manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Topsflo
  6. •
  7. Water Pump
  8. •
  9. Topsflo TS5 Series User manual

Topsflo TS5 Series User manual

TS5 Series Instructions
Solar DC Circulation Pump
Installation & Operating
Areas of use
Hot Water Circulation
Radiant Floor Heating
Solar Applications
Liquid Transfer
General Purpose Pumping
PV operated easily
For solar system loops, the pump can be powered directly from a PV
panel. The sun comes up, heat builds in the solar hot water panel
and at the same time electricity is made in the PV panel. The pump
slowly starts with the smallest amount of current and pushes the
heated water to the storage tank. It's all too simple and eliminates all
controllers, thermostats and sensors.
Main Features
Voltage: 6V~24V DC(Rated:12V DC)
Max working temperature: 110°C (230° F)
Max system pressure: 10Bar
Low noise:≤45dB far from 1m distance
Long life brushless pump with energy efficiency technology
Soft start at very low in-rush current, good convenient working
directly with PV panel
Min start-up power consumption less than 2 Watt
Advanced magnetic drive technology for static-impeller, without any
leakage for ever
Durable permanent magnetic rotor/impeller and fine ceramic shaft
Heavy duty work, can sustain continual 24 hours’ work
Low power consumption, low or no maintenance
Motor protective functions:
a. Protection against dry operation.
Drivecircuitrycandetectnoorlittleliquidinpumpchamberandwill
stop the pump
b. Excessive temperature.
The pump will slow or stop when the motor temperature increases
beyond rated temperature as a result of elevated fluid temperature
and installed environment temperature, and will automatically
recover when temperature decrease to rated temperature
c. Over load protection.
The drive circuitry is protected against excessive current and load.
Materials of Construction (Wetted Parts)
• Hi-Temp Ryton Plastic- PPS (food grade)
• Brass Inlet/Outlet
• Viton “O” Ring
• Hi-Temp Ryton (PPS) Impeller
• Ceramic Ferrite Magnet
The performance
Max. flow based on discharge pressure of 0 psi and max. head
based on operating pump at shut-off.
Performance data is based on pumping clear water at normal
ambient temperature.
MODEL
PV
MODULE
(W)
MAX HEAD
(M)
MAX FLOW
(L/M)
5PV 5 1.4 8.5
10PV 10 2.3 10
15PV 15 3 11.5
For direct PV operation, real PV output is affected by efficiency of PV
and intensity of sunlight, the full load work of pump is subject to the
sufficient power supply.
Dimensions
CAUTION!
• Check that the pump body and parts have not been accidentally
damaged or that any bolts or nuts have not been loosened in transit.
• To avoid break the inlet&outlet, when connect and tighten the pipe
connections, it’s necessary to reliably fix the hexagonal nut of
inlet/outlet by wrench. (as shown in the following figure)
• Wires have polarity. Red is plus and black is minus. Wrong polarity
will damage the motor.
• Make certain that the system is filled with liquid and that all air has
been purged before start the pump.
• Be sure the power source conforms to the requirements of pump.
• There is a powerful magnet inside the pump liquid end, do not use
any liquid that contains metallic substances such as iron, nickel, etc.
• To avoid the introduction of water into the electronics, keep the
pump body dry.
• Pump should be drained when subjected to freezing temperatures.
Connecting:
Installation & direction
• It is preferred that the pump always remains in a horizontal
direction and pumping upward. (as shown in the following figure)
• It is acceptable for the pump to be mounted under the piping in a
vertical direction.
• The pump cannot be mounted over the piping in a vertical direction
and any position of the motor is over the pump chamber, this can
cause the pump to run dry leading to premature failure of the pump.
• It is recommended that the pump shall be installed in a position
lower than the liquid level of the tank by at least 12 inches (30 cm). If
this distance is too short, air may enter the pump, causing damage.
• To minimize frictional resistance, the shortest piping possible with a
minimum number of bends should be utilized on the inlet or suction
side of the pump.
• Install a water conditioner if you have hard water.
Installing:
Before start the pump:
• Install the pump in correct direction and position.
• Make certain that the power source conforms to the requirement of
pump.
• Be sure the check valve is installed in the proper direction of flow.
• Make certain that the system is filled with liquid and that the air has
been purged.
Start the pump
• Open the isolation valves and any other valves that may have been
closed during the pump installation
• Plug the pump on
• Power cycling the pump several times accelerates the air removal.
If you hear noise initially, this should abate after a short while as air
is purged from around the impeller
If the pump is noisy there may be air trapped in the system. To
purge the air from the pump, turn the pump off and on several times.
To purge the air from the system open a faucet until all the air in
the line has escaped.
• If the noise does not disappear or decrease substantially, change
the pump’s installation direction or position, and purge the system
once again.
Trouble Shooting
Noise in the System
The pump should run smoothly and quietly, the virtual noise intensity
is relative to the pump consumption. During normal operation, an
occasional air bubble may pass through the pump housing causing
a momentary gurgling noise. However, if noise at the pump persists
for any prolonged period, correct the problem (see below).
• The check valve/non-return valve is mistakenly installed on the inlet
side of pump or in the wrong direction.
• The inlet side shut-off valve is closed or clogged.
• There is air trapped in the pump housing, turn the pump on and off
several times to see if the air pocket can be “bumped” out of the
pump and if not, then open a faucet for manual venting until all the
air in the line has escaped.
• The untight pipe connections permit air into the loop.
• The pump was mounted over the piping in a vertical direction, the
rotor maybe be surrounded by air and no liquid lubricate the bearing,
dry running virtually (change installation direction and purge of air)
• There is sediment or crimps blocking the rotor/impeller.
• The rotor bearing has worn due to dry running causing the rotor to
wobble during operation.
Solar DC Circulation Pump
Installation & Operating
Pump Operating Intermittently or Not at All
• Error in polarity connecting (will damage the motor).
• No or insufficient power to the pump.
• Dry running protection is action, need switch the pump on again.
• Over-temperature protection is working, will resume normal
running when the temperature decreases.
• The ceramic bearing of rotor is worn or damaged, need replace the
rotor/impeller.
• There are sediment or crimps in the recirculation line that would
restrict the flow, please clean the impeller.
If above reason can not resolve the problem, please unplug the
pump several times.

