TEV Marstair CX 30 User manual

55908014-17
CX(E) SPLIT SYSTEMS
TECHNICAL MANUAL
CX(E) LOW TEPERATURE SPLIT SYSTEMS

2/19
55908014-17
INDEX
CONTENTS
PAGE
PART NUMBERS, OPTIONS, UNIT COMBINATIONS
3
DIMENSIONS & WEIGHTS, PERFORMANCE DATA
4
AIR FLOW, SOUND POWER AND SOUND PRESSURE LEVELS
5
ELECTRICAL DATA
6
CX(E)
DIMENSIONS
7
INSTALLATION: CONTENTS & PIPEWORK
8
ELECTRICAL: FUSES & WIRING DIAGRAMS
9
REMOTE SETTINGS
10
CKC
INSTALLATION: DIMENSIONS
11
PIPEWORK
12
ELECTRICAL
13
CONTROLS
16
PIPEWORK
17
COMPONENT IDENTIFICATION
CX(E) UNITS
18
CKC UNITS
19
1. TEV Ltd recommend that personnel working on this equipment be skilled and fully conversant with
the appropriate Air Conditioning, Refrigeration and Electrical practices and have sound knowledge
of current Industrial Safe Working practices.
2. CX(E) models are electromechanical / Electronic control units that use R407C refrigerant; they
provide cooling within the range of 2.8 –6.8 kW. These units are matched with CKC outdoor units
to complete a system.
CX(E) units are fitted with an expansion assembly, allowing the use of a liquid line. This can be
transferred to the outdoor unit (CKC only), when an expansion line is required to accommodate
longer pipe runs.
3. These units contain live electrical components, moving parts and refrigerant under pressure.
Always site out of reach of children and protect from vandalism.
4. The data plate only gives information for the CX(E) unit. For system details add input power and
current of indoor and outdoor unit, including any heater load.
GENERAL

3/19
55908014-17
MODEL
CX 30
CX 40
CX 50
CX 70
PART NUMBER
55917001
55917002
55917003
55917004
MODEL
CXE 30
CXE 40
CXE 50
CXE 70
PART NUMBER
55917017
55917016
55917015
55917014
MODEL
CKC 20 1ph
CKC 30 1ph
CKC 50 1ph
CKC 80 1ph
CKC 80 3ph
PART NUMBER
55017720
55017730
55017722
55017723
55017724
Low Temperature Match
MODEL
CXE 40
CXE 50
CXE 70
PART NUMBER
55917016
55917015
55917014
MODEL
CKC 20 1ph
CKC 40 1ph
CKC 60 1ph
PART NUMBER
55017720
55017741
55017740
INDOOR UNIT
OUTDOOR UNIT
CX(E) 30
CKC 20
CX(E) 40
CKC 30
CX(E) 50
CKC 50
CX(E) 70
CKC 80
Low Temperature Match
INDOOR UNIT
OUTDOOR UNIT
CXE 40
CKC 20
CXE 50
CKC 40
CXE 70
CKC 60
OPTIONAL KITS
PART NUMBER
DESCRIPTION
55900700
3kW heater (CX only)
55900701
Digital temperature display (CX only) std on CXE
55900702
De-ice thermostat (CX only)
55900709*
Extended pipe run CX 30/40/50 only
55900710*
Extended pipe run CX 70 only
55900715
3kW heater (CXE only)
* When matched with CKC outdoor units
CX(E) OPTIONS
UNIT COMBINATIONS
PART NUMBERS

