United Technologies Carrier 30RQM 160 Manual

INSTALLATION, OPERATION AND
MAINTENANCE INSTRUCTIONS
Original document
Reversible air-to-water heat pump
30RQM 160-520 A
30RQP 160-520 A
Unit with low-noise option
Nominal heating capacity 170 - 540 kW
Nominal cooling capacity 160 - 510 kW

1 - INTRODUCTION............................................................................................................................................................................4
1.1 - Specic features of 30RQP units ..............................................................................................................................................4
1.2 - Installation safety considerations ..............................................................................................................................................4
1.3 - Pressure equipment and components.......................................................................................................................................5
1.4 - Repair safety considerations.....................................................................................................................................................6
2 - PRELIMINARY CHECKS...............................................................................................................................................................8
2.1 - Check equipment received........................................................................................................................................................8
2.2 - Handing and positioning ...........................................................................................................................................................8
2.3 - Checks before system start-up..................................................................................................................................................9
2.4 - Actual start-up ...........................................................................................................................................................................9
3 - DIMENSIONS AND CLEARANCES............................................................................................................................................10
3.1 - 30RQM/30RQP 160-230 .........................................................................................................................................................10
3.2 - 30RQM/30RQP 240-330 .........................................................................................................................................................12
3.3 - 30RQM/30RQP 380-520 .........................................................................................................................................................14
3.4 - Installation of multiple heat pumps..........................................................................................................................................15
3.5 - Distance to the wall .................................................................................................................................................................15
4 - PHYSICAL AND ELECTRICAL DATA FOR 30RQM AND 30RQP UNITS ................................................................................16
4.1 - Physical data 30RQM 160-520 ..............................................................................................................................................16
4.2 - Physical data 30RQP 160-520 ................................................................................................................................................17
4.3 - Electrical data 30RQM 160-520 .............................................................................................................................................18
4.4 - Electrical data 30RQP 160-520...............................................................................................................................................18
4.5 - Short circuit stability current ....................................................................................................................................................19
4.6 - Electrical data notes for the hydraulic module.........................................................................................................................19
4.7 - Compressor usage and electrical data....................................................................................................................................21
5 - ELECTRICAL CONNECTION .....................................................................................................................................................22
5.1 - Power supply...........................................................................................................................................................................22
5.2 - Voltage phase imbalance (%) .................................................................................................................................................22
5.3 - Power connection/disconnect switch.......................................................................................................................................22
5.4 - Recommended wire sections ..................................................................................................................................................23
5.5 - Power cable access routing ....................................................................................................................................................24
5.6 - Field control wiring ..................................................................................................................................................................24
5.7 - Electric power reserve for the user..........................................................................................................................................24
6 - APPLICATION DATA...................................................................................................................................................................25
6.1 - Operating range .....................................................................................................................................................................25
6.2 - Minimum water ow (units without hydraulic module)............................................................................................................. 25
6.3 - Maximum water ow (units without hydraulic module)............................................................................................................ 26
6.4 - Variable ow water heat exchanger (units without hydraulic module).....................................................................................26
6.5 - System minimum water volume ..............................................................................................................................................26
6.6 - Maximum system water volume..............................................................................................................................................26
6.7 - Exchanger water ow..............................................................................................................................................................26
6.8 - Pressure drop curves for the exchanger and standard water inlet/outlet piping .....................................................................27
7 - WATER CONNECTIONS .............................................................................................................................................................28
7.1 - Operating precautions and recommendations ........................................................................................................................28
7.2 - Hydraulic connections .............................................................................................................................................................29
7.3 - Water ow detection................................................................................................................................................................31
7.4 - Frost protection .......................................................................................................................................................................31
7.5 - Protection against cavitation (with option 116) ........................................................................................................................ 32
7.6 - Operation of two units in Master/Slave mode (option 58) .......................................................................................................32
7.7 - Auxiliary electric heaters..........................................................................................................................................................33
8 - NOMINAL SYSTEM WATER FLOW CONTROL.........................................................................................................................34
8.1 - Units without hydraulic module ...............................................................................................................................................34
8.2 - Units with hydraulic module and xed speed pump ................................................................................................................34
8.3 - Units with hydraulic module and variable speed pump – Pressure differential control ...........................................................35
8.4 - Units with hydraulic module and variable speed pump – Temperature differential control...................................................... 35
8.5 - Units with hydraulic module and variable speed pump – Setting a xed ow for the system .................................................36
8.6 - Pump pressure/ow rate curves..............................................................................................................................................37
8.7 - Available static system pressure ............................................................................................................................................. 39
CONTENTS
2

This manual applies to the following units:
-30RQM: Standard reversible heat pump.
-30RQP: Reversible heat pump with variable speed fan.
For controls operation, please refer to the 30RQM/30RQP control manual.
9 - MAIN COMPONENTS OF THE UNIT AND OPERATING CHARACTERISTICS........................................................................41
9.1 - Compressors...........................................................................................................................................................................41
9.2 - Lubricant..................................................................................................................................................................................41
9.3 - Air coils....................................................................................................................................................................................41
9.4 - Fans ........................................................................................................................................................................................41
9.5 - Electronic expansion valve (EXV) ...........................................................................................................................................42
9.6 - Moisture indicator....................................................................................................................................................................42
9.7 - Refrigerant accumulator with built-in lter drier....................................................................................................................... 42
9.8 - Water heat exchanger ............................................................................................................................................................42
9.9 - Refrigerant...............................................................................................................................................................................42
9.10 - High-pressure safety pressostat............................................................................................................................................42
9.11 - Variable frequency drive ........................................................................................................................................................42
9.12 - Power factor correction capacitors (option 231)....................................................................................................................42
9.13 - Low temperature and brine solution option (Option 6B)........................................................................................................43
9.14 - Fan arrangement...................................................................................................................................................................44
9.15 - Fan stages (30RQM units only).............................................................................................................................................44
9.16 - Variable speed ventilation (30RQP units only) ......................................................................................................................44
9.17 - Smart View control ................................................................................................................................................................44
10 - OPTIONS ..................................................................................................................................................................................45
10.1 - Hydraulic module without variable speed (options 116R, 116S, 116T, 116U) .......................................................................45
10.2 - Hydraulic module with variable speed (options 116V, 116W)................................................................................................45
10.3 - Units with fans with operating pressure for indoor installation (Option 12 - Fan with high static pressure) .......................... 45
10.4 - Installation .............................................................................................................................................................................45
10.5 - Nominal and maximum air ows per circuit (A and B) for 30RQP sizes................................................................................ 46
10.6 - Factory-installed duct connection interface on each fan .......................................................................................................46
10.7 - Partial heat reclaim using desuperheaters (option 49)..........................................................................................................48
10.8 - Other options.........................................................................................................................................................................54
11 - STANDARD MAINTENANCE ....................................................................................................................................................56
11.1 - Level 1 maintenance ............................................................................................................................................................56
11.2 - Level 2 maintenance ............................................................................................................................................................56
11.3 - Level 3 (or higher) maintenance............................................................................................................................................57
11.4 - Tightening torques for the main electrical connections..........................................................................................................57
11.5 - Tightening torques for the main bolts and screws .................................................................................................................57
11.6 - Air coil .................................................................................................................................................................................... 57
11.7 - Water heat exchanger maintenance......................................................................................................................................57
11.8 - Variable frequency drive maintenance ..................................................................................................................................58
11.9 - Characteristics of R-410A......................................................................................................................................................58
11.10 - Check of power factor correction capacitors ....................................................................................................................... 58
12 - FINAL SHUTDOWN...................................................................................................................................................................59
12.1 - Shutting down........................................................................................................................................................................59
12.2 - Recommendations for disassembly ......................................................................................................................................59
12.3 - Fluids to be recovered for treatment .....................................................................................................................................59
12.4 - Materials to be recovered for recycling .................................................................................................................................59
12.5 - Waste Electrical and Electronic Equipment (WEEE).............................................................................................................59
13 - UNIT START-UP CHECKLIST FOR INSTALLERS PRIOR TO CONTACTING CARRIER SERVICE...................................... 60
CONTENTS
The illustrations in this document are for illustrative purposes only and not part of any offer for sale or contract. The manufacturer reserves the right to change the design
at any time without notice.
3

