Trust RB01-TFB36 Series User manual

TRUST AIR CONDITIONING EQUIPMENT CO.
Prepared By: Engineering & R & D Department.
Shiraz- May 2017
AIR HANDING UNIT
TRUST AIR CONDITIONING EQUIPMENT CO.
Prepared By: Engineering & R & D Department.
Shiraz- May 2017

·.
9TRI:IST
·
Air
Conditione
'
rs
· ...
····ElectriC Air Haridler
. .
RECOGNIZE SAFETY SYMBOLS, WORDS
AND
LABELS
.1
'
INTRODUGION
.
...
: ·.
.'
...
~
..
..
·: :
....
·-:
~
·.·
...
:
......
2
INSPECTION
AND
UNPACKING -: :
....
•
...
, ·
..
.-
. ;
....
2 ·
. '
NOTES
TO INSTALLER
............
~
-
-.;
."
..........
2
·INSTALLATION
..........
;
~
. : .·.'. '
...
:
.....
~
.
~
...
2
. .
Codes
..
·
...
·
..
·:
......
·
...
; . ..
~
.··.·
.....
·
....
..
~
...
2
Power
Considerations
...
·
...
~
...........
.
.....
2
Electric
Heat
Kits
............................
2
·
Location
:
........
..: ·.·: ;·
.......
·
.............
..
;2
C:lea
·rances
...
~
....
·. :
....
.: .
~
·.·
...............
2
Upflow
AppliCation
.......
·
..
·
.....
.;
........
·
..
3
Hori~ontal
Applicaton
.........
.·
..
_·
....
~
:
..
.. .4 .
·· .
Downfl.ow
Applicatio
_n
..
·
...........
.. ·
..
.'
..
~
...
5
Connett
Refrigerant
Piping
....
~
....
,.. : ;
......
6
. •·Factory
and
CFielq
~
installed
Expansion
Valv~s
.....
6 ·
Ductwork
·
.......
~
.....
~
...
.
....
~
...
.
..
..
.-
....
7·
Return
Air
Ducting
...............
;
..........
7
. \ . . . . . .
Return
Air
Platform
Height
....
~
..
~
:
.....
~ ~
...
7 ·
LINE
VOLTAGE CONNECTIONS
..
·
...•....
.':
........
7
24 VOLT CONTROL
SYSTEM
......•...............
8
CONDENSATE PLUMBING . .
.......•.....
·
...
.'
.
....
8
.WIRING.OIAGRAM .
....
..
..........
;
..
~.
: ..
........
9 .
DIMENSIONS .
~
.......
:
........
~
.....
:
....
·
....
10
·BLOWER
SPEED/STATIC
OPERATION TABLE
........
11
ELECTRIC
HEAT KIT
............................
12
.. .
Heating
Specifications
..
,
.........
_.
.........
13
SERIES
NOMENCLATURE
.....................
.
..
14
. NOTE:
THESE INSTRUCTIONS .ARE INTENDED AS
AN
AID
TO
QUALIFIED
SERVICE
.PERSONNEL
FOR
PROPER
INSTALLATION, .
ADJUSTMENT
AND
OPERATION
OFTHIS
EQUIPMENT. READ
THE ENTIRE INSTRUcTION
MANUAL
THOROUGHLY
BEFORE
ATTEMPTING INSTALLATION OR OPERATION. ·
1
•'
·
.·
':·
....
r:
·

. . RECOGNIZE SAFETY SYMBOLS,
WORDS
AND
LABELS
. .
What
You
Need.To
Knqw
About
Safety
lnstrudions
Warning and
Important
Safety Instructions appearing in this·
manual are
not
meant
to
cove(all possible conditions and
. situations
that
may occur:'
common
sense,
caution anq care.
must be
exerCised
wben operating
or
cleaning tools and .
·
equipment
·. ·
~
··
·
Always
contad
..
yqur dealer/distributor, service agent
or
· manufacturer
about
problems
or
conditions you
do
not
unde~tand
.
· -
A This
is
the
safety alertsymbol.
It
is
used
to
alert you
to
potential personal injury hazards. Obey all safety
messages
.
that
follow
this symbol
to
avoid possible injury
or
death:
A DANGER A
DANGER indicates an imminently hazardous situation which,
if
not
avoided,
will
.result in'
death
or
serious injury.
A
WARNING
A
WARNING
indicates a potentia-lly hazardous situation which,
if
not
.avoided, could result.in death
or
serious injury. ·
I A "CAUTION A I ;
.....
...
~
CAUTION indicates a potentially hazardous situationwhich,
if
not
avoided, may result in
minor
or
moderate injury.
.CAUTION
CAUTION
used
·witho.ut
the
safety alert symbol indicates
.apotentially hazardous situation which,
if
not
avoided,
may result
in
property damage. ·
-
,--:---
1
·.,
A
WARNING
A
IMPROPER
I~STALLATION,
ADJUSTMENT,
ALTERATION, SERVICE
OR
MAINTENANCE
·
cAN
.
CAUSE INJURY, PROPERTY
DAMAGE
OR LOSS OF LIFE. ·
READ
. . THIS ·.
MANUAL
·
COMPlETELY
BEFORE
BEGINNING
ANY
WORK
AND
FOLLOW ALL SAFETY
.PRECAUTIONS.
A QUALIFIED · · INSTALLER
MUST
PERFORM
.
INSTALLATION
AND
SERVICE.
DO
·NOT . DESTROY THIS ·
MANUAL
•. PLEASE READ
CAREFULLY
AND
KEEP IN A SAFE PLACE FOR FUTURE
REFERENCE BY A SERVICE TECHNICIAN•
. THESE ·INSTRUCTIONS.
~RE
INTI;NDED
AS
AN
.All;) TO
QUALIFIED SERVICE
PERSONNEL
FOR
PROPER
INSTALLATION, . ADJUSTMENT
AND
OPE
.RATION OF
.· THIS
COMPONENT.
.
READ
.THESE ··
INSTRUCTION
~
S
THOROUGHLY BEFORE ATTEMPTING INSTALLATION .
OR
OPERATION,
FAILURE TO . FOLLOW .THESE
iNSTRUCTIONS
MAY
. RESULT . .IN
IMPROPER
INSTALLATION
~
ADJUSTMENT,
SERVICE
OR
· .
MAINTENANCE,
POSSIBLY
RESULTING . IN
FI
.RE, .
.
EL~Cf.RICAL
SHOCK, PROPERTY
DAMAGE,
PERSONAL
.INJURY OR DEATH.
B.
EFORE
.
PERFORMING
·
ANY
WORK
ON
THIS
EQUIPMENT, POWER.SUPPLY MUST
BE
.TURNED OFF AT
, THE
HOUSEHOLD
SERVICE
.
BOX
TO
AVOID
THE
.
PO
·
SSIBILITY
OF
,S.
HOCK,
INJURY,
DAMAGE
TO
EQUIPMENT, OR DEATH. .
DO
NOT
STORE
OR
USE
GASOLINE
.
OR
.
OTHER
FLAMMABLE
VAPORS
AND
.
LIQ
-
UIDS,
OR
OTHER
COMBUSTIBLE
MATERIALS
INTHEVI
.CINiTY
OF
THIS
AIR
HANDLER
OR
ANY
OF
ITS
MATCHING
SYSTEM
.
COMPONENTS
(COND
.
ENSING
UNIT, HEAT
PUMP
OR
1
t
:
URNA~E}.
. .
\