4/19
55908014-17
MODEL
UNPACKED
PACKED
CX(E)
HEIGHT
WIDTH
DEPTH
WEIGHT
HEIGHT
WIDTH
DEPTH
WEIGHT
30
483
845
320
18
530
950
370
21
40
483
845
320
18
530
950
370
21
50
483
845
320
20
530
950
370
23
70
483
845
320
23
530
950
370
26
CKC
HEIGHT
WIDTH
DEPTH
WEIGHT
HEIGHT
WIDTH
DEPTH
WEIGHT
1Ph
3Ph
1Ph
3Ph
20
620
900
310
46
-
625
980
340
48
-
30
620
900
310
48
-
625
980
340
55
-
50
720
1000
310
64
-
730
1080
340
66
-
60
720
1000
310
64
730
1080
340
66
-
80
720
1000
310
66
64
730
1080
340
68
66
MODEL
RATING CONDITIONS
(ROOM 12.7C / 10C) (AMBIENT 27C / 19C)
OPTIONAL ELECTRIC
HEATER
TOTAL
SHR
SENSIBLE
240V
230V
CX(E) 30 + CKC 20
2.80
0.75
2.10
3.25
3.0
CX(E) 40 + CKC 30
3.30
0.68
2.24
3.25
3.0
CX(E) 50 + CKC 50
4.60
0.66
3.02
3.25
3.0
CX(E) 70 + CKC 80
6.80
0.63
4.30
3.25
3.0
MODEL
RATING CONDITIONS
(ROOM 12.7C / 10C) (AMBIENT 35C / 19C)
OPTIONAL ELECTRIC
HEATER
TOTAL
SHR
SENSIBLE
240V
230V
CX(E) 30 + CKC 20
2.38
0.75
1.79
3.25
3.0
CX(E) 40 + CKC 30
2.81
0.68
1.90
3.25
3.0
CX(E) 50 + CKC 50
3.91
0.66
2.57
3.25
3.0
CX(E) 70 + CKC 80
5.78
0.63
3.66
3.25
3.0
Low Temperature Match
MODEL
RATING CONDITIONS
(ROOM 5Cdb/ 3Cwb) (AMBIENT 27C / 19C)
OPTIONAL ELECTRIC
HEATER
TOTAL
SHR
SENSIBLE
240V
230V
CXE 40 + CKC 20
2.3
0.85
2.0
3.3
3.0
CXE 50 + CKC 40
3.5
0.80
2.8
3.3
3.0
CXE 70 + CKC 60
5.0
0.70
3.5
3.3
3.0
MODEL
RATING CONDITIONS
(ROOM 5Cdb/ 3Cwb) (AMBIENT 35C / 19C)
OPTIONAL ELECTRIC
HEATER
TOTAL
SHR
SENSIBLE
240V
230V
CXE 40 + CKC 20
2.0
0.85
1.7
3.3
3.0
CXE 50 + CKC 40
3.0
0.80
2.4
3.3
3.0
PERFORMANCE DATA (kW)
DIMENSIONS & WEIGHTS

5/19
55908014-17
CXE 70 + CKC 60
4.3
0.70
3.0
3.3
3.0
AIR FLOWS
MODEL
m³/s
MODEL
m³/s
CX(E) 30
0.61
CKC 20
0.97
CX(E) 40
0.61
CKC 30
0.97
CX(E) 50
0.66
CKC 50
0.97
CX(E) 70
0.58
CKC 80
0.97
INDOOR UNIT
MAXIMUM
SPEED
SOUND POWER LEVELS
SOUND PRESSURE
LEVELS
SPEED
Frequency Hz
125
250
500
1K
2K
4K
dB(A)
NC
CX(E) 30
69.1
67.7
67.6
65.6
62.2
56.0
55
48
CX(E) 40
69.1
67.7
67.6
65.6
62.2
56.0
55
48
CX(E) 50
71.7
69.2
69.1
67.1
63.2
58.5
56
50
CX(E) 70
70.1
68.2
68.6
66.1
63.2
57.5
56
49
Sound Power Levels were obtained in full accordance with the direct method of BS EN ISO3174:2000. Levels are shown in dB
with a standard reference of 1 pW.
Sound Pressure Levels in dB(A) refer to semi-hemispherical radiation (wall or ceiling mounted) at a distance of 1.5m from the
front of the unit, with the fan operating at full speed.
OUTDOOR UNIT
MAXIMUM
SPEED
SOUND POWER LEVELS
SOUND PRESSURE
LEVELS
SPEED
Frequency Hz
125
250
500
1K
2K
4K
dB(A)
NC
CKC 20
77
67
69
65
60
54
49
44
CKC 30
77
68
69
65
60
54
50
44
CKC 50
74
68
67
66
61
54
49
44
CKC 60
73
68
68
66
62
54
50
45
CKC 80
71
69
68
65
60
54
49
43
Sound Power Levels were obtained in full accordance with the direct method of ISO 3741: 1988. Levels are shown in dB with a
standard reference of 1 pW.
Sound Pressure Levels (SPL) at 3m distance in free field conditions. (Reference 2x10
⁻⁵ N/m²)
SOUND POWER AND SOUND PRESSURE LEVELS

6/19
55908014-17
MODEL
INDOOR/OUTDOOR
1 PH 230V 50Hz
INPUT POWER
FULL LOADS AMPS
SYSTEM
MAX.
STARTING
CURRENT
COOLING
HEATING
COOLING
HEATING
kW
kW
AMPS
AMPS
AMPS
CX(E) 30 + CKC 20
1.3
2.9
7.7
13.8
30
CX(E) 40 + CKC 30
1.6
2.9
8.2
13.8
38
CX(E) 50 + CKC 50
2.2
2.9
9.7
13.8
60
CX(E) 70 + CKC 80
3.2
2.9
12.3
13.8
78
MODEL
INDOOR/OUTDOOR
3 PH 400V 50Hz
INPUT POWER
FULL LOADS AMPS
SYSTEM
MAX.
STARTING
CURRENT
COOLING
HEATING
COOLING
HEATING
kW
kW
AMPS
AMPS
AMPS
CX(E) 70 + CKC 80
3.2
2.9
5.7
13.8
42
Low Temperature Match
MODEL
INDOOR/OUTDOOR
1 PH 230V 50Hz
INPUT POWER
FULL LOADS AMPS
SYSTEM
MAX.
STARTING
CURRENT
COOLING
HEATING
COOLING
HEATING
kW
kW
AMPS
AMPS
AMPS
CXE 40 + CKC 20
1.3
3.1
7.15
12.8
28
CXE 50 + CKC 40
2.1
3.1
10.2
13.8
50
CXE 70 + CKC 60
2.4
3.1
9.8
13.8
61
UNIT ELECTRICAL LOADS [230V 50Hz 1Ph (A) or 400V 50Hz 3Ph (A/Ph)]
MODEL
FAN MOTOR
HEATER
CX(E) 30
0.8
13.0
CX(E) 40
0.8
13.0
CX(E) 50
0.8
13.0
CX(E) 70
0.8
13.0
CKC
20
30
40
50
60
80
Fan motor
0.6
0.6
0.6
0.6
0.6
0.6
R407C compressor (1 Ph) nominal FLA
6.0
10.4
10.2
8.3
9.8
10.9
R407C compressor (3 Ph) nominal FLA
-
-
-
-
-
4.3
Crankcase heater
0.25
0.25
0.25
-
0.25
-

