
ElectricalCodeInformation
CompliancewithLocal,State,andNational Codes is amuston every HVACInstallation.This page
discussesthe criteria regarding minimum working spaces as definedinthe2002NationalElectricCode.
Themain concern is thesafetyoftheHVAC service/maintenanceperson.Minimumworkingclearances
arespecifiedin the NationalElectric Code(NEC)Article110.26
Forelectricalequipmentthatfrom ground to power thevoltage is 600 volts orless:
TheNational Electric Code specifically statesthatserviceareaaroundelectricalequipmentshallprovide
sufficientaccess,andshallbeproperlymaintainedinordertopermitsafeoperationandmaintenanceofthe
equipment.Table110.26aswellasthefigures beside the table describetheminimum clearance for proper
serviceandaccesstoelectricalequipment.
Traneresidential and light commercial condensingunitsrangingfrom1to6tonrequireaccesstotheside
servicepanelasindicated on theprevious pages to gainaccess to theelectrical controls.
Condition 1
(3 ft min. for 151 - 600 V)
Condition 2
(Space would increase to 3 1/2 ft for 151 - 600 V)
Condition 3
(Space would increase to 4 ft for 151 - 600 V)
Minimum Clear Distance
Condition 1 Condition 2 Condition 3
Nominal
Voltage to
Ground
0-150 900 mm (3 FT) 900 mm (3 FT) 900 mm (3FT)
151-600 900 mm (3FT) 1 M (3.5FT) 1.2 mm (4FT)
Note: Where the conditions are as follows
Condition 1 - Exposed live parts on one side and no live or grounded parts
on the other side of the working space, or exposed live parts on both sides
effectively guarded by suitable wood or other insulating materials. Insulated
wire or insulated busbars operating at not over 300 volts to ground shall not
be considered live parts
Condition 2 - Exposed live parts on one side and grounded parts on the
other side. Concrete, brick, or tile walls shall be considered as grounded.
Condition 3 - Exposed live parts on both sides of the work space (not
guarded as provided in Condition 1) with the operator between.
Table 110.26(A)(1) Working Clearances
The table and figure below are excerpts from the National Electric Code 2002:
Pg. 15
Reprintedwithpermissionfrom NFPA70-2002, National Electrical Code®,Copyright© 2001, National Fire
Protection Association. This reprinted material is not the complete and official position of the NFPA on the
referenced subject, which is represented only by the standard of it’s entirety.
National Electrical Code and NEC are registered trademarks of the National Fire Protection Association, Quincy, MA.
Electric
switchboard
150V nominal
or less
Effectively Insulated
Electric
switchboard
150V nominal
or less
Electric
switchboard
150V nominal
or less
Electric
switchboard
150V nominal
or less
Exposed
Live Parts
Exposed
Live Parts
Exposed
Live Parts
Grounded parts, concrete, etc
3’
3’
3’