NOTES TO INSTALLER
The words "SHALL" and "MUST" indicate a requirement which
is
essential
to
satisfactory and safe
p~oduct
·
performance.
The
words "SHOULD" and·
"MAY"
indicate a recommendation
or
advice which
is
not
essential and
nqt
require.d
but
which may
be useful
or
helpful.
The instructions are·
for
the
use
of
qualified individuals specially
trained
and e:Xper:ienced in
the
installation
of
this
type
·
equipment
and related system components. · · ·
Installation and .service personnel are required by some locales
to
be licensed.
Persons
not
qualified shall :
not
·install this
equipment
nor
interpret
these instructi6ns.
· INTRODUCTION
Models A*PB and Plare designed
for
flexibility
and
can
be
used
for
upflow,
horizontal
or
downflow
applications. These .units
are available
for
systems
of
18,000
through
60,000
BTUH
.
nominal.cooling·capaci.
ty
·. Factory authorized electric heater kifs.
are available in 5
kW
through
.
iO
kW
·
sizes,
.
See
.product
..
specifications
for
available accessory kits.
INSPECTION
AND
UNPACKING
A
thorough
inspection
of
the
shipping container
r:nust
be made
immediately upon receiving your unit. Look
for
any punctures
or
openings, and
if it
appears damage
has
occurred,
note
it
em
the
fr~J.ght
bill
before
signing. Contact delivering carrier.
immediately
to
inspect damage. Do
pot
begin installation
work
should begin
until
this inspection
is
completed.
INSTALLATION
Codes ·
The installer must·comply
with
all local, state and federal codes
and/or regulations
pertaining
to
this type
of
equipment
and its '
installation.
Such
co<;Jes
and/or regulations shall
take
precedent
over
any
recommendations
contained
herein.
If
there
are
no
loca
I
codes
on
the
subject,
installations
sha
II
be
made
in
accordance
with
the
Nationa
I
Electrical
Co9e
(N
EC)
and
·
recommendatipns
made
by
the
National
Board
of
Fire
·
Underwriters. ·
Power
Considerations
The
installer
shall check
available
..
power
to
make
certain
it
matches
the
unit
name
plate
rating
and
that
constant
voitage
·
can
be maintained on
the
unit. Unsatisfactory performance
or
a
possible
hazard
could
otherwise
result.
The
loca
·l
power
company should be contacted
with
questions concerning
power
supply. · · ·
Electr:ic
Heater
Kits ·
Location
All
models are approved
for
alcove,·closet, and attic installatic
in
the
upflow,
downflow
or
horizontal
position.
Refer
to
tt
appliCable
section
of
thi$
manual
on
pages 3-5
for
spec.if
installation instructions·on _
eac
h position.
. r
l>
•
The
air
handler
must
be installed in a level position and shou
be
located
for
ease
in
connecting
air
ductwith
proper
a
distribution. . ·
. . .
Exterior surface
of
cabiriet may sweat
when
unit
is
installed
non-air-conditioned
space
~uch
as
attic
or
garage~
Installer
mu
provide
protection
such
as
full-size
auxiliary
drain
pan on«
units.
Be
sure
to
allow
for
filter
access
for
periodiC user servicin
·· In
addition,
caulking
must
be
applied
around
the
power
ar
control
wires
entering
the
control
box.
This
will
"pre.vent c
leakage
into
·
and
condensate
from
forming
.inside
the
contr
box.· ·
Clearances ·
Clearances
from
the
air
handler
to
the
combustibles are
ze
· inches
from
all sides,
top,
and
bottom;
one inch
from
dischan
air plenum; and
the
duct
within
·36 inches
of
the
plenum.
..
·
Provide adequate space
for
servicing
the
air handler;
at
least
inches.
All
service and maintenance can be performed
from
t
·
front
access
.doors
of
the
air handler.
-..J
A WARNING A
DO
NOT,· UNDER.
ANY
.CIRCUMSTANCES,
CONNEC1
RETURN DUCTWORK
TO
ANY
OTHER
HEAT-PRODUCIN~
DEVICE SUCH AS FlREPLACE INSERT, STOVE, .
ETC
UNAUTHORIZED
USE
OF
SUCH
DEVIC.
ES
MAY
RESULT
1•
FiRE, CARBON
MONOXIDE
POISONING, EXPLOSION
PERSONAL INJURY,
OR
PROPERTY DAMAGE.
.
Only
EEB/EEC
series electric heater
kit
may be
install~d
intoth
.e .
air
handler.
See
Electric
Heat
section
on
p·
age
12
for
more
information~
' )'
2