1 - INTRODUCTION
Prior to the initial start-up of the 30RQM/30RQP units, everyone
involved in the works should be thoroughly familiar with these
instructions and with the characteristics of the installation site, and
ensure these are respected.
30RQM/30RQP heat pumps are designed to provide a very high
level of safety and reliability, making installation, start-up, operation
and maintenance easier and safer.
They will provide safe and reliable service if used within their
application ranges.
They are designed to offer a service life of 15 years, assuming a
utilisation factor of 75%, which corresponds to approximately
100,000 operating hours.
The procedures in this manual are arranged in the sequence
required for installation, start-up, operation and maintenance of
the units. Ensure that you follow all the required safety precautions,
including those listed in this guide, such as: wearing personal
protective equipment (gloves, safety glasses, safety shoes), having
the appropriate tools, skills and qualications (electrical, air
conditioning, local legislation).
To find out whether these products comply with European
directives (machine safety, low voltage, electromagnetic
compatibility, pressure equipment, etc.) check the declarations of
conformity for these products.
1.1 - Specic features of 30RQP units
The 30RQP units differ from the 30RQM units by introducing
variable speed drives on all of the fans and optimising the overall
energy efciency of the unit depending on the operating conditions
(air temperature, circuit capacity). This improves the seasonal
efciency (SCOP and ESEER).
All fans in the same refrigerant circuit are controlled by a single
variable speed drive. Therefore, they operate together at the same
rotational speed. The rotational speed of each circuit is controlled
by an algorithm that continuously optimises the condensing
temperature in cooling mode or the evaporating temperature in
heating mode. This ensures optimal energy efciency of the units
(EER and COP) whatever the operating conditions.
1.2 - Installation safety considerations
After the unit has been received, and before it is started up, it must
be visually inspected for damage. Check that the refrigerant circuits
are intact, taking care to check that no components or pipes have
shifted or been damaged (following an impact, for example). If in
doubt, carry out a leak tightness check. If damage is detected
upon receipt, le a claim with the shipping company immediately.
Do not remove the skid or the packaging until the unit is in
its nal position.
These units can be safely moved with a fork lift truck, as long
as the forks are positioned in the location and direction shown
on the unit.
The units can also be lifted with slings, using only the
designated lifting points marked on the unit (labels on the
chassis and label with the unit handling instructions, attached
to the unit).
Use slings with the correct capacity, and follow the lifting
instructions given on the certied drawings for the unit.
Safety can only be guaranteed if these instructions are
carefully followed. Failure to do so may result in damage to
the equipment and physical injury.
DO NOT OBSTRUCT THE PROTECTIVE DEVICES.
This applies to any valves tted on the refrigerant or heat
transfer uid circuits. Check whether the original protection
plugs are still present at the valve outlets. These plugs are
generally made of plastic and must be removed before
operation. If they are still present, please remove them. Fit
devices at the valve or drain piping outlets to prevent the
penetration of foreign bodies (dust, building debris, etc.) and
atmospheric agents (water can form rust or ice). These
devices, as well as the drain piping, must not impair operation
and must not lead to a pressure drop that is higher than 10%
of the control pressure.
Classication and control:
In accordance with the Pressure Equipment Directive and
national usage monitoring regulations in the European Union,
the protective devices tted to these machines are classied
as follows:
Safety
accessory(1)
Accessory for limitation of
damage in the event of an
external re(2)
Refrigerant Side
High pressure switch X
External relief valve(3) X
Rupture disk X
Fuse plug X
Heat transfer uid side
External relief valve (4) (4)
(1) Classied for protection in normal service situations.
(2) Classied for protection in abnormal service situations. These accessories are
sized for res with a thermal ow of 10kW/m2. No combustible matter should
be placed within 6.5 m of the unit.
(3) The instantaneous over-pressure limitation of 10% of the operating pressure
does not apply to this abnormal service situation.
The control pressure can be higher than the service pressure. In this case, either
the design temperature or the high-pressure switch ensures that the service
pressure is not exceeded in normal service situations.
(4) The selection of these relief valves must be made by the personnel responsible
for completing the hydraulic installation.
Do not remove these valves under any circumstances, even
if the re risk is under control for a particular system. There
is no guarantee that the accessories have been re-installed
if the system is changed or for transport with a gas charge.
When the unit is subjected to re, a safety device prevents
rupture due to over-pressure by releasing the refrigerant. The
uid can then break down into toxic residues when in contact
with ames:
• Stay away from the unit;
• Ensure the personnel in charge of extinguishing the
re are duly warned and issued with recommendations;
• Fire extinguishers appropriate to the system and the
refrigerant type must be easily accessible.
All factory-installed relief valves are lead-sealed to prevent
any calibration change.
The external relief valves must always be piped to a safe,
external location if the units are installed in a enclosed space.
Refer to the installation regulations, for example those of
European standard EN 378 and EN 13136. Discharge ductwork
must be installed in a way that ensures that people and
property are not exposed to vented refrigerant. As the uids
can be diffused in the air, ensure that refrigerant is discharged
away from building air intakes or that it is discharged into a
sufcient quantity of suitable absorbent material. Relief
valves must be checked periodically (See the paragraph on
“Maintenance safety considerations”).
If the relief valves are installed on a change-over valve, this
is equipped with a relief valve on each of the two outlets.
Only one of the two relief valves is in operation, the other one
is isolated. Never leave the change-over valve in the
intermediate position, i.e. with both ways open (Bring the
actuator in abutment, front or back according to the outlet to
isolate). If a relief valve is removed for checking or
replacement please ensure that there is always an active relief
valve on each of the change-over valves installed in the unit.
Provide a drain in the discharge duct, close to each valve, to
avoid an accumulation of condensate or rain water. All
precautions concerning handling of refrigerant must be
observed in accordance with local regulations.
4

