 Detector Dimensions
 Schematic Diagram of Detector
 Outside Dimensions of Wall-embedded Type
 Detector Installation Method
* Make sure that the main power breaker is turned OFF and that alarm contact signal lines are open.
Follow the procedure below to check detector installation, setting (adjustment) and operations.
(1) Installing detecting box
 Remove the outer cover. Using a flat-blade driver or similar tool, open the notches below the outer
cover and remove it.
 Remove the intermediate board. Loosen four M4 flat-head screws and remove the intermediate board
(with circuit board) from the enclosure.
* To install a detector in the wall-embedded scheme, refer to: Method of Installing the Wall-embedded Type.
 Work on the enclosure. Decide wire insertion points and work on the enclosure for inserting wires as
need arises.
 Install the enclosure. Using the mounting holes (four 5–mm-diameter holes) on the back of the
enclosure, fix it in place.
(2) Wiring the power supply, sensor, and alarm contact signal lines.
 Insert wires into the enclosure. Using the back of the wall, wire protectors, or conduits, insert wires into
the enclosure.
 Attach crimp contacts to wires. By aligning the intermediate board (with circuit board) on the enclosure,
adjust wire lengths.
Note 1: Use crimp contacts 7.5 mm or less in diameter for use with an M3 or M4 screw.
Note 2: Use crimp pliers matching the crimp contacts and wire size used.
 Connect wires to the circuit board. Make secure connections according to the “terminal description” as
shown below, using a flat-blade screwdriver.
 To improve noiseproof properties and resistance to static electricity, be sure to make grounding
connections.
Note 1: Bend crimp contacts about 45˚ as shown in “cross section.”
AD-AS-1AM-2
ON
1 2 3 4
0
1
4
5
6
9
(3) Setting (adjustment) and checking
 Checking settings: To change a setting, follow the instructions under: Detector Setting Method.
 Checking of operations: To check operations at time of installation, refer to: Method of Operating
Detector and Checking Detector Operations.
(4) Completion of installation
 Attaching the insulating sheet: Align the line on the insulating sheet to the terminal block and attach the
sheet.
 Fitting outer cover: After making sure that LEDs are not bent, attach outer cover.
 Checking operations after installation: When postponing the operation test due to power supply
condition or other situations, remove the outer cover and follow the instructions under: Method of
Operating Detector and Checking Detector Operations for Testing.
 Method of Installing Wall-embedded Type
This detector can be installed in a wall-embedded finish after removal from enclosure.
Refer to illustrations below to install detector using standard switch box, clamp fittings and retaining
fittings.
No.1AM-1206-01
Outer cover Insulating sheet Circuit
board Enclosure
Intermediate
board Dustproof
cover
Terminal block description Insulating sheet
Crimp contact
Crimp contact
Cross section
7.5 mm or less
Examples of wall-embedded work execution (using standard boxes and fittings)
AD-AS-1 AM- 1
AD- AS-1 AM-1
AD- AS-1 AM-1
Position of fixing screw Rear view (back of wall)
Side view
(wall cross section)
Example of work execution with switch box
Example of work execution with clamp fittings
Example of work execution with retaining fittings
Panasonic DM8020K
Panasonic WN3993020
Panasonic WN3997
0 to 25 mm
7 to 18 mm
9 to 30 mm
Dimensions of mounting holes
98
88
98
105
98
94
48
124
120 3315
63
74
ON
12 3 4
AD-AS-1AM-1
45
82
98
Six 5x10-mm holes (for countersunk head screws)
78
66
98
Outside dimensions with
enclosure removed
Inside dimensions with
outer cover removed
AD-AS-1AM
P O W E R
WATER LEAKAGE
CUT-OFF SENCOR
BUZZER STOP
R E S E T
WATER-LEAKAGE
DETECTOR
Tatsuta Electric Wire & Cable Co., Ltd.
<Manufacturer >
Tatsuta Electric Wire & Cable Co., Ltd.
System Division
2-3-1 Iwata-cho, Higashi-Osaka, Osaka 578-8585
Tel: +81-6-6721-3335 Fax: +81-6-6725-0018
Sales department
3rd floor, Nihon-Seimei Kawasaki Bldg., 1-1, Minami-machi, Kawasaki Ward,
Kawasaki City, Kanagawa Prefecture 210-0015
Tel: +81-44-221-7691 Fax: +81-44-221-7695
55
124
120
AD-AS-1AM
P O W E R
WATER LEAKAGE
CUT-OFF SENCOR
BUZZER STOP
R E S E T
WATER-LEAKAGE
DETECTOR
70
70 2727
2525
13
20 18 20
6 6
12 wire entry holes
Four 5-mm-diameter
mounting holes
Two 6x1.5-mm notches to permit outer cover removal
Tatsuta Electric Wire & Cable Co., Ltd.
CN1
Break detection
Alarm hold
Fail-safe
Buzzer
VR1 VR2
Power
Water
leakage
Break Sensitivity
adjustment
ON OFF
Reset →
Buzzer stop
H
M
L
Buzzer
volume
Detection
sensitivit y
Loud High
100V
200V
Ground
Sensor (I)
Sensor (O )
AC power inpu t
NC
COM
NO
NC
COM
NO
!
■Electric shock!
* Do not remove this
protective sheet.
* Do not insert foreign
bodies into the
opening.
* Do not touch with wet
hands.
Caution
Long-pushing the buzzer stop
and reset bu ttons together
(for 2 sec.) allow s you to
check how the detector circuit
and relay o perate.
Water lea kage
Break
Water leakage alarm contact NC1
Water leakage alarm contact COM1
Water leakage alarm contact NO1
Break alarm contact NC2
Break alarm contact COM2
Break alarm contact NO2
N.C.(non
-
contact)
Ground
Sensor(I)
Sensor(O)
AC power
AC100V
~
AC240V