Upflow
Applicaton
In an
upflow
application normally a duct
is
employed
as
a return air means
as
shown in Figure 1
below
or
a
platform
is
installed
as
in Figure
2.
UpflowInstallation With Return Duct
DISCHARGE
DUCT
(600 FPM)
~
"'-----~-
T
24" MINIMUM.
AIR
HANDLER
(MAY ALSO BE
DOWNFLOW)
RETURN DUCT WITH A MINIMUM
OF
1/2" FIBERGLASS DUCT LINER (500 FPM).
REFER TO LOCAL CODES.
Upflow
Installation With Return Platform
·. .
DISCHARGE DUCT (600 FPM)
--~-
.
-T
24" MINIMUM
AIR HANDLER
RETURN PLATFORM LINED WITH
1" FIBERGLASS INSULATION.
REFER TO LOCALCODES.
3
=.,_____
-.-
...,.._-_..,---,---=·.-=.- "
,·
-.
-.-·.
..,.--- . . .
. )

Horizontal
Application
·This
type
of
position
is
lJSUally
used in an
attic
or
crawl space. The
air
.·
handler may be laid on
ttie
left
or
right
side
for
horizo·ntal applications.
The factory-installed coil
is
intended
for
left-side-down installation.
This
type
of
installation requires a
retur
·n air duct
to
be attached
to
the
air handler-inlet. The opposite end
of
the
return air duct
is
then
routed
to
a
return
air
grille
mounted
to
the
ceiling
or
wall. This duct
MUST
be
no smaller
than
the
inlet
opening
of
the
air handler.
For
Horizontal
Right
Application:
1.
Remove.front
.
panel~
from
the
air handler.
2.
-Remove coil assembly
from
the
a1r
handler.
3.
Remove horizontal drain pan
from
left
hand side
of
air handler and
re-install on
right
hand side. Change splash baffle loeation
from
left
hand
to
right
hand side
of
drain pan
flan~e.
·
4.
Remove
the
ho_rizontal coil support bracket
from
the
right
hand side
of
the
air handler.
5.
Reinstall coil assembly in
the
air handler.
·
6.
R·
eattach
coil
support
bracket
to
the
left
hand
side
of
the
air
handler.
7.
Replace
front
panels.
Horizontal
Installation
SERVICE
PLATFORM · AIR HANDLER SUPPORTS
(FIELD SUPPLIED)
4
A CAUTION A
Horizontal applications in unconditioned·areas,
such
.
as
attics
above
a
ceiling,
require
special
.
pre~autionary
mea~u(es.
An
aux'ili.
ary
drain
pa·n
havmg
at
least
two
inches overall clearance around
the
unit
MUST be
field-fabricated
and installed
as
shown below. ' ·
The
drain
outlet
and
drain
:
line
for
the
auxiliary
drain pan need
not
be trapped
but
should be·sloped
to
a suitable drain.
A CAUTION A
For
optimum
condensate
drainage
performance in
horizontal
installations,
unit
should
be
leveled
along
the
length
and
width.
Failure
to
follow
this
caution may result iri product
or
property
darrlage.
A CAUTION A
A
P~type
trap must
be
installed
in
the primar)t
dr~in
line
as
shown in figure 3 below.
.t
RETURN AIR
AUXILIARY
DRAIN LINE

Downflow
Application·
·
.·
Relocating Coil
The coil
MUST
be'relocated
for
downflow
application.
1. Remove coil
access
door.
"'
2.
~I
ide coil
out
of
air handler.
3.
Remove
coil
.rack
from
air
handler
by
removing
·
screws
from
side
of
air hanpler.
4.
·Relocate rack in a·
ir
handler
as
shown
.iri Figure 4
using
screws
from
side
of
air handler.
5.
Turn air handler
into
downflow
position.
6.
Slide refrigerant coil
into
air handler.
7.
Reverse
and replace air handler door(s).
Installation:Cbnsiderations
··
·
•
No
downflow
sub:.base
is
required
with
.
this
~
-
ir
handler, however, localcodes may require
the
use
of
a non..:combustible sub-base
when
used
with
electric heater kit.
.•
An
"L"
or
"T"
shaped duct enclosure
MUST
be
used
.
as
a supp_ly plenum. No registers
or
outlets
SHALL
be
located directly below
the
air handler supply outlet.
•
Size
and frame the
floor
opening
as
shown in Figure
5.
Refer
to
the
Dimension
drawing
on page 10. Care
MUST
be taken
not
t·o
overcutthe
floor
opening.
•
Caulk
around
the
floor
opening
with
a
non-
f-lammable caulk
such
as
silicone.
Set
.
the
air handler
in place and secure
the
airhandler properly.·
•
Allow
access
to
the
low
voltage
connection
by
bVilding
the
platform
so
that
there
is
a minimum
of
5 /2u between
the
floor
and
the
unit
flange. .
Ret~m
·
Air
Filter Clearance
On
downflow
applications, certain ·coil models
~ill
protrude
from
the
top
of
the
air handler (coils greater
than
15" tall on A24
through
A3G
air handlers and coils
greater than 18".on A42
through
AGO
air handlers).
On
these models,
the
return air
filter
may
be
removed and
a .separate
filter
grille may be installed
for
closet
applications. ·
If
this
method
is
not
desirable, cabinet extension
kit
No.
G5-1647
.
for
A24, A30, and
A3G;
or
No.G5-1G49
for
A42,
· .A48, and
AGO
may be ordered. The extension
kit
screws
to
the
side
of
the
air-
handler and extends
the
length
of
.
the
air handler coil cabinet. ln.addition,
the
kit
includes .
a
filter
_compartment and·door.
Emergency Drain.Opening
The
indoor
coil emergency drain opening must be
used
for
this application. Refer
to
page 8
for
instructions on
condensate tubing. ·
R-:locatlng Coil
for
Downflow
Position .· ·
FILTER
DOOR
UP
FLOW
POSITION
.
FILTER
DOOR
Remove
the
three
screws
on
both
sides.
Flip over
and
replace
in
new position using
pre-punched holes.
Supply Plenum Floor Opening
AIR HANDLER·
----
'1!1·
UNIT
LANGE
SUPPLY
OPENING