1.3 - Pressure equipment and components
These products incorporate equipment or components under
pressure, manufactured by Carrier or other manufacturers. We
recommend that you contact your professional body to nd out
which regulations affect you as the operator or owner of pressure
equipment or components (declaration, re-qualication, re-testing,
etc.). The characteristics of this equipment/these components are
given on the name plate or in the regulatory documentation
supplied with the products.
These units comply with the European Pressure Equipment
Directive.
The units are intended to be stored and operated in an
environment where the ambient temperature is always within
the allowable temperature range indicated on the nameplate.
Do not introduce signicant static or dynamic pressure with
regard to the operating pressures used during operation, or
for tests in the refrigerant circuit or heat exchange circuits.
NOTE: Monitoring during operation, re-qualification, re-
testing and re-testing dispensation:
• Follow regulations on the monitoring of pressure
equipment.
• The user or the operator is usually required to create
and maintain a monitoring and maintenance register.
• In the absence of any regulations, or in addition to the
regulations, follow the guidance in EN 378.
• Follow the local professional recommendations,
whenever they exist.
• Regularly inspect the surface of the components for
signs of corrosion. To do this, check an uninsulated
part of the component or check for an accumulation of
rust at the insulation joints.
• Regularly check for the presence of any impurities (e.g.
sand, grit) in the heat transfer uids. These impurities
can cause wear and/or pitting corrosion.
• Install lters in the heat transfer uid piping.
• The reports from the regular checks carried out by the
user or operator must be included in the monitoring
and maintenance register.
Repair:
Any repair or modication of a pressurised container is
prohibited.
Only the replacement of the container with an original
manufacturer component is authorised. In this case, the
replacement must be carried out by a qualied operator.
The replacement of the vessel must be entered in the
monitoring and maintenance register.
Recycling:
The pressure equipment can be recycled in whole or in part.
After use, they may contain refrigerant vapours and oil
residue. Some parts are painted.
1.4 - Maintenance safety considerations
Carrier recommends the following table as a guide to completing
the monitoring and maintenance register (logbook) required by
EN 378-2:
Intervention Name of the
commissioning
engineer
Applicable
national
regulations
Verication
Organism
Date Nature (1)
(1) Maintenance, repairs, regular verications (EN 378), leakage, etc.
Engineers working on the electrical or refrigeration components
must be authorised, trained and fully qualied to do so. All work
on the refrigerant circuit must be carried out by a trained person,
fully qualied to work on these units. He/she must have been
specically trained on this equipment and system. All welding
operations must be carried out by qualied specialists.
30RQM/30RQP units use high pressure R-410A refrigerant (the
unit operating pressure is above 40 bar; the pressure at an air
temperature of 35°C is 50% higher than for R-22). Special
equipment must be used when working on the refrigerant circuit
(pressure measurement, charge transfer, etc.).
Do not clean the unit with hot water or steam. This may cause
the refrigerant pressure to rise.
Any manipulation (opening or closing) of a shut-off valve
must be carried out by a qualied and authorised engineer,
observing applicable standards (e.g. during draining
operations). The unit must be switched off during maintenance.
NOTE: The unit must never be left shut down with the liquid
line valve closed, as liquid refrigerant can be trapped between
this valve and the expansion device and lead to the risk of a
pressure increase. This valve is situated on the liquid line
before the lter drier.
Equip the engineers that work on the unit as follows:
Personal protection
equipment (PPE) (1)
Operations
Handling Maintenance,
service
Welding or
brazing (2)
Protective gloves,
eye protection,
safety shoe,
protective clothing.
X X X
Ear protection. X X
Filtering respirator. X
(1) We recommend to follow the instructions in EN 378-3.
(2) Performed in the presence of A1 refrigerant according to EN 378-1.
Never work on a unit that is still energized.
Never work on any of the electrical components until the
general power supply to the unit has been isolated.
Lock the power supply circuit upstream of the unit in the open
position during maintenance interventions.
If work is interrupted for any reason, check that all circuits
are powered off before resuming work.
CAUTION: Even if the unit has been shut down, the power
circuit remains energized, unless the unit or circuit disconnect
switch is open. Refer to the wiring diagram for further details.
Follow the appropriate safety guidelines. When working on
the fan deck, particularly if the discharge grilles have been
removed, isolate the power supply to the fans to prevent their
operation.
CAUTION: The option Power factor (231) and the variable
frequency drives (VFD) tted to the 30RQP units and the units
with options 116V, 116W or 28 have capacitor banks whose
discharge time is ve (5) minutes after disconnecting the
power supply.
After disconnecting the power supply to the electrical box,
wait for 5 minutes before accessing the electrical box or
variable drives.
Before any intervention, verify that there is no voltage present
on any accessible conducting parts of the power circuit.
It is recommended that an indicating device be installed to
check if any refrigerant has leaked from the relief valve.
The presence of oil at the outlet orice is a useful indicator
that refrigerant has leaked. Keep this orice clean to ensure
that any leaks are obvious. The calibration of a valve that has
leaked is generally lower than its original calibration. The new
calibration may affect the operating range. To avoid nuisance
tripping or leaks, replace or re-calibrate the valve.
CAUTION: If refrigerant circuit service valves are installed,
ensure the protective caps are fitted in order to avoid
leakages.
1 - INTRODUCTION
5