7/19
55908014-17
ELECTRICAL DATA
CX(E) DIMENSIONS
DIMENSIONS (mm)
CONDENSATE DRAIN 22mm OD
96
35 65 TYP.
140
75
215 36
17.5
17.5
39
39
124
422.5
70
845
888
124
888 (Fixing centres)
(Fixing centres)
320
96
MIN. 500
FOR SIDE ACCESS
483
20
X = Interconnecting Wiring
Z1= Suction
Z2= Liquid / Expansion
SIDE VIEW
(Wall mounted)
X
Z1
Z2
X
SIDE VIEW
(Ceiling mounted)
TOP VIEW
(Ceiling Mounted)
REAR VIEW
(Wall mounted)
FRONT VIEW
(Wall mounted)
120
MIN. 120
MIN.

8/19
55908014-17
INSTALLATION
CONTENTS
PARTS DESCRIPTION
QTY
ACTION
Envelope containing operating instructions and
Declaration of Conformity
1
Pass to the end user.
Mounting brackets
2
Use to hang unit.
Drain Stub/Nut/Gasket
1
Fitted by installer.
Drain stub adaptor
1
Convert to ¾" drain if required.
Screw M5
6
To fix brackets to unit.
Washer nylon
6
To fix brackets to unit.
Washer M5 shakeproof
6
To fix brackets to unit.
Reducing flare nut 1/2” – 3/8”
1
Fit to liquid connection on the CXE 70 indoor unit
when matched with a CKC 60 outdoor unit
The unit may be mounted on a wall or solid ceiling using brackets supplied. It should be matched with the appropriately
sized outdoor unit; this instruction should be used in conjunction with the outdoor unit installation instructions.
UNIT COMBINATIONS
1. Fit all kits prior to installing the unit. (Heater kit is easier to fit when unit has been mounted).
2. Ensure that the mounting surface will support the operating weight of the unit (see table below).
3. Mark out the mounting positions and drill holes to suit 6mm rawlbolt shields or equivalent strength fasteners
(ensure that the unit is positioned to give sufficient access (min 0.5m) to the removable side panel).
4. Fix the mounting brackets to the unit in the correct position for wall or ceiling mounting.
5. Raise the unit into position and secure the fixings, ensuring that it is square and level.
6. Remove the drain tray then fit the drain stub, nut &
gasket. Refit the drain tray.
NITROGEN CHARGE
The unit contains a small charge of dry nitrogen, which should
be discharged into the atmosphere. This is a non-toxic, non-
ozone depleting gas with no global warming potential.
FITTING LOSSES, in equivalent straight lengths of pipe (m).
FITTING
Pipe Size OD
To calculate the total equivalent
length, the equivalent lengths of all
fittings in a pipe run must be added
to the actual length of pipe in the
run: these are the fittings most
likely to be used.
R = Radius of bend
d = Diameter of tube
C = Centres of bend
3/8"
1/2"
5/8"
3/4"
7/8"
45° Bend
0.12
0.15
0.18
0.21
0.24
90° Bend R/d = 1
0.37
0.43
0.49
0.55
0.61
90° Bend R/d = 1.5
0.24
0.27
0.3
0.37
0.43
180° Bend R/d = 1.5
0.73
0.91
1.1
1.28
1.46
180° Bend C/d = 2.5
0.46
0.55
0.64
0.76
0.85
90° Elbow
0.67
0.85
1.04
1.25
1.46
A. USING SUCTION AND LIQUID LINES:
With the expansion device connected to the indoor unit, the equivalent pipe run should be 20m maximum,
including a maximum lift of 7.5m. Fully insulate the suction line. Ensure the suction pipe is insulated well over
the drain tray at the indoor unit. Liquid lines should be routed to avoid hot areas. This prevents flash gas
forming, which may result in erratic control of liquid refrigerant to the evaporator.
MAXIMUM EQUIVALENT LENGTH OF SUCTION LINE PIPE SIZES (m)
LIQUID LINE
SYSTEM
3/8"
1/2"
5/8"
3/4"
1/4"
3/8"
CX(E)30 + CKC20
7.5
20
-
-
20
-
CX(E)40 + CKC30
-
15
20
-
-
20
CX(E)50 + CKC50
-
7.5
18
-
-
20
CX(E)70 + CKC80
-
-
11
20
-
20
Minimum Set Temperature 4°C
INDOOR UNIT
OUTDOOR UNIT
CXE 40
CKC 20
CXE 50
CKC 40
CXE 70
CKC 60
Minimum Set Temperature 8°C
INDOOR UNIT
OUTDOOR UNIT
CXE 30
CKC 20
CXE 40
CKC 30
CXE 50
CKC 50
CXE 70
CKC 80
DRAIN TRAY
GASKET
NUT
DRAIN STUB
CKC PIPEWORK

