
Installation, Operation and Maintenance Manual
VariCool®VAV
16
Subject to change without notice. 10.20-IM (0818)
1� Drill a hole large enough to insert the pneumatic tubing
into the ducting at a 90 degree right angle.
2� Place approximately 1/8” of the high pressure tube into
the duct at the 90 degree right angle. The end of the
pneumatic tubing must be cut at and make a right
angle for the tube to pick up the correct air pressure
reading.
3� Use a clamp to secure the tube to the ducting and
route it back to the high static pressure switch.
4� Place the other end of this tubing onto the high
pressure end of the switch.
5� Install a second tube onto the low pressure side of the
pressure switch and route it to a room neutral pressure
location.
6� Again, make certain the end of the tube is cut ush at
a 90 degree right angle. This tube must be located in
ambient air.
Remote Alarm Output (Option)
A dry contact closure on alarm option may be provided
upon request. During an alarm condition, the Remote Alarm
output can be used to energize a eld provided and installed
alarm indicator light or buzzer.
If the system has this option, wire the electrical hot or
common side of the device being energized into terminals
TB2- 9 and TB2-10. The control circuit voltage must be 24
VAC and less than 1 amp inductive.
Remote Water Pump (Option)
If the system has the Remote Water Pump ON/OFF control
option, the hot or common side of the water pump’s starter
must be wired to terminals TB2-7 and TB2-8. The control
circuit voltage must be less than 250 VAC and not exceed
10 amps inductive loading.
O/A Damper Control (Option)
If the system has the Optional Outdoor Air Damper control,
the control signal to drive the eld provided damper actuator
must be wired through the factory provided terminals TB2-11
and TB2-12. The control circuit voltage must be 24 VAC and
not exceed1 amp inductive loading.
Smoke Detector/Fire Stat (Option)
If Smoke Detector or Fire Stat shutdown option is required,
a voltage free dry normally closed contact opens on alarm
must be eld provided from the device and wired back to the
VariCool’s Control Panel. Terminate from the device contact
termination points to the factory provided terminals TB2-18
and TB2-19.
Remote On/Off Control (Option)
With the Remote On/Off Control option, the unit will start
when a voltage free dry contact closure is provided to
Terminals TB2-20 and TB2-21. This closure may be provided
by a eld provided building management system or switch.
SEQUENCE OF OPERATION
DANGER: Be aware that fast moving fan drives and high
horsepower blowers/motors can cause injuries. Before
applying power to the VariCool unit, make sure all service
access doors are closed and latched to prevent injuries from
doors from blowing open or fast moving drives. Connect
power to the unit at the main power supply. Next, apply
power at the eld installed service disconnect switch and/
or optional factory supplied single point power disconnect.
MARVEL PLUS CONTROLLER
The VariCool system is designed to operate using a double
microprocessor design control system called a Marvel Plus.
The Marvel Plus control system incorporates a Marvel Plus
Main Board Control and a Marvel Plus Wall Mount Control
and display.
The Marvel Plus Main Board microprocessor is a 16 bit
microprocessor programmable controller with onboard
ash memory (6 Megabytes) to ensure better performance.
An onboard real time clock card allows for setting up of
occupancy schedules and recording of alarm occurrence for
storing of alarm history. Each Marvel Plus has the ability to
record up to 36 alarms/faults under an alarm history page to
allow technicians to view alarm history and temperatures
when the alarm occurred. Marvel Plus Main Boards allow
for connection some of the more widely used Building
Management Systems without requiring a Gateway to
interface.
The Marvel Plus Wall Controller is a terminal unit used to
interface with the Marvel Plus Main Board Controller through
the onboard display and keypad. The software stored in the
ash memory of the Marvel Plus Main Board was designed
with menu driven pages allowing customers to easily
navigate through the menus and submenus for setup of their
systems.
Note: See Our Marvel manual for operating instructions�
http://www.unitedcoolair.com/user-les/le/controls/
Marjiom.pdf