OPERATING CHECKS:
• IMPORTANT INFORMATION REGARDING THE
REFRIGERANT USED:
This product contains uorinated greenhouse gas
covered by the Kyoto protocol.
Refrigerant type: R-410A
Global Warming Potential (GWP): 2088
WARNING:
1. Any intervention on the refrigerant circuit of this product
should be performed in accordance with the applicable
legislation. In the EU, the regulation is called F-Gas,
N°517/2014.
2. Ensure that the refrigerant is never released to the
atmosphere during installation, maintenance or equipment
disposal.
3. The deliberate gas release into the atmosphere is not
allowed.
4. If a refrigerant leak is detected, ensure that it is stopped
and repaired as quickly as possible.
5. Only a qualied and certied personnel can perform
installation operations, maintenance, refrigerant circuit
leak test as well as the equipment disposal and the
refrigerant recovering.
6. The gas recovery for recycling, regeneration or destruction
is at customer charge.
7. Periodic leak tests have to be carried out by the customer
or by third parties. The EU regulation set the periodicity
here after:
System WITHOUT
leakage detection
No
Check
12
Months 6 Months 3 Months
System WITH leakage
detection
No
Check
24
Months 12 Months 6 Months
Refrigerant charge/
circuit (CO2 equivalent)
< 5 Tons
5 ≤
Charge
< 50 Tons
50 ≤
Charge
< 500 Tons
Charge
> 500
Tons(1)
Refrigerant charge/
Circuit (kg)
R134A
(GWP 1430)
Charge
< 3.5 kg
3.5 ≤
Charge
< 34.9 kg
34.9 ≤
Charge
< 349.7 kg
Charge
> 349.7 kg
R407C
(GWP 1774)
Charge
< 2.8 kg
2.8 ≤
Charge
< 28.2 kg
28.2 ≤
Charge
< 281.9 kg
Charge
> 281.9 kg
R410A
(GWP 2088)
Charge <
2.4 kg
2.4 ≤
Charge
< 23.9 kg
23.9 ≤
Charge
< 239.5 kg
Charge
> 239.5 kg
HFO’s: R1234ze No requirement
(1) From 01/01/2017, units must be equipped with a leakage detection system.
8. A logbook must be established for equipments subject to
periodic leak tests. It should contain the quantity and the
type of uid present within the installation (added and
recovered), the quantity of recycled uid, regenerated or
destroyed, the date and output of the leak test, the
designation of the operator and its belonging company,
etc.
9. Contact your local dealer or installer if you have any
questions.
PROTECTIVE DEVICE CHECKS:
• If no national regulations exist, check the protective
devices on site in accordance with standard EN378:
once a year for the high pressure switches, every ve
years for external relief valves.
The company or organisation that conducts a pressure switch test
must establish and implement detailed procedures for:
-Safety measures,
-Measuring equipment,
-Values and tolerances for cut-off and discharge devices,
-Test stages,
-Recommissioning of the equipment.
Please contact Carrier Service for this type of test. The test
principle set out here by Carrier does not involve removal of the
pressure switch:
-Verify and record the nominal values for activation of the
pressure switches and external relief devices (pressure relief
valves or rupture discs),
-Be ready to switch off the main disconnect switch of the power
supply if the pressure switch does not trigger (avoid over-
pressure or excess gas if there are valves on the high
pressure side on the recovery air exchangers, for example),
-Connect a pressure gauge protected against pulsations (lled
with oil with maximum pointer if mechanical), preferably
calibrated (the values displayed on the user interface may
be inaccurate in an instant reading because of the scanning
delay applied in the control)
-Complete an HP Test as provided by the software (refer to
the Control IOM for details).
Caution: If the test results in the replacement of the pressure
switch, it is necessary to recover the refrigerant charge; these
pressure switches are not installed on Schrader type
automatic valves.
Visually inspect the protective devices (relief valves, pressure
switches) at least once a year.
If the machine operates in a corrosive atmosphere, inspect
the devices more frequently.
Check regularly for leaks and, if detected, have these repaired
immediately.
Regularly check that the vibration levels remain acceptable
and close to those at the initial machine start-up.
Before opening a refrigerant circuit, drain and consult the
pressure indicators.
After an equipment failure, replace the refrigerant in
accordance with a procedure such as that described in NF
E29-795, or have a refrigerant analysis carried out at a
specialist laboratory.
If the refrigerant circuit remains open after an intervention
(such as a component replacement, etc.):
• Seal the openings if the duration is less than a day;
• If more than one day, charge the circuit with a dry, inert
gas (e.g. nitrogen)
The objective is to prevent penetration of atmospheric
humidity and the resulting corrosion of the unprotected
internal steel walls.
1.4 - Repair safety considerations
All parts of the system must be maintained by the personnel
responsible for such maintenance, in order to avoid any damage
or accidents. Faults and leaks must be repaired immediately. An
authorised technician must remedy the fault immediately. After
each repair of the unit, check the operation of all protective devices
and record operating readings for all parameters.
Comply with the regulations and recommendations given in the
safety standards for refrigerant systems and machines, such as:
EN 378, ISO 5149, etc.
If a leak occurs or if the refrigerant becomes contaminated (e.g.
by a short circuit in a motor or freezing of the BPHE), remove the
complete charge using a recovery unit and store the refrigerant
in mobile containers. The compressors cannot transfer the whole
refrigerant charge and can be damaged if used to pump-down.
The refrigerant charge should not be transferred to the high-
pressure side.
Detect and repair the leak, and recharge the circuit with the full
charge of R410A indicated on the unit's nameplate. Do not top up
the refrigerant charge. Only charge liquid refrigerant R-410A at
the liquid line.
Check the type of refrigerant before adding the full charge to
the machine.
1 - INTRODUCTION
6