Other Tatsuta Electric Wire & Cable Security Sensor manuals

Tatsuta Electric Wire & Cable AD–AS–1CM Technical manual

Tatsuta Electric Wire & Cable

Tatsuta Electric Wire & Cable AD–AS–1CM Technical manual

Tatsuta Electric Wire & Cable AD-AS-1LDMA User manual

Tatsuta Electric Wire & Cable

Tatsuta Electric Wire & Cable AD-AS-1LDMA User manual

Tatsuta Electric Wire & Cable AD-AS-1BM User manual

Tatsuta Electric Wire & Cable

Tatsuta Electric Wire & Cable AD-AS-1BM User manual

Tatsuta Electric Wire & Cable AD-AS-1LCM-A User manual

Tatsuta Electric Wire & Cable

Tatsuta Electric Wire & Cable AD-AS-1LCM-A User manual

Tatsuta Electric Wire & Cable AD-AS-1C-SR User manual

Tatsuta Electric Wire & Cable

Tatsuta Electric Wire & Cable AD-AS-1C-SR User manual

Popular Security Sensor manuals by other brands

Visonic GLASSTECH installation instructions

Visonic

Visonic GLASSTECH installation instructions

Theben LUXA 103-100 AP WH operating instructions

Theben

Theben LUXA 103-100 AP WH operating instructions

Hikmicro HM-TD1018-1/QR user manual

Hikmicro

Hikmicro HM-TD1018-1/QR user manual

Philips Dynalite DUS704W installation manual

Philips

Philips Dynalite DUS704W installation manual

Atsumi Electric NR30TM installation instructions

Atsumi Electric

Atsumi Electric NR30TM installation instructions

ActiV C4408 manual

ActiV

ActiV C4408 manual

Simplex 4098-9839 Quick reference guide

Simplex

Simplex 4098-9839 Quick reference guide

Autostopcock Plus user manual

Autostopcock

Autostopcock Plus user manual

System Sensor WFDTNRN Installation and maintenance instructions

System Sensor

System Sensor WFDTNRN Installation and maintenance instructions

Panasonic SE4D Series instruction manual

Panasonic

Panasonic SE4D Series instruction manual

KPS DETELUX180IP110VCBINT instruction manual

KPS

KPS DETELUX180IP110VCBINT instruction manual

Berner DETECTOR-1 MULTI-FINDER Original instructions

Berner

Berner DETECTOR-1 MULTI-FINDER Original instructions

Simon 8902006-039 quick start guide

Simon

Simon 8902006-039 quick start guide

Prime DS101 operating instructions

Prime

Prime DS101 operating instructions

STI UB-1 manual

STI

STI UB-1 manual

Omron F3SG series user manual

Omron

Omron F3SG series user manual

MUNBYN IMC02R user manual

MUNBYN

MUNBYN IMC02R user manual

teko Astra-A ILS user guide

teko

teko Astra-A ILS user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.