Connect
Refrigerant
Piping
Use
field
supplied
~ubing
of
refrigerant
grade. Suction
tube
m
.-
List
be
insulated.
Do
not
use
damaged,
dirty,
or
contaminated
tubing
because
it
may
plug
refrigerant
flow
control
device. ALWAYS evacuate
the
coil and
field
supplied
tubing
before
opening
outdoor
unit
~ervice
valves.
Factory
and
Field-Installed
Expansion
Valves
1.
The
bulb
and capillary
tubing
should be
routed
outstde
of
the
case.
Make
sure
the
capillary
tube
will
not
contact
any sharp edges
of
the
case.
On
f~ctory
ins.talled
expansion valves,
the
adjustable_
s,ensmg
~ul~
1s
not
permanently
installed
onto
the
coils
vapor
lme m
order
to
allow
easy removal
during
installation.
Vapor
line
Sensing
bulb
attached
with
clamps
8 p'clock 4 o'clock
Attach
bulb
to
vapor
line
at
four
or
eight
o'clock
position
A CAUTION A
THE
TXV
VALVE CAN
BE
DAMAGED
BY EXTREME
HEAT.
PROPER
PRECAUTIONS SHOULD
BE
TAKEN
TO
AVOID
OVERHEATING
THE
TXV
VALVE
AND
CAUSING
DAMAGE
TO
THE
INTERNAL COMPONENTS.
A CAUTION A
THE
TXV
SENSING
BULB
· CAN
BE
DAMAGED
BY
EXTREME HEAT FROM BRAZING.
THE
BULB
SHOUlD
·
BE
RE
-
MOVED
BEFORE
PERFORMING
ANY
BRAZING
PROCEDURE .
AND
NOT INSTALLED UNTIL AFTER
THE
VAPOR
AND
LIQUID LINES ARE BRAZED
AND
LEAK
CHE(:KED.
6
2.
To assure accurate sensing and
the
best performance
the
bulb
should be placed on a
horizontal
section
of
the
·
vapor
line
at
the
four
or
eight
o'clock position and
at
·,.
least
6"
from
the
coil
manifold.
· ·
" A
WARNING
A
ALWAYS HAVE A
FIRE
'EXTINGUISHER AVAILABLE
.WHEN WORKING WITH
AN
OPEN .fLAME..
ALWAYS
USE
SAFETY GLASSES, PROTECTIVE
CLOTHING,
AND
WORK GLOVES.
~·
' 0
<jg
TXV valve can be
accessed
through
the
valve cover-plate
on
the
front
of
the
air handler.
3.
Attach
the
bulb
securely
with
the
copper strap provided.
4.
Insulate
the
bulb
thoroughly
with
a suitable insulation
materiai
such
as
cork tape.
5.
Coils ·
with
TXVs should be charged 10-12 degrees
(+
or-
one degree)
of
sub-cooJing.
This
supercedes any
subcooiing value listed
with
condensing unit's literature.
For .
the
majority
of
installations
no
adjustment
·
to
the
TXV setting
is
required. However,
if
the
measured
superheat
is
less
than
4°
or
greater
than
so
· an
adjustment
is
required. The
adjustment
st~m
i~
at
the
base
of
the
valve
under
the
flare
nut. To mcrease
superheat~
tighten
the
stem clockwise and
to
decrease
superheat, back-out
th~
ste,n1
counter-clockwise.
Us~
a
1t4"
refrigeration
service wrench
for
this
function.
·
NOTE:
When
removing
refrigerant,
always
use
standard reclaim
procedures.