Charging any refrigerant other than the original type (R410A)
will impair machine operation and can even cause irreparable
damage to the compressors. The compressors operating with
this refrigerant type are lubricated with a synthetic polyolester
oil.
Before any intervention on the refrigerant circuit, the complete
refrigerant charge must be recovered.
RISK OF EXPLOSION:
Never use air or a gas containing oxygen during leak tests to
purge ductwork or to pressurise a unit. Pressurised air
mixtures or gases containing oxygen can be the cause of an
explosion. Oxygen reacts violently with oil and grease.
Only use dry nitrogen for leak tests, with an appropriate tracer
gas if necessary.
If the recommendations above are not observed, this can
have serious or even fatal consequences and damage the
installations.
Never exceed the specied maximum operating pressures.
Check the maximum permissible test pressures on the high
and low pressure sides, consulting the instructions in this
manual and the pressures indicated on the unit's nameplate.
Do not unweld the refrigerant ductwork or any refrigerant
circuit component or cut these with a torch until all refrigerant
(liquid and vapour) as well as the oil have been removed from
the heat pump. Traces of vapour should be displaced with
dry nitrogen. Refrigerant in contact with an open flame
produces toxic gases.
The necessary protective equipment must be available, and
appropriate fire extinguishers for the system and the
refrigerant type used must be within easy reach.
Do not siphon refrigerant.
Avoid spilling liquid refrigerant on skin or splashing it into
the eyes. Use safety goggles and safety gloves. Wash any
uid spills from the skin with soap and water.
If refrigerant enters the eyes, immediately ush the eyes
thoroughly with water and consult a doctor.
Any accidental release of refrigerant, whether this is caused
by a small leak or signicant discharges following the rupture
of a pipe or an unexpected release from a relief valve, can
cause frostbites and burns to personnel exposed. Do not
ignore such injuries. Installers, owners and especially service
engineers for these units must:
-Create a procedure to ensure medical attention is sought
before treating such injuries;
-Provide rst-aid equipment, including equipment for
treating eye injuries.
We recommend that standard EN 378-3 Annex 3 is applied.
Never apply an open ame or live steam to a refrigerant
container. This can result in dangerous overpressure.
During refrigerant removal and storage operations, follow
applicable regulations. These regulations, permitting
conditioning and recovery of halogenated hydrocarbons
under optimum quality conditions for the products and
optimum safety conditions for people, property and the
environment are described in standard NF E29-795. Any
refrigerant transfer and recovery operations must be carried
out using a suitable transfer unit. 3/8” SAE connectors on the
liquid, suction and discharge lines are available on all units
for connection to the transfer unit. The units must never be
modied to add refrigerant and oil charging, removal and
purging devices. All these devices are factory tted on the
units. Please refer to the certied dimensional drawings for
the units.
It is dangerous and illegal to re-use disposable (non-
returnable) cylinders or attempt to rell them. When cylinders
are empty, evacuate the remaining gas pressure, and move
them to a designated place for recovery. Do not incinerate.
Do not attempt to remove components tted to the refrigerant
circuit or ttings while the machine is under pressure or while
it is running. Check that there is zero pressure in the circuit
and that the unit has been shut down and deenergized before
removing components or opening a circuit. When the
refrigerant circuit is opened to carry out a repair, see the
blanketing recommendations in the paragraph on
“Maintenance safety considerations”.
Do not attempt to repair or recondition a valve if there has
been any corrosion or build-up of foreign material (rust, dirt,
scale, etc.) on the valve body or mechanism. If necessary,
replace the device.
Do not install relief valves in series or backwards.
CAUTION: No part of the unit must be used as a walkway,
rack or support. Periodically check and repair or, if necessary,
replace any component or piping that shows signs of damage.
The ducts can break under the pressure and release
refrigerant, causing injuries.
Do not climb on a machine. Use a platform to work at height.
Use mechanical lifting equipment (crane, hoist, winch, etc.)
to lift or move heavy components.
For lighter components, use lifting equipment if there is any
risk of slipping or losing your balance.
Use only original replacement parts for any repair or
component replacement. Consult the list of replacement parts
that corresponds to the original equipment's specications.
Do not drain the heat transfer uid circuit without informing
the installation site technical maintenance department or
other competent body rst.
Close the shut-off valves on the water inlet and outlet and
drain the unit's hydraulic circuit before working on the
components installed on the circuit (screen lter, pump, water
ow sensor, etc.).
Periodically inspect all valves, ttings and pipes on the
refrigerant and hydraulic circuits to ensure that they do not
show any signs of corrosion or leaks.
It is recommended that ear defenders are worn when working
near the unit if it is running.
1 - INTRODUCTION
7

2 - PRELIMINARY CHECKS
2.1 - Check equipment received
■ Check that the unit has not been damaged during transport
and that no parts are missing. If the unit has been damaged or
the shipment is incomplete, send a claim to the shipping
company.
■ Check the unit's nameplate to ensure it matches the model
ordered. The nameplate is attached in two places to the unit:
-On the outside of one of the unit frames,
-On the inside of the electrical panel door.
■ The unit nameplate must include the following information:
-Model number - size
-CE marking
-Serial number
-Year of manufacture and pressure and leak tightness test
date
-Fluid used for transport
-Refrigerant used
-Refrigerant charge per circuit
-OP: Min./max. allowable pressure (high and low pressure
side)
-OT: Min./max. allowable temperature
-(high and low pressure side)
-Pressure switch cut-out pressure
-Unit leak test pressure
-Voltage, frequency, number of phases
-Maximum current
-Maximum input power
-Unit net weight
■ Conrm that all accessories ordered for eld installation have
been delivered in perfect working order.
The unit must be checked periodically, if necessary removing
the insulation (thermal, acoustic), throughout its service life
to ensure that nothing has damaged the unit (handling
equipment, tools, etc.). If necessary, damaged parts must be
repaired or replaced. See also the section on “Maintenance”.
2.2 - Handing and positioning
2.2.1 - Handling
See the section on “Installation safety considerations”.
In some cases, uprights are added for transporting and handling
the unit. The uprights must be removed if necessary for access
or connection.
Important: follow the disassembly procedure indicated in the
disassembly instructions.
• Undo the bolt (3).
• Remove the upright (2).
• Remove the plate (1).
Keep the uprights following start-up and ret them when moving
the unit.
2.2.2 - Positioning within the installation area
The machine must be installed in a place that is not accessible to
the public or protected against access by non-authorised persons.
If the unit is to be raised, ensure the machine's surroundings
permit easy access for maintenance operations.
Always refer to the "Dimensions and clearances" section to
conrm that there is adequate space for all connections and
maintenance operations. For the centre of gravity coordinates,
the position of the unit mounting holes, and the weight
distribution points, refer to the certied dimensional drawing
supplied with the unit.
The typical applications of these units are heating and
cooling, which do not require earthquake resistance.
Earthquake resistance has not been veried.
CAUTION: Only attach slings at the designated lifting points
which are marked on the unit.
8

