Subject to change without notice. 20.3-TD (1018)
Chilled Water Coil Performance
VSCW8G* Valve Size: 1"
EWT GPM PD Ft H20 CFM 86 / 72 80 / 67 75 / 62.5 72 / 60
Total Sensible Total Sensible Total Sensible Total Sensible
48
22.5 15.35
3520 95,390 75,290 90,850 73,310 86,750 71,840 83,570 70,080
3200 93,890 73,100 89,420 71,180 85,390 69,750 82,260 68,040
2880 92,570 70,900 88,160 69,040 84,190 67,650 81,100 65,990
15 7
3520 85,620 67,580 81,550 65,810 77,870 64,490 75,020 62,910
3200 84,280 65,620 80,270 63,900 76,650 62,620 73,840 61,080
2880 83,100 63,650 79,140 61,980 75,570 60,740 72,800 59,240
7.5 1.84
3520 65,730 51,880 62,600 50,520 59,780 49,500 57,590 48,290
3200 64,700 50,370 61,620 49,050 58,840 48,060 56,690 46,890
2880 63,790 48,850 60,750 47,570 58,010 46,610 55,890 45,480
45
22.5 15.35
3520 105,970 83,650 100,930 81,460 96,380 79,820 92,860 77,870
3200 104,310 81,220 99,350 79,090 94,870 77,500 91,400 75,610
2880 102,840 78,780 97,950 76,710 93,540 75,170 90,120 73, 340
15 7
3520 95,130 75,090 90,610 73,130 86,530 71,660 83,360 69,900
3200 93,640 72,910 89,190 71,000 85,170 69,580 82,050 67,870
2880 92,320 70,720 87,940 68,810 83,970 67,490 80,900 65,830
7.5 1.84
3520 73,040 57,640 69,560 56,130 66,420 55,010 63,990 53,660
3200 71,890 55,970 68,470 54,500 65,380 53,410 62,990 52,100
2880 70,880 54,290 67,510 52,860 64,460 51,800 62,100 50,530
42
22.5 15.35
3520 116,570 92,020 111,020 89,610 106,020 87,810 102,130 85,660
3200 114,740 89,340 109,280 87,000 104,360 85,260 100,530 83,170
2880 113,130 86,650 107,750 84,390 102,890 82,700 99,120 80,670
15 7
3520 104,640 82,600 99,660 80,440 95,170 78,820 91,690 76,890
3200 103,000 80,200 98,100 78,100 93,680 76,530 90,250 74,660
2880 101,550 77,790 96,720 75,150 92,360 14,230 88,980 72,420
7.5 1.84
3520 80,330 63,400 76,510 61,740 73,070 60,510 70,380 59,020
3200 79,070 61,560 75,310 59,950 71,920 58,750 69,280 57,310
2880 77,960 59,710 74,250 58,150 70,910 56,980 68,310 55,590
Notes:
(1) Performance based on water as the chilled uid.
(2) Pressure drop is for the coil only and does not Include a valve�
(3) Unit shipped with coil stubbed through the cabinet and capped�
(4) Pressure drops over 10 Ft. H20 are considered excessive.
Contact the factory for a special coil selection to meet your specic parameters.