Ductwork
This
air
handler
shall
not
be
installed
without
supply
plenums
a·nd proper ducfing. Connectsupply air
duct
over 1/2" flanges on
supply
air
opening.
Secure
duct
to
flang
·e
and
seal
connection.
u'
se
flexible connectors between
ductwork
and
unit
at
discharge
connection.
Ductwork
passing
through
unconditioned
space
must·
.be
insulated and covered
with
vapor barrier.
Return
Air
oUding
The dimensions
of
the
return
air duct
or
platform
must
be
at
a
minimum
the
same size
as
the
return
air
opening on
the
air
handler, regardless
of
the
air handler position. ·
When framing a return air
platform,
the
opening size should be
.
as
shown ·
below
;
If
the
air handler
is
to
be installed in a closet,
be sure
to
allo\1\,-room
fqr
wiring
and refrigerant lines.
iJ
TopVi~w
~
ICI
..
·•ID_I.F
-i Framed-in t
Opening
Air
B Handler
1
Bottom
·
-· 1
-
...E._
I -A
..
I
MOOEL A B c D E F
IN
CM
·
IN
CM
IN
CM
IN
CM
IN
CM
IN
CM
i
RB01-
TFB36*
14
37.3
141/4
36.2
2 5 2 5 4
10.1
4
10
.1
RB01-
TFB48*
1631
81
41.6
221/4
56
.5 3
7.6
3 7.6
1314
4.4
2 5
RB01-TFB60
* 1
6318
41
.6
.
221/4
56.5
3
7.6
3
7.6
.
1314
4.4 . 2 5
I
Return
Air
Platform
Height
If
the
air handler·
is
to
be used in
the
upflow
position,
the
height
of
the
return air
platform
should be no smaller
than
the
height
listed
below
for
the
specific model
of
air handler.
Platform
Model Height
Inches
Cm
v
RB01-TFB36DXN02/SOON
12NNW1
A01
14
35.6
RB01-TFB48DXN02/SOON12NNW1801
16
40.6
RB01-TFB60DXN02/SOON12NNW1801
18
45.7
7
LINE VOLTAGE
CONNECTIONS
A WARNING A
. BEFORE PERFORMING ANY WORK
ON
THIS EQUIPMENT,
POWER
.·
SUPPLY
MUST
BE
.
TURNED
OFF
AT
THE
HOUSEHOLD SERVICE BOX TO.AVOID THE POSSIBILIT_Y
OF SHOCK, INJURY, DAMAGE TO EQUIPMENT
OR
DEATH.
1.
The
power
supply can be connected
through
the
right
si1
or
top
of
the
air
handler.
Conduit
knockouts are providE
for
112",
3t4",
1
",and
1114"
conduit. ,
2.
Refer
to
the
Control System section
for
recommended lo\
voltage
wire
gauges. · ·
3.
See
Power
Supply
Table
on
page
9
for
power
.
supp
l
specifications.
4.
Use
only copperconductors
for
supply
wiring.
5.
The
air
handler
must
be
permanently
grounde
a
The ground lug
is
located in
the
field
wiring
box.
Conduit
Knockout
Locations
..
Top
of
air
handler
0
00
I
Conduit knockouts
Grounding
Lug
Location
Field
wiring
box
(detail)
Grounding lug
Right side
of
air handler
Conduit knockouts
0

:
24
VOLT
CONTRO~
$YSTEM
A WARNING A
BEFORE PERFORMING
ANY
WORK
ON
THIS EQUIPMENT,
POWER
SUPPLY
MUST
BE
TURNED
OFF
AT
THE
HOUSEHOLD SERVICE BOX·
T0
AVOID.THE POSSIBILITY OF
SHOCK, INJURY, DAMAGE TO EQUIPMENT,
OR
DE~TH.
A WARNING A
IMPROPER
INSTALlATION
OF THE ELECTRICAL WIRING
OR THE HEAT
ASSEMBLY
MAY
RESULT IN FIRE, SERIOUS
PERSONAL INJURY,
OR
DEATH. .. . . . .
Connection
to
unit
. ., .
Wire
low
voltage in accordance
with
wiring
label
on
the
blower.
Use
no. 18 AWG
wire
to
make
the
low
voltage connections
between
the
thermostat,
the
unit,
and
the
outdoor
equipment.
If
the
thermostat
is
located more
than
100
feet
from
the
unit
use
16
AWG wire.
All
wiring
must be.
NEC
Class
1 and must be
separated
from
incoming
power
leads. ·
The
thermostat
preheat
anticipator
should be adjusted
to
match
the
current
listed
below
for
the
EEC
model
heat
assembly
to
be
installed. -. ·
.-
THERMOSTAT
EEC
HEATER MODEL
TYPE 5 7.5 . 10 15 20
SINGLE STAGE .4 .4 .4 .8 .8 .
TWO 1ST NIA N/A. N/A .4 .4
STAGE 2ND N/A N/A · N/A .4 .4
When used
with
a
heat
purnp,
the
heat
output
must be staged
for
models above 10 kW.
W1
should be
wired
as
auxiliary
heat
to
assist
the
heat
pump. W2 must only be
wired
as
emergency
heat. Both stages
of
heat
should
nev~r
be
wired
so
as
to
be
energized
while
the
heat
pump
is
operating.,
See
the
Blower
Speed/Static Table
for
maximum all.
owable
auxiliary first-stage ·
heat.
All
EEC
series .electric heat assemblies over
10
kW
have
b~eakers
factory-installed on
the
heat
as~embly.
- . I
Transformer
Information
The
low-voltage
transformer
is
equipped
with
a 208-
or
23E>-volt
tap. The
transformer
is
factory
wired
for
230-volt
op~ratioh.
For
208-volt operation, remove
the
yellow
.
wire
from
the
230-volt
terminal.and install
it
onto
the
208-volt terminal.
The acceptable voltage
range
for each
tap
is
as follows: ·
Tap
Voltage
Range
230
207-253
208
187-229
Time
Delay
Relay
Information
A
fan
relay
is
provided
to
control
the
operation
of
the
indoor
fan
motor.
All
models are equipped
with
a
time
delay "OFF"-
type
fan
relay which
will
allow
the
fan
motor
to
continue
to
·
operate
for
a preset
time
after
the
relay
is
de-energized:
8
--
--
...
CONDENSATE
DRAIN
PLUMBING .
A
CAUTION
A
.. : .
For
downflow,
or
any
installation
where
condensate
··
overflow
could
create
a
hazard
or
water
damage,
the
emergency
drain
fitting
MUST
be
used. The
emergency
drain MUST be
left
open.
If
the
emergency
drain
has
to
be
piped
away.from
the
air
handler,
its
·
outlet
.
MUST
be
installed in a location
that
would
allow
any drainage
to
be
immediately noticed. •
Install condensate
drain
trap
as
close
to
the
coil
as
possible.
··
Use
drain
connection
size
or
larger.
Do
not
operate
unit
·
without
trap
(see
illustration
below.)
Unit
must
be
level
or
slightly incline-d
toward
drain.
Condensate Drain Trap
A
CAUTION
A
1.
Do
not
connect
the
drain line
to
a closed sewer.
·
2.
Neverterminate
an
open
sewer
or
drain
connection
within
the
return
air
duct,
platform
or
return plenum.
3.
Pitch
the
drain
line
at
least 114"
per
foot
away
from
the
drain pan. · ·
' . . . .
4
~
If
condensate drain connection
is
onthe
negative side
of
the
blower,
a
trap
must
be installed
to
ensure positive
drainage.
5.
Condensate
drain
lines
should
not
be
reduced
in
size
from
the
connection size supplied:
6.
The dr:ain
line
should
be
insulated
where
necessary,
to
..
prevent
sweating
and
damage
due
to
condei"\Sate
forming
on
the
outside surfac:e
of
the
line.
7.
Test condensate
drain
line
with
water
before '
operating
system. · -
· 8..
If
unit
is
located
in
or
above
a
living
.space-
where
damage
may
result
from
condensate
overflow,
ct
fiet"
supplied,
external
con·
densate
pan should be·installed
under
the
.
entire
unit,
and a secqndary condensate line
(with
appropriate
trap)
should
be
run
from
the
unjt
into
·
the
pan.
Any
condensate
in
this
external
condensate
pan
should
be
drained
to
a
noticeable
place.
As an
·.
alternative
to
using an
exte
·rnal condensate pan, some
localities
may
allow
the
runnin.g
of
a
separate
3/4'~
condensate
line
(with
appropriate
trap)
per
local code
to
a place
where
the
condensate
will
be noticeable;