Before positioning the unit, check that:
-The chosen location can support the weight of the unit, or
that appropriate reinforcement measures have been taken.
-The unit is installed level on an even surface (maximum
tolerance is 5 mm along both axes).
-If the support structure is sensitive to vibration and/or noise
transmission it is advisable to insert anti-vibration mounts
(elastomeric mounts or metal springs) between the unit and
the structure. Selection of these devices is based on the
system characteristics and the comfort level required and
should be made by a qualied design engineer.
-There is adequate space above and around the unit for air
to circulate and for access to the components (see
dimensional drawings).
-The number of support points is adequate and that they are
in the right places.
-The location is not subject to ooding.
-For outdoor applications, avoid installing the unit in a location
where snow is likely to accumulate (in areas subject to long
periods of sub-zero temperatures, the unit should be raised).
-Bafes may be necessary to protect the unit from strong
prevailing winds. These must not restrict air ow into the unit.
CAUTION: Before lifting the unit, check that all casing panels
and grilles are securely xed in place. Lift and set down the
unit with great care. Tilting and jarring can damage the unit.
If 30RQM/30RQP units are hoisted with slings, it is advisable to
protect coils from accidental impacts. Use sleeves or a lifting beam
to spread the slings above the unit. Do not tilt a unit by more than
15°.
CAUTION: Never apply pressure or leverage to any of the
unit's panels or uprights; only the base of the unit frame is
designed to withstand such stresses. No force or effort must
be applied to pressurised parts, especially via pipes
connected to the water heat exchanger. If a unit includes a
hydraulic module (options 116R, S, T, U, V, W), the hydraulic
module and pump piping must be installed in a way that does
not submit it to any strain. The hydraulic module pipes must
be tted so that the pump does not support the weight of the
pipes.
2.3 - Checks before system start-up
Before the start-up of the heat pump, the complete system,
including the heat pump, must be veried against the installation
drawings, dimensional drawings, system piping and instrumentation
diagrams and the wiring diagrams. Heat transfer uid temperatures
above the maximum recommended can lead to an increase in the
refrigerant pressure and can cause a loss of refrigerant due to the
relief valve discharge.
National regulations must be followed during these checks. If the
national regulation does not specify any details, refer to standard
EN 378 as follows:
External visual checks of the installation:
-Ensure that the machine is charged with refrigerant. Verify
on the unit nameplate that the ‘uid transported’ is that
recommended for operation, and is not nitrogen.
-Compare the complete system with the refrigeration system
and power circuit diagrams.
-Check that all components comply with the design
specications.
-Check that all protection equipment and documents provided
by the manufacturer (dimensional drawings, Pipe and
instrument diagram (PID), declarations, etc.) to comply with
the regulations are present.
-Verify that the environmental protection and safety devices
and arrangements provided by the manufacturer to comply
with the regulations are in place and compliant.
-Verify that all documents for pressure containers, certicates,
name plates, register, instruction manuals and documentation
provided by the manufacturer to comply with the regulations
are present.
-Verify that access and safety routes are unobstructed.
-Verify the instructions and guidelines to prevent the deliberate
discharge of refrigerant.
-Verify the installation of connections.
-Verify the supports and xing elements (materials, routing
and connection).
-Verify the quality of welds and other joints.
-Check the protection against mechanical damage.
-Check the protection against heat.
-Check the protection of moving parts.
-Verify the accessibility for maintenance or repair and to check
the piping.
-Verify the status of the valves.
-Verify the quality of the thermal insulation.
-Check the condition of 400 V cable insulation.
2.4 - Actual start-up
Always ensure you have read and fully understood the operating
instructions for the units before starting up the heat pump, and
ensure the following precautions have been taken:
-Check the water circulation pumps, the air handling
equipment and any other device connected to the water heat
exchanger.
-Refer to the manufacturer's instructions.
-Refer to the wiring diagram supplied with the heat pump.
-Ensure that there is no refrigerant leak.
-Check the tightening of xing clamps on all pipes.
-Check the power supply at the main connection point and
the order of phases.
-Check that the compressor crankcase heaters, and the
compressor head heaters if applicable, have been energized
for 6 hours before starting up the system.
-Open the suction shut-off valves on each circuit.
IMPORTANT: Commissioning and start-up must be supervised
by a qualied engineer.
-Start-up and operating tests must be carried out with a
thermal load applied and water circulating in the water
heat exchanger.
-All setpoint adjustments and control tests must be
carried out before the unit is started up.
-Refer to the Service guide.
Start up the heat pump.
Ensure that all safety devices are operational, checking
specically that the high pressure switches are activated and
that any alarms have been cleared.
NOTE: If Carrier's recommendations (power and water
connections and installation) are not observed, then no claims
can be made under the warranty.
2 - PRELIMINARY CHECKS
9

3 - DIMENSIONS AND CLEARANCES
3.1 - 30RQM/30RQP 160-230
WITHOUT HYDRAULIC MODULE
Power connection
30RQP only
Sizes 210-230
WITH HYDRAULIC MODULE
210-230 ONLY
30RQP ONLY
Legend
All dimensions are given in mm.
NOTE:
Non-contractual drawings.
When designing a system, refer to the certied dimensional
drawings provided with the unit or available on request.
Please refer to the certied dimensional drawings for the
positioning of the xing points, weight distribution points
and centre of gravity coordinates.
B
Clearances required for maintenance and air ow
C
Clearance recommended for coil removal
Water inlet
Water outlet
Air outlet, do not obstruct
Control box
10

WITH WATER BUFFER TANK MODULE
Main hydraulic connection
Electrical power connection
Legend
All dimensions are given in mm.
NOTE:
Non-contractual drawings.
When designing a system, refer to the certied dimensional
drawings provided with the unit or available on request.
Please refer to the certied dimensional drawings for the
positioning of the xing points, weight distribution points
and centre of gravity coordinates.
B
Clearances required for maintenance and air ow
C
Clearance recommended for coil removal
Water inlet
Water outlet
Air outlet, do not obstruct
Control box
3 - DIMENSIONS AND CLEARANCES
11

3.2 - 30RQM/30RQP 240-330
WITHOUT HYDRAULIC MODULE
Power connection
Sizes 270-310-330
30RQP only
Size 330
WITH HYDRAULIC MODULE
Legend
All dimensions are given in mm.
NOTE:
Non-contractual drawings.
When designing a system, refer to the certied dimensional
drawings provided with the unit or available on request.
Please refer to the certied dimensional drawings for the
positioning of the xing points, weight distribution points
and centre of gravity coordinates.
B
Clearances required for maintenance and air ow
C
Clearance recommended for coil removal
Water inlet
Water outlet
Air outlet, do not obstruct
Control box
3 - DIMENSIONS AND CLEARANCES
12

WITH WATER BUFFER TANK MODULE
Main hydraulic connection Electrical power connection
Legend
All dimensions are given in mm.
NOTE:
Non-contractual drawings.
When designing a system, refer to the certied dimensional
drawings provided with the unit or available on request.
Please refer to the certied dimensional drawings for the
positioning of the xing points, weight distribution points
and centre of gravity coordinates.
B
Clearances required for maintenance and air ow
C
Clearance recommended for coil removal
Water inlet
Water outlet
Air outlet, do not obstruct
Control box
3 - DIMENSIONS AND CLEARANCES
13