9/19
55908014-17
MAXIMUM EQUIVALENT LENGTH OF SUCTION LINE PIPE SIZES (m)
LIQUID LINE
SYSTEM
3/8"
1/2"
5/8"
-
1/4"
3/8"
CXE40 + CKC20
7.5
20
-
-
20
--
CXE50 + CKC40
-
15
20
-
-
20
CXE70 + CKC60
-
7.5
18
20
-
20
B. USING SUCTION AND EXPANSION LINES
The expansion assembly must be removed from the indoor unit and connected to the outdoor unit allowing a
pipe run of up to 80m, including a maximum lift of 20m (CKC20 maximum 50m with 7.5m lift).
CX(E) units only, remove the right hand panel cover plate from the indoor unit and remove the expansion
assembly. [Make good the gap using Extended Pipe Run Kit 55900709 (30,40,50), 55900710 (70).]
Fit the expansion assembly onto the outdoor unit liquid line service valve. Fully insulate both the suction and
expansion lines, including the expansion device: ensure the pipes are insulated well over the drain tray at the
indoor unit.
MAXIMUM EQUIVALENT LENGTH OF SUCTION LINE PIPE
SIZES (m)
EXPANSION LINES
SYSTEM
3/8"
1/2"
5/8"
3/4"
7/8"
3/8"
1/2"
5/8"
CX(E)30 + CKC20
7.5
23
50
-
-
50
-
-
CX(E)40 + CKC30
-
10
36
80
-
7.5
80
-
CX(E)50 + CKC50
-
7.5
18
50
80
7.5
50
80
CX(E)70 + CKC80
-
-
11
30
80
-
50
80
MAXIMUM EQUIVALENT LENGTH OF SUCTION LINE PIPE
SIZES (m)
EXPANSION LINES
SYSTEM
3/8"
1/2"
5/8"
3/4"
7/8”
3/8"
1/2"
5/8"
CXE40 + CKC20
7.5
23
50
-
-
50
-
-
CXE50 + CKC40
-
10
36
80
-
7.5
80
-
CXE70 + CKC60
-
7.5
18
50
80
7.5
50
80
PIPE CONNECTIONS
Units are supplied with the
following male flare connections
(sizes in inches):
RESTRICTORS
Indoor units are supplied with restrictors fitted.
OUTDOOR UNIT
CKC20
CKC30
CKC40
CKC50
CKC60**
CKC80
LIQUID / EXPANSION
3/8"
3/8"
3/8”
3/8"
3/8”
1/2"
SUCTION
1/2"
1/2"
1/2”
1/2"
5/8”
5/8"
NOTE
When the CXE 40 is matched with a CKC 20.
The restrictor in the indoor unit must be
changed to 0.033"
When the CXE 50 is matched with a CKC 40.
The restrictor in the indoor unit remains as
a 0.050"
When the CXE 70 is matched with a CKC 60.
The restrictor in the indoor unit must be
changed to 0.057"

