manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. turck
  6. •
  7. Signal Processor
  8. •
  9. turck MS96-11EX0-R/230VAC User manual

turck MS96-11EX0-R/230VAC User manual

Signal processor
MS96 for flow sensors
MS96-11EX0-R/230VAC
Type code MS96-11EX0-R/230VAC
Ident no. 5231400
Ambient temperature -20…60 °C
Operating voltage 198…242 VAC
No-load current I0ð 28 mA
Output function Relay output, changover contact
Device designation É II(1) G D [EEx ia] IIC
Protection type II(1) G D [EEx ia] II C
Ex approval acc. to conformity certificate TÜV 96 ATEX 1098
Protection class IP20
Protection class (terminals/housing) IP20 / IP40
Design terminal chamber
Dimensions 110 x 50 x 75 mm
Housing material polycarbonate/ABS
Connection terminal chamber
Indication: Drop below setpoint LED red
Indication: Setpoint reached LED yellow
Indication: Setpoint exceeded 4 x LEDs green
■ATEX category II (1) G, Ex Zone 0
■ATEX category II (1) D, Ex Zone 20
■single-channel signal processor MS96
■for connection of an intrinsically safe
flow control sensor in zone 0
■adjustment via potentiometer
■6 LEDs for display of the flow state
■intrinsically safe control circuit, [EExia]
IIC
■switch-off delay adjustable in a range of
0…25 s
■wire-break monitoring
■198…242 VAC
■Changeover contact, relay output
Wiring diagram
Functional principle
Signal processors not only supply insertion
and inline sensors with voltage, they also pro-
cess and display the measured signals. De-
vices with MK96…, MS96… and MC96…
housing styles are available. The individual
housing styles are designed for different oper-
ating voltages and feature various output and
supplementary functions. For intrinsically safe
flow sensors it is required to use signal pro-
cessors with intrinsically safe control circuits
of the series MS96…Ex… and MC96…Ex… .
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]
Signal processor
MS96 for flow sensors
MS96-11EX0-R/230VAC
Operating manual
Intended use
This device fulfils the directive 94/9/EC and is suited for use in explosion hazardous areas according to EN50014 and EN50020.
In order to ensure correct operation to the intended purpose it is required to observe the national regulations and directives.
For use in explosion hazardous areas conform to classification
II 1 G and II 1 D (Group II, Category 1 G, electrical equipment for gaseous atmospheres and category 1 D, electrical equipment for dust atmo-
spheres).
Marking (see device or technical data sheet)
Ex II 1 G and Ex ia IIC T6 acc. to EN60079-11 and -26 and Ex II 1 D Ex iaD 20 T95°C acc. to EN60079-11 and EN61241-0 and -11
Local admissible ambient temperature
-20…+60 °C
Installation / Commissioning
These devices may only be installed, connected and operated by trained and qualified staff. Qualified staff must have knowledge of protection
classes, directives and regulations concerning electrical equipment designed for use in explosion hazardous areas.
Please verify that the classification and the marking on the device comply with the actual application conditions.
This device is accessory equipment which features intrinsically safe circuits as well as non-intrinsically safe circuits. It may only be installed out-
side the explosion hazardous area in dry, clean and well monitored areas. If a declaration of conformity or declaration of the manufacturer as a
category 3 device exists, the device may be installed in zone 2. Special conditions for safe operation must be observed. Intrinsically-safe elec-
trical equipment can be connected to the intrinsically-safe connections. All equipment must comply with the demands for operation in the exist-
ing zone of the explosion hazardous area. If the intrinsically safe circuits lead to the dust explosion hazardous zones 20 or 21, it is important to
ensure that the devices connected to this circuit fulfil the demands for category 1D or 2D and are certified accordingly. If the equipment is inter-
connected, it is necessary to perform the "Proof of intrinsic safety" (EN 60079-14). Equipment which has been used once to connect intrinsical-
ly safe circuits to non-intrinsically safe circuits is no longer suitable for subsequent use with intrinsically safe circuits. Relevant regulations ex-
ist for the establishment of intrinsically-safe circuits, mounting of external connection parts as well as the characteristics and laying of cables.
Cables and terminals with intrinsically-safe circuits must be marked. They should be separated from non-intrinsically safe circuits or must fea-
ture appropriate insulation (EN 60079-14). Observe the prescribed clearances to earthed components and connections of other devices to the
intrinsically-safe connections of this device. Unless expressed specifically in the device-specific operating instructions, the approval becomes
void if the device is opened, repaired or actions are performed on the device by someone other than approved experts or the manufacturer. Vis-
ible changes to the device housing, such as brown-black discolourations caused by heat, as well as holes or bulges also indicate a serious dan-
