manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. United Electric Controls
  6. •
  7. Thermostat
  8. •
  9. United Electric Controls 55HT Series User manual

United Electric Controls 55HT Series User manual

GENERAL
55 HT Series Thermostats are designed to control heat
tracing and freeze protection circuits. Temperature varia-
tions are sensed by a liquid filled sensing bulb which
hydraulically transmits to a diaphragm which either actu-
ates or deactuates a snap-acting switch at a predeter-
mined set point.
MAXIMUM TEMPERATURE IS THE HIGHEST
TEMPERATURE TO WHICH A SENSING ELE-
MENT MAY BE OCCASION- ALLY SUBJECTED
WITHOUT ADVERSELY AFFECTING SET POINT CALI-
BRATION AND REPEATABILITY. MAXIMUM TEMPERA -
TURE LIMITS STATED IN LITERATURE MUST NEVER
BE EXCEEDED, EVEN BY SURGES IN THE SYSTEM.
OCCASIONAL OPERATION OF UNIT UP TO MAX. TEM-
PERATURE IS ACCEPTABLE (E.G. START-UP, TEST-
ING). CONTINUOUS OPERATION SHOULD BE
RESTRICTED TO THE DESIGNATED ADJUSTABLE
RANGE.
Tools Needed
Flathead screwdriver
MOUNTING
INSTALL UNIT WHERE SHOCK, VIBRATION
AND TEMPERATURE FLUCTUATIONS ARE MIN-
IMAL. ORIENT UNIT SO THAT MOISTURE IS
PREVENTED FROM ENTERING THE ENCLOSURE.
Do not mount unit in ambient temperatures exceeding
product specifications. 55 Series Thermostats can be
mounted in any position.
For remote sensing thermostats, mount the unit via the (2)
3/16” screw clearance holes on the enclosure (See
Dimensions on back page.) Locate the bulb and 6” of
Installation and
Maintenance Instructions
IM55HT
Please read all instructional literature carefully and thoroughly before starting. Refer to the final page for the listing of Recommended
Practices, Liabilities and Warranties.
55HT Series
Thermostats for Heat Tracing
and Freeze Protection Applications in
Ordinary
Locations
Type E55HT
Part I - InstallationPart I - Installation
capillary in the area that is exposed to the coldest tempera-
ture. Be sure to locate the bulb so that it will not be
exposed to temperatures beyond sensor exposure limits.
Avoid bending or coiling the capillary tube smaller than
1/2” radius. Exercise caution when making bends near the
capillary ends.
For ambient sensing thermostats, locate the unit in area
that is exposed to coldest temperature.
WIRING
DISCONNECT ALL SUPPLY CIRCUITS BEFORE
WIRING UNIT. ELECTRICAL RATINGS STATED
IN LITERATURE AND NAMEPLATES MUST NOT
BE EXCEEDED. OVERLOAD ON A SWITCH CAN
CAUSE FAILURE ON THE FIRST CYCLE. WIRE UNITS
ACCORDING TO NATIONAL AND LOCAL ELECTRICAL
CODES. RECOMMENDED WIRE SIZE IS 14 AWG.
Remove the four screws retaining the cover and cover gasket.
Connect conduit to the 1/2” NPT connection located on the
side of the enclosure. Wire directly to the switch terminals
according to local and national electrical codes. The three
switch terminals are clearly labeled “common”, “norm
open”, and “norm closed”.
Start-Up Process
Turn dial and knob to the desired temperature setting.
Thermostat is ready for operation.
UNITED ELECTRIC
CONTROLS
RECOMMENDED PRACTICES AND WARNINGS
United Electric Controls Company recommends careful consideration of the following
factors when specifying and installing UE pressure and temperature units. Before
installing a unit, the Installation and Maintenance instructions provided with unit must
be read and understood.
• To avoid damaging unit, proof pressure and max temperature limits stated in lit-
erature and on nameplates must never be exceeded, even by surges in the system.
Operation of the unit up to proof pressure or max temperature is acceptable on a lim-
ited basis (i.e.start-up, testing) but continuous operation must be restricted to the des-
ignated adjustable range. Excessive cycling at proof pressure or maximum tempera-
ture limits could reduce sensor life.
• A back-up unit is necessary for applications where damage to a primary unit
could endanger life, limb or property. A high or low limit switch is necessary for appli-
cations where dangerous runaway condition could result.
• The adjustable range must be selected so that incorrect, inadvertent or mali-
cious setting at any range point can not result in an unsafe system condition.
• Install unit where shock, vibration and ambient temperature fluctuations will not
damage unit or affect operation. Orient unit so that moisture does not enter the enclo -
sure via the electrical connection.
• Unit must not be altered or modified after shipment. Consult UE if modification is
necessary.
• Monitor operation to observe warning signs of possible damage
to unit, such as drift in set point. Check unit immediately.
• Preventative maintenance and periodic testing is necessary for critical applica -
tions where damage could endanger property or personnel.
• For all applications, a factory set unit should be tested before use.
• Electrical ratings stated in literature and on nameplate must not be exceeded.
Overload on a switch can cause damage, even on the first cycle. Wire unit according
to local and national electrical codes, using wire size recommended in installation
sheet.
• Use only factory authorized replacement parts and procedures.
• Do not mount unit in ambient temp. exceeding published limits.
• For remote mounted temperature units, capillary lengths beyond 10 feet can
increase chance of error, and may require re-calibration of set point and indication.
LIMITED WARRANTY
UE warrants that the product thereby purchased is, upon delivery, free from defects
in material and workmanship and that any such product which is found to be defec-
tive in such workmanship or material will be repaired or replaced by UE (F.O.B. UE);
provided, however, that this warranty applies only to equipment found to be so defec-
tive within a period of 12 months after installation by buyer but not to exceed 18
months after delivery by the seller. Except for the limited warranty of repair and
replacement stated above, UE disclaims all warranties whatsoever with
respect to the product, including all implied warranties of merchantability or fit-
ness for any particular purpose.
LIABILITY LIMITATION
The sole and exclusive remedy of buyer for any liability or seller
for any claim, including incurred in connection with (I) breach of any warranty whatso -
ever expressed or implied, (II) a breach of contract, (III) a negligent act or acts (or
negligent failure to act) committed by seller, or (IV) an act for which strict liability will
be imputed to seller, is limited to the limited warranty or repair and replacement stat-
ed herein. In no event shall the seller be liable for any special,
indirect, consequential or other damages of a like general nature, including,
without limitation, loss of profits or production, or loss or expenses of any
nature incurred by any third party.
180 Dexter Ave., P.O. Box 9143, Watertown, MA 02272-9143 USA 617 926-1000
Fax 617 926-2568
IKON5M8/97
UNITED ELECTRIC
CONTROLS
Dimensions