10/19
55908014-17
INTERCONNECTING PIPEWORK
1. The indoor unit has a low pressure charge of N2, which may be safely released into the atmosphere
before connection. The service valves on the outdoor unit should remain closed (IN, fully clockwise)
until pipework has been fitted and system evacuated.
2. Connecting the pipework
a. Remove the flare nuts from the suction and liquid service valves.
b. Ensure that the suction line is fully insulated: if an expansion line is used this should also be fully
insulated.
c. Place the flare nuts over the incoming pipework and flare the pipe ends. The use of a little
refrigeration oil on the flaring tool will help.
d. Connect the pipework between the units. Do not leave pipe ends, valves etc. open to the
atmosphere.
R407C is very hygroscopic and will absorb damaging levels of moisture if left open.
Always use two spanners when tightening the flare nuts to avoid twisting the pipes. Use a small
amount of refrigerant oil on the mating surfaces.
e. Sight glasses and filter driers are not necessary, but if required should be fitted between the
outdoor unit liquid shut off valve and the expansion device.
EVACUATING
1. Connect a vacuum pump to the service ports on the outdoor unit valves and evacuate the system to 1000
microns (1 Torr) or better and allow to be held for a minimum of 15 minutes.
2. Replace the caps on the service ports, (torque to 25NM).
ADDING REFRIGERANT
1. Allunits are fitted with head pressure control. The link wire across the orange terminals allows the fan
to operate at full speed. THIS SHOULD BE REMOVED AFTER CHARGING
2. If a manual HP cut-out is fitted, ensure that the reset button is depressed.
3. A 3 minute delay occurs between successive compressor operations.
4. R407C should be introduced through the Schrader valve on the indoor unit, or the service port on the
suction service valve on the outdoor unit. No other refrigerant must be used.
NOTE: LABEL R407C POE (supplied loose) TO BE FIXED ABOVE SERVICE VALVES.
CHARGE (g)
No extra POE oil needed with liquid lines.
Charges shown are for guidance: actual charge will depend on the individual application. It is recommended that
you charge to a sweat line on the outlet of the evaporator and/or a full sight glass if fitted.
Additional
charge
based on:-
Liquid line
Expansion line
1/4"
3/8"
3/8"
1/2"
5/8"
25 g/m
60 g/m
16 g/m
30 g/m
48 g/m
Additional POE oil
25g per 350g of additional refrigerant to a maximum of 300g
NOTE: The new 17 Series CKC are pre-charged for a 3 metre pipe run with R407C Refrigerant. See
chart below. The old 23 Series CKC have a small nitrogen charge.
PLEASE CHECK BEFORE INSTALLATION.
Unit
Pre-Charged (Kgs)
CKC20
0.650
CKC30
0.761
CKC40
0.807
CKC50
1.167
CKC60
1.477
CKC80
1.357
CKC REFRIGERANT

11/19
55908014-17
NOTE: All refrigerant charges shown below are in grams
LOW TEMPERATURE MATCH
NEW CX 17 SERIES MATCHED WITH NEW CKC 17 SERIES
SYSTEM CX (NEW) CXE (NEW) CKC (NEW) 5 10 15 20
CX(E)30 + CKC20 55917001 55917017 55017720 679 794 909 1024
CX(E)40 + CKC30 55917002 55917016 55017730 884 1184 1484 1784
CX(E)50 + CKC50 55917003 55917015 55017722 1286 1586 1886 2186
CX(E)70 + CKC80 55917004 55917014 55017723 1410 1710 2010 2310
PART NUMBER
LIQUID LINE (m)
R407C
SYSTEM CX (NEW) CXE (NEW) CKC (NEW) 25 30 35 40 45 50 55 60 65 70 75 80
CX(E)30 + CKC20 55917001 55917017 55017720 964 1044 1124 1204 1284 1364 - - - - - -
CX(E)40 + CKC30 55917002 55917016 55017730 1324 1474 1624 1774 1924 2074 2224 2224 2524 2674 2824 2974
CX(E)50 + CKC50 55917003 55917015 55017722 1811 1961 2111 2261 2411 2561 2801 2801 3281 3521 3761 4001
CX(E)70 + CKC80 55917004 55917014 55017723 2655 2805 2955 3105 3255 3405 3645 3645 4125 4365 4605 4845
EXPANSION LINE (m)
R407C
PART NUMBER
SYSTEM CX (NEW) CXE (NEW) CKC (NEW) 5 10 15 20
CX(E)40 + CKC20 55917002 55917016 55017720 434 734 1034 1334
CX(E)50 + CKC40 55917003 55917015 55017741 546 846 1146 1446
CX(E)70 + CKC60 55917004 55917014 55017740 940 1240 1540 1840
LIQUID LINE
R407C
NEW CX/NEW CKC
PART NUMBER
SYSTEM CX (NEW) CXE (NEW) CKC (NEW) 25 30 35 40 45 50 55 60 65 70 75 80
CX(E)40 + CKC20 55917002 55917016 55017720 934 1084 1234 1384 1534 1684
CX(E)50 + CKC40 55917003 55917015 55017741 1186 1336 1486 1726 1966 2206 2356 2506 2656 2806 2956 3106
CX(E)70 + CKC60 55917004 55917014 55017740 1580 1730 1880 2030 2180 2330 2570 2810 3050 3290 3530 3770
EXPANSION LINE
R407C
NEW CX/NEW CKC
PART NUMBER
NEW CX 17 SERIES MATCHED WITH OLD CKC 23 SERIES
SYSTEM CX (NEW) CXE (NEW) CKC (OLD) 5 10 15 20
CX(E)30 + CKC20 55917001 55917017 55000720 918 1033 1148 1263
CX(E)40 + CKC30 55917002 55917016 55000730 1123 1423 1723 2023
CX(E)50 + CKC50 55917003 55917015 55000722 1809 2109 2409 2709
CX(E)70 + CKC80 55917004 55917014 55000723 1933 2233 2533 2833
PART NUMBER
LIQUID LINE (m)
R407C
SYSTEM CX (NEW) CXE (NEW) CKC (OLD) 25 30 35 40 45 50 55 60 65 70 75 80
CX(E)30 + CKC20 55917001 55917017 55000720 1203 1283 1363 1443 1523 1603
CX(E)40 + CKC30 55917002 55917016 55000730 1563 1713 1863 2013 2163 2313 2463 2463 2763 2913 3063 3213
CX(E)50 + CKC50 55917003 55917015 55000722 2334 2484 2634 2784 2934 3084 3324 3324 3804 4044 4284 4524
CX(E)70 + CKC80 55917004 55917014 55000723 3178 3328 3478 3628 3778 3928 4168 4168 4648 4888 5128 5368
EXPANSION LINE (m)
R407C
PART NUMBER
LOW TEMPERATURE MATCH