Wiring
Diagram
8
E
BE
GN
RD
POST
PURGE
FAN
RELAY
CD
1-CIRCUIT
FEMALE
RD
.
BE
.
4-CIRCUIT
FEMALE
BK
w
E 8 WG
KE N R
D
HEAT
CONTROL
RECEPTACLE
FOR
ELECTRIC
HEAT
WHEN
APPLICABLE
&
C W
W2
G
I I I I R
I
LOW
VOLTAGE
CONNECTIONS
I I I I L-
-TO
R_Q_N
THERMOSTAT_
-
I I I L -
~
-
TO
UlN_lHERMOSTAL
-
I I L- - - -
_TQ_Yiz_QN__]iERMOSTAL
-
I L -
--'-
- - - -
TO
VLQN_IHERMOSTAl_
-
L- - - - - - - ·_
TO
OUTDOO~N!l_
- -
POWER
SUPPLY TABLE
SINGLE
CIRCUIT
SUPPLY
REMOVE
&
CONNECT
~
TO
THE
208V
TERMINAL
FOR
208V
OPERATION
YW
CAPACITOR
BK
..
..
...
~
..
.:;·
. .
L1
L2
~~\lit•·
EQUIPMENt
·
GROUND
BK
, .
BLOWER
MOTOR
FIELD
WIRING
FACTORY
WIRING
NOTE:
INSTALL
JUMPER
BETWEEN
W&
W2
FOR
SINGLE
STAGE
HEAT
OPERATION
DUAL
CIRCUIT
SUPPLY
kW
Phase
·
No.
of
MBTUH
Heat
Min.
Max.
Wire
Ground
Min.
Wire
Max.
Fuse
Wire
Size
(2.)
.
Ground
Size
(2.)
230
Supply
2081230
Load
Wire
CD
Fuse
~
Size
(2.)
Size
~
Ampacity
CD
Size
CD
Ckt1
Ckt2
Ckt3
Ckt1
Ckt2
.
Ckt3
VAC
Circuits
Amps
Ampacity
Size
AWG
MM
2
AWG
MM
2•
Ckt1
Ckt2 Ckt3
Ckt1
Ckt2
Ckt3
AWG
MM
2
AWG
MM
2
AWGMM
2
AWG
MW.
AWG
MM
2
AWG
MM
2
0 1 1
5.0
15
14
2.1
14
2.1 - - - - - - -. -- - - - -- - - -
5*
1 1
1'2
.6/17.1
20.9
30
30
10
5.3
10
5.3
- - - -- - - -· -- - - - - - - -
10*
1 1
25.6/34.1
41.7
57
60
6
13.3
10
5.3
..,.
-- - ----- - -
....,
- -
,...
--
15*
1 1or2
38.4/51.2
62
.5
83
90
4
21.2
8
8.4
57
26
-
60
30
-6
13
.3
10
5.3
~
-
10
5.3_
10
5.3
-
20*
1 1or2 51.2/68.2
83.4
109
110
2
33.6
6 13.3
57
53
-
60 60
-6
13.3
6
13
.3 - -
10
5.3
10
5.3 -
-
*kWaoes
not include motorwatts.
CD
Ampacities and
over
current
protec~ion
based on largest airhandler motor load. Refer to specific
mime
plate for exact ampacity and
overcurr~nt
protection size.
Minimum wire ampacity values are used for sizing field power conductors. Refer
to
the National Electrical Code (latest version), Article 310, for sizing conductors. When more than three current-carrying
canductors are in
the
same conduit, the conductor's ampacity MUST
be
derated. See Note 8 ofTable 310 for ampacity adjustment factors.
~
Maximum
size fuse
or
HACR-type circuit breakerfor field wiring protection. .
@Wire size based on 75°C copperwire with no more than three current-carrying conductors in the same condu.it. All wiring
MUST
conform to the National Electrical
Code
and all local codes.
9
-
-
-
-
-