This manual suits for next models

3

Other Topsflo Water Pump manuals

Topsflo TD5 User manual

Topsflo

Topsflo TD5 User manual

Topsflo TD5 Manual

Topsflo

Topsflo TD5 Manual

Popular Water Pump manuals by other brands

Sears Craftsman 390.304051 owner's manual

Sears

Sears Craftsman 390.304051 owner's manual

Crane BARNES 8XSHDA Installation and operation manual

Crane

Crane BARNES 8XSHDA Installation and operation manual

Pearl JACKY Installation and operating instructions

Pearl

Pearl JACKY Installation and operating instructions

Graco President A Series Instructions-parts list

Graco

Graco President A Series Instructions-parts list

Oase ProMax Pressure Well 6500/10 operating instructions

Oase

Oase ProMax Pressure Well 6500/10 operating instructions

Truper BOAP-1/2A manual

Truper

Truper BOAP-1/2A manual

Utilitech 148013 manual

Utilitech

Utilitech 148013 manual

Finish Thompson VKC5.5 Series Installation and maintenance instructions

Finish Thompson

Finish Thompson VKC5.5 Series Installation and maintenance instructions

TMG TMG-50TWP product manual

TMG

TMG TMG-50TWP product manual

Marco 164 662 13 - UP2/A 24V Instructions for use

Marco

Marco 164 662 13 - UP2/A 24V Instructions for use

Waldbeck Fontanica S45 manual

Waldbeck

Waldbeck Fontanica S45 manual

Star UTHALC manual

Star

Star UTHALC manual

Zoeller 1261-0001 Quick reference guide

Zoeller

Zoeller 1261-0001 Quick reference guide

GORMAN-RUPP PUMPS VG Series Installation, operation, and maintenance manual with parts list

GORMAN-RUPP PUMPS

GORMAN-RUPP PUMPS VG Series Installation, operation, and maintenance manual with parts list

Johnson Pump SPXFLOW TopGear BLOC Series instruction manual

Johnson Pump

Johnson Pump SPXFLOW TopGear BLOC Series instruction manual

Clarke CBM100SS Operation & maintenance instructions

Clarke

Clarke CBM100SS Operation & maintenance instructions

JABSCO 18330 Series quick start guide

JABSCO

JABSCO 18330 Series quick start guide

Dankoff Solar SunCentric Series Installation & service manual

Dankoff Solar

Dankoff Solar SunCentric Series Installation & service manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.