ger. Switch off the device immediately. With the associated electrical equipment the interconnected intrinsically-safe equipment must also be
checked. Inspection of a device with regard to the explosion protection can only be performed by an expert or the manufacturer. The operation
of the devices is only permitted in conjunction with the permitted data printed on the side of the housing. Before any commissioning or modifica-
tion of the device interconnections, ensure that the respective regulations, directives and conditions have been complied with and also ensure
that use is only for the intended purpose and the safety requirements have been fulfilled.
Installation and mounting instructions
Avoid static charging of cables and plastic devices. Please only clean the device with a damp cloth. Do not install the device in a dust flow and
avoid build-up of dust deposits on the device.
If the devices and the cable could be subject to mechanical damage, they must be protected accordingly. They must also be shielded against
strong electro-magnetic fields.
The pin configuration and the electrical specifications can be taken from the device marking or the technical data sheet.
In order to avoid contamination of the device, please remove possible blanking plugs of the cable glands or connectors only shortly before in-
serting the cable or opening the cable socket.
Special conditions for safe operation
The device must be protected against any kind of mechanical damage.
service / maintenance
Repairs are not possible. The approval expires if the device is repaired or modified by a person other than the manufacturer. The most important
data from the approval are listed.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]
Signal processor
MS96 for flow sensors
MS96-11EX0-R/115VAC
Type code MS96-11EX0-R/115VAC
Ident no. 5231402
Ambient temperature -20…60 °C
Operating voltage 99…121 VAC
No-load current I0ð 75 mA
Output function Relay output, changover contact
Device designation É II(1) G D [EEx ia] IIC
Protection type II(1) G D [EEx ia] II C
Ex approval acc. to conformity certificate TÜV 96 ATEX 1098
Protection class IP20
Protection class (terminals/housing) IP20 / IP40
Design terminal chamber
Dimensions 110 x 50 x 75 mm
Housing material polycarbonate/ABS
Connection terminal chamber
Indication: Drop below setpoint LED red
Indication: Setpoint reached LED yellow
Indication: Setpoint exceeded 4 x LEDs green
■ATEX category II (1) G, Ex Zone 0
■ATEX category II (1) D, Ex Zone 20
■single-channel signal processor MS96
■for connection of an intrinsically safe
flow control sensor in zone 0
■adjustment via potentiometer
■6 LEDs for display of the flow state
■intrinsically safe control circuit, [EExia]
IIC
■switch-off delay adjustable in a range of
0…25 s
■wire-break monitoring
■99…121 VAC
■Changeover contact, relay output
Wiring diagram
Functional principle
Signal processors not only supply insertion
and inline sensors with voltage, they also pro-
cess and display the measured signals. De-
vices with MK96…, MS96… and MC96…
housing styles are available. The individual
housing styles are designed for different oper-
ating voltages and feature various output and
supplementary functions. For intrinsically safe
flow sensors it is required to use signal pro-
cessors with intrinsically safe control circuits
of the series MS96…Ex… and MC96…Ex… .
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]
Signal processor
MS96 for flow sensors
MS96-11EX0-R/115VAC
Operating manual
Intended use
This device fulfils the directive 94/9/EC and is suited for use in explosion hazardous areas according to EN50014 and EN50020.
In order to ensure correct operation to the intended purpose it is required to observe the national regulations and directives.
For use in explosion hazardous areas conform to classification
II 1 G and II 1 D (Group II, Category 1 G, electrical equipment for gaseous atmospheres and category 1 D, electrical equipment for dust atmo-
spheres).
Marking (see device or technical data sheet)
Ex II 1 G and Ex ia IIC T6 acc. to EN60079-11 and -26 and Ex II 1 D Ex iaD 20 T95°C acc. to EN60079-11 and EN61241-0 and -11
Local admissible ambient temperature
-20…+60 °C
Installation / Commissioning
These devices may only be installed, connected and operated by trained and qualified staff. Qualified staff must have knowledge of protection
classes, directives and regulations concerning electrical equipment designed for use in explosion hazardous areas.
Please verify that the classification and the marking on the device comply with the actual application conditions.
This device is accessory equipment which features intrinsically safe circuits as well as non-intrinsically safe circuits. It may only be installed out-
side the explosion hazardous area in dry, clean and well monitored areas. If a declaration of conformity or declaration of the manufacturer as a