Dimensions
-~+------,--
G
----1
'
·.
~
.
..
~r==========~-.
•l
OUTLETOPENING
l
1
H .
~~--~~~~~--
LOW
VOLT
CONNECTIONS
0
~-----~0-~=~~---~
LINE
VOLTAGE
KNOCK
OUTS
.
,....___.
_I
LOW
VOLT
CONNECTIONS
I
E
K~~~
-
.
..
INLET
WIDTH
INLET·WIDTH
All
dimensions in inches ' '
.Models A B c D E F G.· . H I . J K
RB01-TFB36.* 2 1/4' 3 5/8
~3.
1/4 15 1/4 43 3/8 15 17
22
18 14 ' 16 1/4
~
RB01-rFB48* ' 2 1/4 3 5/8· 13 1/4 ' 15
481/8
19 1/8
21
26 22 16 3/8 22 1/4
l
RB01-TFB60* 2 1/4 3 5/8 13 1/4 15
481/8
.19 1/8
21
26
22
163/8
22 1/4
10

Motor
Speed
Correct
heating
and cooling
motor
speeds MUST
be
used
for
proper
operation.
Refer
to
the
Blower Speed/Static Operation Tabl
below
for
correct cooling speed and
for
minimum
allowable
heating
speed. ·
BLOWER SPEED I STATIC OPERATION TABLE
UNIT
A*PC48A1
MOTOR
SPEED
HIGH
RESISTANCE HEAT
STATIC PRESSURE (IN. WC) ACROSS
HEAT ELEMENT@ MAX. CFM
*20
kW
@.
0.60"
15
kW@
0.45"
60 Hz OPERATION .
CFM @ EXTERNAL DUCT STATIC (IN. WC)
.4
.5
1680 1640 1590
1520
.6
1430
r-------~------~----~--------~----r-------~--------~--------4-----~--~~--~
A*PC4881
MEDIUM
*20
kW
@
0.50"
15
kW@
0.40"
LOW
*20
kW@
0.40"
15
kW@
0.40"
*Specifications applicable
to
upflow
and hor-izontal applications
Air
flow
shown
at
the
following
conditions:
1440 1410 1380
1240
.
1~20
1190
.·
• No
heat
elements in air
handler
. . .
• Decrease
CFM
1%
for
5 kW, 7.5 kW,
or
10
kW
heat
kits. Decrease
CFM
2%
for
15
kW
or
20
kW
heat
kits
•
50
Hertz-
220 volts. Decrease
CFM
6%
for
208
volt
operation
• Standard
air
handler
filter.Dry
coil
airflow
shown
11
1340
1250
1.
150
1100

ELECTRI.C HEATER
KIT
This
unit
is
not
equipped
withan
electric
heater
kit.
A
factory
approved,
field
installed
UL
listed
heater
package
is
available
from
your
equipment
supplier. Heaters
that
are
not
factory
approved could cause damage
which
would
not
be covered
under
the
equipment
warranty.
Installation
Only
EEC
series
electri~
heat
assemblies may be instal.led
into
the
air
handler. Consult installing contractor
for
the
correct
electric
heat
assembly
to
be installed in each model
of
air
handler.
For
ease
of
installation,
it
is
recommended
that
the
electric
heat
kit
be installed before
the
furnace plenum
is
installed. .
A WARNING A ·
BEFORE
PERFORMING
ANY WO.RK ON
THIS
EQUIPMENT,
POWER SUPPLY MUST
BE
TURNED.OFF AT THE HOUSEHOLD
SERVICE
BOX
TO
AVOID
TfiE
POSSIBILITY
OF
SHOCK,
INJURY, DAMAGE TO EQUIPMENT,
OR
DEATH.
1.
Remove
the
upper
access
door
from
the
air handler.
2.
Remove and discard
the
field
wiring
compartment
box by
removing
the
screws
that
attach
it
to
the
right
side
of
the
air handler.
Remove
air
handler
field
wiring
box~
and discard 0 0
' . 0
~
Removetwo .
·
oe.
....
screws
0
9.
<::::
1'
3.
The black and yellow high voltage transformer leads should
be
connected
to
theterminal block or breaker
of
tbe.heat kit.
4.
From
the
electrical
compartment,
remove
the
cover plate
from the element housing.
12
5. Cut
the
wire
tie
holdrng
the
heater plug and
unroll
the
heater
plug harness
so
that
it
will
hang
out
of
the
electrical box.
6. ·Carefully slide
the
heat assembly
into
the
element opening.
Be
sure
the
heater
kit
or
elements do
not
rub
or
scrapeagainst
the
metal
e~ges
or
existing components in
the
electrical box. Guide
the
element support rods into
the
matching holes in the blower
boot
.
7. Make sure
the
·assembly
is
.
botto~~-d
put
agai~
.
~
t
the
element
housing. Install
the
.screws provided
through
the
assembly and
.
into
the
element housing. ·
8.
Connect
the
heater plugs
to
the
heater receptacles.
9.
Slide_
heater
element
in and secure
with
three
screws.
Attach
· wires according
to
w·
iring
diagram
on
p~ge
·
9.
Guide
the
element
support rods
into
· ·
the matching holes in
the
blower
boot
- .
c,
r
Heater
receptacle
. !