12/19
55908014-17
SYSTEM CX (OLD) CXE (OLD) CKC (OLD) 25 30 35 40 45 50 55 60 65 70 75 80
CX(E)30 + CKC20 55900001 55900017 55000720 1310 1390 1470 1550 1630 1710 - - - - - -
CX(E)40 + CKC30 55900002 55900016 55000730 1670 1820 1970 2120 2270 2420 2570 2570 2870 3020 3170 3320
CX(E)50 + CKC50 55900003 55900015 55000722 2505 2655 2805 2955 3105 3255 3495 3495 3975 4215 4455 4695
CX(E)70 + CKC80 55900004 55900014 55000723 3465 3615 3765 3915 4065 4215 4455 4455 4935 5175 5415 5655
EXPANSION LINE (m)
R407C
PART NUMBER
LOW TEMPERATURE MATCH
SYSTEM CX (NEW) CXE (NEW) CKC (OLD) 5 10 15 20
CX(E)40 + CKC20 55917002 55917016 55000720 673 973 1273 1573
CX(E)50 + CKC40 55917003 55917015 55000741 979 1279 1579 1879
CX(E)70 + CKC60 55917004 455917015 55000740 1463 1763 2063 2363
PART NUMBER
LIQUID LINE
R407C
NEW CX/OLD CKC
SYSTEM CX (NEW) CXE (NEW) CKC (OLD) 25 30 35 40 45 50 55 60 65 70 75 80
CX(E)40 + CKC20 55917002 55917016 55023720 1173 1323 1473 1623 1773 1923
CX(E)50 + CKC40 55917003 55917015 55023741 1619 1769 1919 2159 2399 2639 2789 2939 3089 3239 3389 3539
CX(E)70 + CKC60 55917004 455917015 55023740 2103 2253 2403 2553 2703 2853 3093 3333 3573 3813 4053 4293
PART NUMBER
R407C
EXPANSION LINE
NEW CX/OLD CKC
OLD CX SERIES MATCHED WITH OLD CKC 23 SERIES
LOW TEMPERATURE MATCH
SYSTEM CX (OLD) CXE (OLD) CKC (OLD) 5 10 15 20
CX(E)40 + CKC20 55900002 55900016 55000720 780 1080 1380 1680
CX(E)50 + CKC40 55900003 55900015 55000741 1150 1450 1750 2050
CX(E)70 + CKC60 55900004 55900014 55000740 1750 2050 2350 2650
PART NUMBER
LIQUID LINE
R407C
SYSTEM CX (OLD) CXE (OLD) CKC (OLD) 25 30 35 40 45 50 55 60 65 70 75 80
CX(E)40 + CKC20 55900002 55900016 55023720 1280 1430 1580 1730 1880 2030
CX(E)50 + CKC40 55900003 55900015 55023741 1790 1940 2090 2330 2570 2810 2960 3110 3260 3410 3560 3710
CX(E)70 + CKC60 55900004 55900014 55023740 2390 2540 2690 2840 2990 3140 3380 3620 3860 4100 4340 4580
PART NUMBER
EXPANSION LINE
R407C
SYSTEM CX (OLD) CXE (OLD) CKC (OLD) 5 10 15 20
CX(E)30 + CKC20 55900001 55900017 55000720 1025 1140 1255 1370
CX(E)40 + CKC30 55900002 55900016 55000730 1230 1530 1830 2130
CX(E)50 + CKC50 55900003 55900015 55000722 1980 2280 2580 2880
CX(E)70 + CKC80 55900004 55900014 55000723 2220 2520 2820 3120
PART NUMBER
LIQUID LINE (m)
R407C