category 3 device exists, the device may be installed in zone 2. Special conditions for safe operation must be observed. Intrinsically-safe elec-
trical equipment can be connected to the intrinsically-safe connections. All equipment must comply with the demands for operation in the exist-
ing zone of the explosion hazardous area. If the intrinsically safe circuits lead to the dust explosion hazardous zones 20 or 21, it is important to
ensure that the devices connected to this circuit fulfil the demands for category 1D or 2D and are certified accordingly. If the equipment is inter-
connected, it is necessary to perform the "Proof of intrinsic safety" (EN 60079-14). Equipment which has been used once to connect intrinsical-
ly safe circuits to non-intrinsically safe circuits is no longer suitable for subsequent use with intrinsically safe circuits. Relevant regulations ex-
ist for the establishment of intrinsically-safe circuits, mounting of external connection parts as well as the characteristics and laying of cables.
Cables and terminals with intrinsically-safe circuits must be marked. They should be separated from non-intrinsically safe circuits or must fea-
ture appropriate insulation (EN 60079-14). Observe the prescribed clearances to earthed components and connections of other devices to the
intrinsically-safe connections of this device. Unless expressed specifically in the device-specific operating instructions, the approval becomes
void if the device is opened, repaired or actions are performed on the device by someone other than approved experts or the manufacturer. Vis-
ible changes to the device housing, such as brown-black discolourations caused by heat, as well as holes or bulges also indicate a serious dan-
ger. Switch off the device immediately. With the associated electrical equipment the interconnected intrinsically-safe equipment must also be
checked. Inspection of a device with regard to the explosion protection can only be performed by an expert or the manufacturer. The operation
of the devices is only permitted in conjunction with the permitted data printed on the side of the housing. Before any commissioning or modifica-
tion of the device interconnections, ensure that the respective regulations, directives and conditions have been complied with and also ensure
that use is only for the intended purpose and the safety requirements have been fulfilled.
Installation and mounting instructions
Avoid static charging of cables and plastic devices. Please only clean the device with a damp cloth. Do not install the device in a dust flow and
avoid build-up of dust deposits on the device.
If the devices and the cable could be subject to mechanical damage, they must be protected accordingly. They must also be shielded against
strong electro-magnetic fields.
The pin configuration and the electrical specifications can be taken from the device marking or the technical data sheet.
In order to avoid contamination of the device, please remove possible blanking plugs of the cable glands or connectors only shortly before in-
serting the cable or opening the cable socket.
Special conditions for safe operation
The device must be protected against any kind of mechanical damage.
service / maintenance
Repairs are not possible. The approval expires if the device is repaired or modified by a person other than the manufacturer. The most important
data from the approval are listed.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]
Signal processor
MS96 for flow sensors
MS96-11EX0-R/24VDC
Type code MS96-11EX0-R/24VDC
Ident no. 5231407
Ambient temperature -20…60 °C
Operating voltage 21…28VDC
No-load current I0ð 125 mA
Output function Relay output, changover contact
Device designation É II(1) G D [EEx ia] IIC
Protection type II(1) G D [EEx ia] II C
Ex approval acc. to conformity certificate TÜV 96 ATEX 1098
Protection class IP20
Protection class (terminals/housing) IP20 / IP40
Design terminal chamber
Dimensions 110 x 50 x 75 mm
Housing material polycarbonate/ABS
Connection terminal chamber
Indication: Drop below setpoint LED red
Indication: Setpoint reached LED yellow
Indication: Setpoint exceeded 4 x LEDs green
■ATEX category II (1) G, Ex Zone 0
■ATEX category II (1) D, Ex Zone 20
■single-channel signal processor MS96
■for connection of an intrinsically safe
flow control sensor in zone 0
■adjustment via potentiometer
■6 LEDs for display of the flow state
■intrinsically safe control circuit, [EExia]
IIC
■switch-off delay adjustable in a range of
0…25 s
■wire-break monitoring
■21…28 VDC
■Changeover contact, relay output
Wiring diagram
Functional principle
Signal processors not only supply insertion
and inline sensors with voltage, they also pro-
cess and display the measured signals. De-
vices with MK96…, MS96… and MC96…
housing styles are available. The individual
housing styles are designed for different oper-
ating voltages and feature various output and
supplementary functions. For intrinsically safe
flow sensors it is required to use signal pro-
cessors with intrinsically safe control circuits
of the series MS96…Ex… and MC96…Ex… .