HEATING SPECIFICATIONS
ELECTRIC HEAT ASSEMBLY NOMENCLATURE
·
EE
·C 15 B 1
•A
T T T . T T T
ELECTRIC
HEAT
DESIGN k-WAT B=BREAKER 1 = 1 PHASE REVISION
ASSEMBLY SERIES SERIES 230
VOLTS
N=
NO
BREAKER
HEATING TEMPERATURE RISE
Formula:
Temp.
Rise
of =
3160
=
CONSTANT
.
3160xkW
CFM
.
kW
=
kW
RATING
OF
UNIT
CFM
=
AIR
FLOW
AT
SPECIFIED
CONDITIONS
Based
.on 230-volt operation. For voltage
other
than 230,
multiply
temperature rise by.capacity correction factor. Refer
to
CFM
tables
to
. determine Cfm
at
total
external static
pressure in system.
w
TEMPERATURE
R~SE
°F
CFM
TOTALkW
3 5
10
500 19
32
600 16
26
700 ' .
800
40
900 35
1000
32
1100
29
1200
26
1300
1400
1500
1600
•.
1700
1800 . '.
1900
2000
..
.
'
.2100
. 13 .
.
\..}
.
~
.
HEATING
CORRECTION
FACTOR
.
.15
68
59
53
:
47
43
40
36
34
..
32
30
28
26
·25
1-
z 260
t'
::) .250 .
1-+-'--4----+-'--+/----;-+i
~
240
1-+---lf-----t-.....,.r-t-1
~
230-
1+---t-/--+-v~/-+--t-1
< 220
H--+-v--r--+--+---t-1
t-:
.
-210
H-___,.,&.t----+--+-+1
0>
/
200
Ef::::::f:=::±:==±::::i:j
>
~
Q.
Q.
::)
en
.7
~8
.9 1.0 1.1
.
CAPACITY
CORRECTION
FACTOR
For correction
··
of
unit
output~
multiply
the
correction
factor
times
the
kW
rating
at
230 volts.
For
~orrection
of
temperature
rise,
multiply
.
the
correction
factor
times
the
rise ·calculated
for
the
kW
at
230 volts.
20
.70 .
..
63
57
53
49
45
42
39
37
35
33 . ,
32
30

AIR HANDLING UNIT
SERIES
NOM~NCLATURE
.
·
..
··
JRBo
l
J-~~~§]§1~
t[~~GJ§J~~~~
~
~
. .. ·
L:
.Order No.
(2
cha~:acters)
.
01, 02,
...
. -
Product Serie
(f
.character) / .
.
A,B
\
Power Supply (2.characters)'
.-1: Single phase, 3; Three phases
Control Moqe
(l
character) .
·
w:
Wire ,·R: Remote ·
Filter }'ype
(1
character).
N:
Without filter
1: WashableBefore Fan ,
2:
Low Speed Before Fan
3: High Speed Before Fan
..
4:
Bag Before
F~
5:
Hepa AfterFart 6: Bag After Fan ·
Fresh AirSupply
(1
character) . . .
Y:Yes
,-
N:
No ·
,.
··
SEER (2 characters)
<·
10,12,13;14,.
~
.
Pipe Connection Side·(1 chanrcter) ·
R: Right, L:·
Left
~
·
N:
Not Important
.Electrical.
Heater
Power (2 characters)
(Kw)
NO: Without Electrical
Heate~
Skin:
Type (1 character)
S:
Single , D:-Double
Refrigerant(1
_.
character)
1: 134A.,
2:
R22', 3: R407C , 4: R410A
Heatihg.T)'pe (2.
charact~;r)
..
WH
-:
W~ter
Heating , EH: Electrical Heater;
Sll
:Steam Heating,
NO
:NoHea:ting I.
Coqling Type (2 character)
. .. .
CW
: Cooling Water , DX: Cooling DX ,
CH: Cooling & Heatllig , NO: No Cooling
.Cooling CapacitY (2_characters)
' ..
lOOOBtulh
. -
Position (2'charaCters)
• .
V:
Vertical , H: Honzontal ,
B:
Both
Manufacturer (2 chara<;ters)
·-
J .
TF:
TRUST Fedders , TM: TRUST·Midea
TG: TRUST Gree ·,TC: TRUST Chunhin , ...
Product (4 characters)..
,-
RBOl: Residential Air
Conditio~ingSystems,
Blower .
Operating Systems, Air Handling Units
CB01: Commercial .Air Conditioning Systems, Blower
.
Operatin~
Systems,. Air·Haridllng
~nits
. · .
14

TRUST AIR-CONDITIONING EQUIPMENT CO.
Shiraz office: 8 th floor, Alvand Blog., Dostan St.,
Moaliabad Ave., SHIRAZ, IRAN., Post code: 71877-14446
Tel.: +98-71-36341070
Fax.: +98-71-36341094
Tehran office: No. 19- koohe nour St.- Motahhari St.-
TEHRAN, IRAN., Post code: 15876-73111
Tel.: +98-21-89389
Fax.: +98-21-88541903
Ahwaz office: No. 309- Kaveh St.- AHWAZ, IRAN., Post code: 61939-
47911
Tel.: +98-61-32230647-8
Fax.: +98-61-32230647
E-mail: info@trustacs.com
Web site: http://www.trustacs.com
Air Conditioning Systems
Cooling & Heating
This manual suits for next models
2
Table of contents
Popular Fan manuals by other brands

Ebmpapst
Ebmpapst R2E220-AA44-C5 operating instructions

Savoy House
Savoy House 52-120-5CN-SN owner's manual

Domo
Domo DO8123 Instruction booklet

Silvercrest
Silvercrest STV 45 C2 operating instructions

minkaAire
minkaAire DREAM STAR F788L Instruction manual warranty certificate

Ebmpapst
Ebmpapst D2D133-AB02-07 operating instructions

Concept2
Concept2 VS 5020 manual

System air
System air fantech bathfan Select Fit SF Series Installation, operation and maintenance instructions

German pool
German pool EFB-226 user manual

Black & Decker
Black & Decker BXEFD41E Original instructions

Casa Fan
Casa Fan ALU 132 Mounting and operating manual

Siku
Siku SPHERE WiFi 100 user manual