This manual suits for next models

1

Popular Thermostat manuals by other brands

Lux Products TX1500E Installation and operating instructions

Lux Products

Lux Products TX1500E Installation and operating instructions

Lauda PTT operating instructions

Lauda

Lauda PTT operating instructions

Pego NECTOR Operation and maintenance manual

Pego

Pego NECTOR Operation and maintenance manual

ritetemp 6005 install guide

ritetemp

ritetemp 6005 install guide

Desa GA3400T manual

Desa

Desa GA3400T manual

Etherma eTOUCH-PRO-WB Installation and usage instructions

Etherma

Etherma eTOUCH-PRO-WB Installation and usage instructions

Vimar Eikon 20440 Instruction handbook

Vimar

Vimar Eikon 20440 Instruction handbook

Theben RAMSES 850 top2 OT Installation and operating instructions

Theben

Theben RAMSES 850 top2 OT Installation and operating instructions

Braeburn 3220 Speci?cations

Braeburn

Braeburn 3220 Speci?cations

Technotherm TPF-Eco Control guide

Technotherm

Technotherm TPF-Eco Control guide

Johnson Controls GLAS installation instructions

Johnson Controls

Johnson Controls GLAS installation instructions

Hach LANGE LT20 Basic user manual

Hach

Hach LANGE LT20 Basic user manual

Tech Controllers EU-R-9s PLUS manual

Tech Controllers

Tech Controllers EU-R-9s PLUS manual

Honeywell Home Round TH8732WFH5004 Professional install guide

Honeywell Home

Honeywell Home Round TH8732WFH5004 Professional install guide

Siemens Free Energy Band TH 193 HC Technical instructions

Siemens

Siemens Free Energy Band TH 193 HC Technical instructions

S+S Regeltechnik THERMASREG FS Operating Instructions, Mounting & Installation

S+S Regeltechnik

S+S Regeltechnik THERMASREG FS Operating Instructions, Mounting & Installation

Siemens RDD100.1 DHW instruction manual

Siemens

Siemens RDD100.1 DHW instruction manual

Trane ZSASSMAL012 Installer's guide

Trane

Trane ZSASSMAL012 Installer's guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.