3.3 - 30RQM/30RQP 380-520
WITHOUT HYDRAULIC MODULE
Power connection
Sizes 430-470-520
30RQP only
WITH HYDRAULIC MODULE
Legend
All dimensions are given in mm.
NOTE:
Non-contractual drawings.
When designing a system, refer to the certied dimensional
drawings provided with the unit or available on request.
Please refer to the certied dimensional drawings for the
positioning of the xing points, weight distribution points
and centre of gravity coordinates.
B
Clearances required for maintenance and air ow
C
Clearance recommended for coil removal
Water inlet
Water outlet
Air outlet, do not obstruct
Control box
3 - DIMENSIONS AND CLEARANCES
14

WITH WATER BUFFER TANK MODULE
Main hydraulic connection
Electrical power connection
Legend
All dimensions are given in mm.
NOTE:
Non-contractual drawings.
When designing a system, refer to the certied dimensional
drawings provided with the unit or available on request.
Please refer to the certied dimensional drawings for the
positioning of the xing points, weight distribution points
and centre of gravity coordinates.
B
Clearances required for maintenance and air ow
C
Clearance recommended for coil removal
Water inlet
Water outlet
Air outlet, do not obstruct
Control box
3.4 - Installation of multiple heat pumps
It is recommended to install multiple heat pumps in a single row,
arranged as shown in the example below, to avoid recycling of air
from one unit to another.
If the oor space does not allow this arrangement, contact your
Carrier distributor to assess the various installation options.
3.5 - Distance to the wall
To guarantee correct operation in most cases:
If h < H, S minimum = 3 m
If h > H or S < 3 m, contact your Carrier distributor to assess the
various installation options.
Anti-vibration
mounts
3 - DIMENSIONS AND CLEARANCES
15

4 - PHYSICAL AND ELECTRICAL DATA FOR 30RQM AND 30RQP UNITS
4.1 - Physical data 30RQM 160-520
30RQM 160 180 210 230 240 270 310 330 380 430 470 520
Sound levels
Standard unit
Sound power(1) dB(A) 90 91 91 91 92 92 93 93 94 94 94 94
Sound pressure at 10 m(2) dB(A) 58 59 59 59 60 60 61 61 62 62 62 62
Standard unit + option 15(3)
Sound power(1) dB(A) 89 90 90 90 91 91 91 92 92 93 93 93
Sound pressure at 10 m(2) dB(A) 57 58 58 58 59 59 59 60 60 61 61 61
Dimensions
Length mm 2410 3604 4797
Width mm 2253 2253 2253
Height mm 2322 2322 2322
Unit length with water buffer tank module opt mm 3604 4798 5991
Operating weight(4)
Standard unit kg 1415 1490 1618 1641 2049 2197 2318 2548 3013 3274 3286 3327
Standard unit + option 15 kg 1497 1572 1726 1749 2157 2323 2444 2693 3175 3454 3466 3507
Standard unit + option 15 + option 116W(3) kg 1637 1712 1878 1900 2318 2531 2662 2897 3380 3700 3748 3788
Unit + option 15 + option 116W + Water buffer tank module
kg 2585 2656 2821 2844 3257 3471 3598 3833 4312 4643 4692 4732
Compressors Hermetic Scroll 48,3 r/s
Circuit A 112222223444
Circuit B 222223344444
No. of control stages 3 3 4445567888
Refrigerant(4) R-410A
Circuit A charge kg 14,5 22,0 23,0 24,0 27,0 27,0 30,0 33,0 42,0 53,0 54,0 56,0
tCO2e30,3 45,9 48,0 50,1 56,4 56,4 62,6 68,9 87,7 110,7 112,8 116,9
Circuit B charge kg 23,0 23,0 23,0 24,0 35,0 36,0 48,5 53,0 53,0 53,0 54,0 56,0
tCO2e 48,0 48,0 48,0 50,1 73,1 75,2 101,3 110,7 110,7 110,7 112,8 116,9
Control Smart View Control
Minimum capacity %33% 33% 25% 25% 25% 20% 20% 17% 14% 13% 13% 13%
Air heat exchanger Grooved copper tubes and aluminum ns
Fans Axial Flying Bird 4 with rotating shroud
Quantity 3 44455667888
Maximum total air ow l/s 13542 18056 18056 18056 22569 22569 27083 27083 31597 36111 36111 36111
Maximum rotation speed rps 16 16 16 16 16 16 16 16 16 16 16 16
Water heat exchanger Dual-circuit plate heat exchanger
Water volume l 15 15 15 19 27 27 35 44 44 44 47 53
Max. water-side operating pressure without hydraulic
module kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Hydraulic module (option) Pump, Victaulic screen lter, relief valve, water and air drain valve, pressure
sensors, expansion tank (option)
Pump Centrifugal pump, monocell, 48,3 rps, low- or high-pressure (as required), single
or dual (as required)
Expansion vessel volume l 50 50 50 50 80 80 80 80 80 80 80 80
Max. water-side operating pressure with hydraulic
module kPa 400 400 400 400 400 400 400 400 400 400 400 400
Water connections with or without hydraulic module Victaulic type
Connections inch 33334444444 4
External diameter mm 88,9 88,9 88,9 88,9 114,3 114,3 114,3 114,3 114,3 114,3 114,3 114,3
Chassis paintwork Colour code: RAL 7035
(1) en dB ref=10-12 W, pondération (A). Valeur d’émission sonore déclarée dissociée conformément à l'ISO 4871 (avec une incertitude de +/-3dB(A)). Mesurée selon ISO
9614-1 aux conditions de fonctionnement nominales EN14511 - mode froid.
(2) en dB ref 20µPa, pondération (A). Valeur d’émission sonore déclarée dissociée conformément à l'ISO 4871 (avec une incertitude de +/-3dB(A)). Pour information,
calculée à partir de la puissance acoustique Lw(A).
(3) Options: 15 = bas niveau sonore, 116W = Module hydraulique pompe double haute pression vitesse variable
(4) Valeurs données à titre indicatif. Se référer à la plaque signalétique de l'unité.
Eurovent certied values
16