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]
Signal processor
MS96 for flow sensors
MS96-11EX0-R/24VDC
Operating manual
Intended use
This device fulfils the directive 94/9/EC and is suited for use in explosion hazardous areas according to EN50014 and EN50020.
In order to ensure correct operation to the intended purpose it is required to observe the national regulations and directives.
For use in explosion hazardous areas conform to classification
II 1 G and II 1 D (Group II, Category 1 G, electrical equipment for gaseous atmospheres and category 1 D, electrical equipment for dust atmo-
spheres).
Marking (see device or technical data sheet)
Ex II 1 G and Ex ia IIC T6 acc. to EN60079-11 and -26 and Ex II 1 D Ex iaD 20 T95°C acc. to EN60079-11 and EN61241-0 and -11
Local admissible ambient temperature
-20…+60 °C
Installation / Commissioning
These devices may only be installed, connected and operated by trained and qualified staff. Qualified staff must have knowledge of protection
classes, directives and regulations concerning electrical equipment designed for use in explosion hazardous areas.
Please verify that the classification and the marking on the device comply with the actual application conditions.
This device is accessory equipment which features intrinsically safe circuits as well as non-intrinsically safe circuits. It may only be installed out-
side the explosion hazardous area in dry, clean and well monitored areas. If a declaration of conformity or declaration of the manufacturer as a
category 3 device exists, the device may be installed in zone 2. Special conditions for safe operation must be observed. Intrinsically-safe elec-
trical equipment can be connected to the intrinsically-safe connections. All equipment must comply with the demands for operation in the exist-
ing zone of the explosion hazardous area. If the intrinsically safe circuits lead to the dust explosion hazardous zones 20 or 21, it is important to
ensure that the devices connected to this circuit fulfil the demands for category 1D or 2D and are certified accordingly. If the equipment is inter-
connected, it is necessary to perform the "Proof of intrinsic safety" (EN 60079-14). Equipment which has been used once to connect intrinsical-
ly safe circuits to non-intrinsically safe circuits is no longer suitable for subsequent use with intrinsically safe circuits. Relevant regulations ex-
ist for the establishment of intrinsically-safe circuits, mounting of external connection parts as well as the characteristics and laying of cables.
Cables and terminals with intrinsically-safe circuits must be marked. They should be separated from non-intrinsically safe circuits or must fea-
ture appropriate insulation (EN 60079-14). Observe the prescribed clearances to earthed components and connections of other devices to the
intrinsically-safe connections of this device. Unless expressed specifically in the device-specific operating instructions, the approval becomes
void if the device is opened, repaired or actions are performed on the device by someone other than approved experts or the manufacturer. Vis-
ible changes to the device housing, such as brown-black discolourations caused by heat, as well as holes or bulges also indicate a serious dan-
ger. Switch off the device immediately. With the associated electrical equipment the interconnected intrinsically-safe equipment must also be
checked. Inspection of a device with regard to the explosion protection can only be performed by an expert or the manufacturer. The operation
of the devices is only permitted in conjunction with the permitted data printed on the side of the housing. Before any commissioning or modifica-
tion of the device interconnections, ensure that the respective regulations, directives and conditions have been complied with and also ensure
that use is only for the intended purpose and the safety requirements have been fulfilled.
Installation and mounting instructions
Avoid static charging of cables and plastic devices. Please only clean the device with a damp cloth. Do not install the device in a dust flow and
avoid build-up of dust deposits on the device.
If the devices and the cable could be subject to mechanical damage, they must be protected accordingly. They must also be shielded against
strong electro-magnetic fields.
The pin configuration and the electrical specifications can be taken from the device marking or the technical data sheet.
In order to avoid contamination of the device, please remove possible blanking plugs of the cable glands or connectors only shortly before in-
serting the cable or opening the cable socket.
Special conditions for safe operation
The device must be protected against any kind of mechanical damage.
service / maintenance
Repairs are not possible. The approval expires if the device is repaired or modified by a person other than the manufacturer. The most important
data from the approval are listed.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