13/19
55908014-17
5. Run the system for a few minutes to allow it to stabilize. Where possible, charge to a sweat line on the
evaporator. Typical suction pressure on short lines at UK conditions should be approx. 3.8bar (55 psig).
6. Head pressure controller
The head pressure controller is factory set to suit the refrigerant. It may be necessary to adjust this to
suit site conditions, to raise or lower the nominal head pressure.
a. With the system switched off, connect a high pressure gauge to the liquid line service valve.
b. Switch on the system, and run for a few minutes to stabilise.
c. The head pressure should be approximately:
R407C: 275-280 psig (18.9-19.6barg) to achieve this remove sealing plug and insert 2mm or 5/64” allen key
into setting screw. Turn allen key clockwise (+) or counter clockwise (-) to readjust the setting. Do not turn
setting screw more than 3 turns clockwise (+3). Use following table as a quick guideline for setting:
After adjustment, re-insert sealing plug and make sure that it is properly fitted. IP65 protection requires
firmly sealed plug
NOTES:
Tolerances for condensing temperatures setpoint: ±2K
Min fan speed (0 rpm) and fan cut in pressure 200 psig (13.8 barg) are factory set and not adjustable.
NOTE: The condenser fan may stop if the operating pressure drops below 200 psig (13.8 barg)
ELECTRICAL CONNECTIONS
Cables are routed to the terminal block via the cable cord grips at the rear of the unit and then through the back of
the electrics box (see page 2).
Cables MUST be size compatible with the recommended system fuse.
FUSES
SYSTEM
COOL ONLY
WITH ELECTRIC HEATER
1PH
3PH
1PH
3PH
CXE 30
16A
-
16A
-
CXE 40
20A
-
20A
-
CXE 50
20A
-
20A
-
CXE 70
20A
20A/PH
32A
20A/PH
Note: On 3 ph systems the supply must go to the CKC outdoor unit and then to the CXE indoor unit.

14/19
55908014-17
WIRING DIAGRAM
CXE
CX

15/19
55908014-17
CAREL IR33 Controller
ON/OFF SWITCH
The switch operates the fan motor and is illuminated when power is supplied to the indoor unit. When switched OFF, the
fan stops, the switch remains illuminated and the crankcase heater in the outdoor unit (if fitted) remains live.
Systems (STD)
Minimum Set
Temperatures
Indoor
Unit
Outdoor
Unit
CXE 30
CKC 20
8⁰C
CXE 40
CKC 30
8⁰C
CXE 50
CKC 50
8⁰C
CXE 70
CKC 80
8⁰C
CXEA 30
CKA 35
8⁰C
CXEA 50
CKA 35
8⁰C
CXEA 50
CKA 50
8⁰C
CXEA 70
CKA 70
8⁰C
Systems (Low Temp)
Minimum Set
Temperatures
Indoor Unit
Outdoor
Unit
CXE 40
CKC 20
4⁰C
CXE 50
CKC 40
4⁰C
CXE 70
CKC 60
4⁰C
TEMPERATURE CONTROL (Do not set the controller below 4⁰C.)
The SET temperature is factory set at 12⁰C.
The digital display normally displays the return air temperature.
To change the SET temperature, press and hold down the SET button. If no alarms active, the ‘St1’ label appears and
the current value is shown on the screen and will flash.
To change the Setpoint value, press ▲ and ▼ keys within 60 seconds.
The display will revert to the return air temperature after 60 seconds.
The fitted de-ice thermostat will activate a de-ice cycle when there is a build up of ice on the evaporator coil.
Cellarators will only heat a room if the electric heater option is fitted.
Displaying inputs on screen display
Press ▼ to display the current input. There are 6 inputs to select from to display
onto the screen. These are as follows:
b1: probe 1;
b2: probe 2;
di1: digital input 1;
di2; digital input 2;
St1: set point 1;
St2: set point 2;
Press ▲ and ▼ to select the input to be displayed. Press set for 3
seconds to confirm your choice.
To display the live temperature in the room you need to select
b1: probe 1
WARNING
The following actions could damage your system:
1. Switching the unit OFF and ON quickly
2. Setting the unit to HEAT and then back to COOL quickly
NB: Allow at least 3 minutes between the above actions.
CXE ELECTRONIC COOLING SYSTEM CONTROLS

16/19
55908014-17
Eliwell ICPlus 915 Controller
TEMPERATURE CONTROL (Do not set the controller below 4°C.)
The SET temperature is factory set at 12°C.
The digital display normally displays return air temperature.
To change the SET temperature, press the SET button. If no alarms are active, the ‘SP1’ label appears.
Press SET button again, the setpoint value appears on the display.
To change the Setpoint value, press the and keys within 15 seconds. Press SET to confirm the
modification.
The display will revert to the return air temperature after 15 seconds.
The fitted de-ice thermostat will activate a de-ice cycle when there is a build up of ice on the evaporator
coil.
cCellarators will only heat a room if the electric heater option is fitted.
WARNING
The following actions could damage your system:
1. Switching the unit OFF and ON quickly.
2. Setting the unit to Heat and then back to cool quickly.
NB. Allow at least 3 minutes between the above actions.
MOUNTING
Whether floor or wall mounted, it is essential that the mounting surface is
capable of supporting the unit weight. Leave space around the unit for air
circulation and access for installation and maintenance.
Dimensions in mm.
1500 min air off
100 min 100 min
600 min
CKC PIPEWORK
CKC INSTALLATION
12°C –23°C
«
«

17/19
55908014-17
1. Individual pipe runs to a maximum of 20m, including 7.5m lift, are permissible with liquid lines, 80m
with expansion lines, provided good refrigeration practice is followed.
Performance is based on 7.5m pipe runs. Correctly sized pipes for each installation will result in no
significant loss of capacity on extended pipe runs.
a) Pipe sizes are based on:-
Minimum of 3.8 m/s (750 fpm) suction gas velocity for horizontal or downflow.
Minimum of 7.6 m/s (1500 fpm) suction gas velocity for upflow.
Maximum of 15.2 m/s (3000 fpm) suction gas.
b) Where vertical risers exceed 3m, oil traps must be formed in the pipe. This will help ensure that oil
returns to the compressor. Typically fit an oil trap every 3m with a trap at the bottom of the riser.
2. In calculating equivalent lengths of pipe runs, the effect of bends and fittings must be taken into
account. The table below covers the fittings most likely to be encountered in this installation.
The equivalent lengths of all the fittings in a pipe run should be added together and the total added to
the actual pipe length in order to calculate the total equivalent length.
3. Use the shortest possible route, avoiding sharp bends.
4. Completely insulate the suction line, fully over the indoor unit drain tray.
MODEL
A
B
C
D
E
F
G
H
CKC 20
900
300
560
525
185
60
333
308
CKC 30
900
300
560
525
185
60
333
308
CKC 50
1000
300
660
570
213
60
333
308
CKC 80
1000
300
660
570
213
60
333
308

18/19
55908014-17
1
Grille
9
De-ice stat (option)
2
Fan / motor
10
Heater assembly (option)
3
Case
11
Drain stub adaptor
4
Wall / ceiling mounting brackets
12
Drain tray
5
Heater bracket
13
Side access panel
6
Coil assembly
14
Electrics box door
7
Thermostat bulb & bracket
15
Digital display (option)
8
Restrictor assembly / extended pipe (option)
Capillary Entry
Mains Cable Entry
Point
Internal Earth
Terminal
ENL
SPARE
CU
CU OUT
EN
L
MAINS IN
De - Ice
Thermostat
Capacitor
Incoming Fan
Wires
Thermostat
Switch
Digital
Temperature
Display
INSIDE VIEW OF ELECTRICS BOX
413
11
12
15
14
23
1
56
10 9
87
4
CX INDOOR UNIT COMPONENT IDENTIFICATION

19/19
55908014-17
1
LID
18
FRONT ACCESS
2
CONTACTOR
19
FAN GUARD
3
OVERLOAD
20
FASCIA PANEL
4
HEAT EXCHANGER COIL
21
CORNER PANEL
5
REAR ACCESS PANEL
22
SUPPORT BRACKET
6
MAINS TERMINAL COVER
23
FAN / MOTOR ASSEMBLY
7
FAN CAPACITOR
24
END CLAMP
8
BULKHEAD PANEL
25
TERMINAL
9
HP SWITCH (MANUAL, OPTION)
26
FUSE
10
SERVICE VALVE (LIQUID)
27
FUSE TERMINAL
11
SERVICE VALVE (SUCTION)
28
TERMINAL (4 WAY)
12
VALVE PANEL
29
EARTH TERMINAL
13
BASE
30
HEAD PRESSURE CONTROL pcb
14
MOUNTING FOOT
31
3 MINUTE TIMER pcb
15
LP SWITCH
32
COMPRESSOR CAPACITOR
16
COMPRESSOR
33
ELECTRICS BOX
17
HANDLE
CKC OUTDOOR UNIT COMPONENT IDENTIFICATION
TEV LTD,ARMYTAGE ROAD, BRIGHOUSE, WESTYORKSHIRE, HD6 1QF. + 44 (0) 1484 405600 +44 (0) 1484 405620
sales@marstair.com www.marstair.com
TEL: FAX:
EMAIL: WEB:
This manual suits for next models
29
Table of contents
Other TEV Air Conditioner manuals
Popular Air Conditioner manuals by other brands

Fujitsu
Fujitsu ASYG 09 LLCA installation manual

York
York HVHC 07-12DS Installation & owner's manual

Carrier
Carrier Fan Coil 42B Installation, operation and maintenance manual

intensity
intensity IDUFCI60KC-3 installation manual

Frigidaire
Frigidaire FAC064K7A2 Factory parts catalog

Sanyo
Sanyo KS2432 instruction manual

Mitsubishi Electric
Mitsubishi Electric PUHZ-RP50VHA4 Service manual

Panasonic
Panasonic CS-S18HKQ Service manual

Panasonic
Panasonic CS-E15NKE3 operating instructions

Gree
Gree GWH18TC-K3DNA1B/I Service manual

Friedrich
Friedrich ZoneAire Compact P08SA owner's manual

Daikin
Daikin R32 Split Series installation manual