This manual suits for next models

2

Other turck Signal Processor manuals

turck MS96-11EX0-R/230VAC User manual

turck

turck MS96-11EX0-R/230VAC User manual

turck MS96-11EX0-R/24VDC User manual

turck

turck MS96-11EX0-R/24VDC User manual

turck MS96 User manual

turck

turck MS96 User manual

Popular Signal Processor manuals by other brands

BBE 462 user manual

BBE

BBE 462 user manual

Radial Engineering REAMP JCR STUDIO REAMPER user guide

Radial Engineering

Radial Engineering REAMP JCR STUDIO REAMPER user guide

FHB Audio MX-1616-C user manual

FHB Audio

FHB Audio MX-1616-C user manual

Crestron Avia DSP-1282 Configuration guide

Crestron

Crestron Avia DSP-1282 Configuration guide

Motorola Freescale Semiconductor DSP56000 manual 

Motorola

Motorola Freescale Semiconductor DSP56000 manual 

OPTO 22 SNAP-PAC-EB1 datasheet

OPTO 22

OPTO 22 SNAP-PAC-EB1 datasheet

Finders Super Fix manual

Finders

Finders Super Fix manual

Tait T805 Service manual

Tait

Tait T805 Service manual

Snell & Wilcox Prefix Cpp100 Operator's manual

Snell & Wilcox

Snell & Wilcox Prefix Cpp100 Operator's manual

LD LD X223 user manual

LD

LD LD X223 user manual

Motorola Freescale Semiconductor DSP56000 manual

Motorola

Motorola Freescale Semiconductor DSP56000 manual

Yamaha MMP1 Getting started

Yamaha

Yamaha MMP1 Getting started

Rohde & Schwarz SMB100A Release notes

Rohde & Schwarz

Rohde & Schwarz SMB100A Release notes

Analogue Solutions Dr. Strangelove user manual

Analogue Solutions

Analogue Solutions Dr. Strangelove user manual

Befaco Muxlicer user manual

Befaco

Befaco Muxlicer user manual

Motorola DSP56012 user manual

Motorola

Motorola DSP56012 user manual

Inter-m CSP-4.8 Operation manual

Inter-m

Inter-m CSP-4.8 Operation manual

Atlas IED ASP-MG24 owner's manual

Atlas IED

Atlas IED ASP-MG24 owner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.