4.2 - Physical data 30RQP 160-520
30RQP
160 180 210 230 240 270 310 330 380 430 470 520
Sound levels
Standard unit
Sound power(1) dB(A) 90 91 91 91 92 92 93 93 94 94 94 94
Sound pressure at 10 m(2) dB(A) 58 59 59 59 60 60 61 61 62 62 62 62
Standard unit + option 15(3)
Sound power(1) dB(A) 89 90 90 90 91 91 91 92 92 93 93 93
Sound pressure at 10 m(2) dB(A) 57 58 58 58 59 59 59 60 60 61 61 61
Standard unit + option 15LS(3)
Sound power(1) dB(A) 84 85 86 86 86 87 87 87 88 89 89 89
Sound pressure at 10 m(2) dB(A) 52 53 54 54 54 55 55 55 56 57 57 57
Dimensions
Length mm 2410 3604 4797
Width mm 2253 2253 2253
Height mm 2322 2322 2322
Unit length with water buffer tank module opt mm 3604 4798 5991
Operating weight(4)
Standard unit kg 1450 1526 1654 1677 2085 2233 2355 2585 3050 3331 3343 3393
Standard unit + option 15 /15LS kg 1533 1609 1762 1785 2193 2359 2481 2729 3212 3512 3524 3573
Standard unit + option 15/15LS + option 116W(3) kg 1673 1749 1914 1936 2354 2568 2699 2934 3416 3757 3806 3854
Unit + option 15 + option 116W + Water buffer tank module
kg 2632 2708 2873 2895 3313 3527 3658 3893 4375 4716 4765 4813
Compressors Hermetic Scroll 48,3 r/s
Circuit A 112222223444
Circuit B 222223344444
No. of control stages 3 3 4445567888
Refrigerant(4) R-410A
Circuit A charge kg 14,5 22,0 23,0 24,0 27,0 27,0 30,0 33,0 42,0 53,0 54,0 56,0
tCO2e30,3 45,9 48,0 50,1 56,4 56,4 62,6 68,9 87,7 110,7 112,8 116,9
Circuit B charge kg 23,0 23,0 23,0 24,0 35,0 36,0 48,5 53,0 53,0 53,0 54,0 56,0
tCO2e 48,0 48,0 48,0 50,1 73,1 75,2 101,3 110,7 110,7 110,7 112,8 116,9
Control Smart View Control
Minimum capacity %33% 33% 25% 25% 25% 20% 20% 17% 14% 13% 13% 13%
Air heat exchanger Grooved copper tubes and aluminium ns
Fans Axial Flying Bird 4 with rotating shroud
Quantity 3 44455667888
Maximum total air ow l/s 13542 18056 18056 18056 22569 22569 27083 27083 31597 36111 36111 36111
Maximum rotation speed rps 16 16 16 16 16 16 16 16 16 16 16 16
Water heat exchanger Dual-circuit plate heat exchanger
Water volume l 15 15 15 19 27 27 35 44 44 44 47 53
Max. water-side operating pressure without hydraulic
module kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Hydraulic module (option) Pump, Victaulic screen lter, relief valve, water and air drain valve, pressure
sensors, expansion tank (option)
Pump Centrifugal pump, monocell, 48,3 rps, low- or high-pressure (as required), single
or dual (as required)
Expansion vessel volume l 50 50 50 50 80 80 80 80 80 80 80 80
Max. water-side operating pressure with hydraulic
module kPa 400 400 400 400 400 400 400 400 400 400 400 400
Water connections with or without hydraulic module Victaulic type
Connections inch 333344444444
External diameter mm 88,9 88,9 88,9 88,9 114,3 114,3 114,3 114,3 114,3 114,3 114,3 114,3
Chassis paintwork Colour code: RAL 7035
(1) en dB ref=10-12 W, pondération (A). Valeur d’émission sonore déclarée dissociée conformément à l'ISO 4871 (avec une incertitude de +/-3dB(A)). Mesurée selon ISO
9614-1 aux conditions de fonctionnement nominales EN14511 - mode froid.
(2) en dB ref 20µPa, pondération (A). Valeur d’émission sonore déclarée dissociée conformément à l'ISO 4871 (avec une incertitude de +/-3dB(A)). Pour information,
calculée à partir de la puissance acoustique Lw(A).
(3) Options: 15 = bas niveau sonore, 15LS = très bas niveau sonore, 116W = Module hydraulique pompe double haute pression vitesse variable
(4) Valeurs données à titre indicatif. Se référer à la plaque signalétique de l'unité.
Eurovent certied values
4 - PHYSICAL AND ELECTRICAL DATA FOR 30RQM AND 30RQP UNITS
17

4.3 - Electrical data 30RQM 160-520
30RQM 160 180 210 230 240 270 310 330 380 430 470 520
Power circuit
Nominal voltage V-ph-Hz 400 - 3 - 50
Voltage range V 360 - 440
Control circuit supply 24 V via internal transformer
Nominal unit current draw (1)
Circuit A&B A 100 110 133 147 151 166 191 199 233 266 294 322
Maximum unit input power (2)
Circuit A&B kW 80 88 107 118 120 134 152 161 188 215 236 258
Cosine Phi unit at maximum power (2) 0,88 0,87 0,88 0,88 0,87 0,88 0,87 0,88 0,88 0,88 0,88 0,88
Maximum unit current draw (Un-10%) (3)
Circuit A&B A 144 158 192 211 215 241 273 289 337 385 422 460
Maximum unit current draw (Un) (4)
Circuit A&B - Standard Unit A133 146 177 195 199 222 252 266 310 354 390 425
Circuit A&B - Unit with option 231 A 100 110 133 148 151 166 192 200 233 266 296 326
Maximum start-up current, standard unit (Un) (5)
Circuit A&B A307 356 352 406 409 396 462 440 485 529 600 636
Max. start-up current, unit with soft starter (Un) (5)
Circuit A&B A 261 283 305 332 336 350 389 394 438 482 527 562
(1) Conditions equivalent to the standardised Eurovent conditions (evaporator water input-output temperature = 12 °C/7 °C, outside air temperature = 35 °C).
(2) Power input, compressors and fans, at the unit operating limits (saturated suction temperature 15 °C, saturated condensing temperature 68.3 °C) and nominal voltage
of 400 V (data given on the unit nameplate).
(3) Maximum unit operating current at maximum unit power input and at 360 V.
(4) Maximum unit operating current at maximum unit power input and at 400 V (values given on the unit nameplate).
(5) Maximum instantaneous starting current at operating limits (maximum operating current of the smallest compressor(s) + current of the fan(s) + locked rotor current of
the largest compressor).
Fan motor electrical data reported upstream of the variable drive at Eurovent equivalent conditions and motor ambient air temperature of 50 °C at 400 V: Current 3.8
A; Start-up current 20 A; Power input: 1.75 kW.
4.4 - Electrical data 30RQP 160-520
30RQP 160 180 210 230 240 270 310 330 380 430 470 520
Power circuit
Nominal voltage V-ph-Hz 400 - 3 - 50
Voltage range V 360 - 440
Control circuit supply 24 V via internal transformer
Nominal unit current draw (1)
Circuit A&B A 97 107 130 144 147 162 186 195 227 260 288 316
Cosine Phi unit at maximum power (2)
Circuit A&B kW 81 88 108 118 120 134 153 161 188 215 237 259
Cosinus Phi unité à puissance maximale (2) 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88
Maximum unit current draw (Un-10%) (3)
Circuit A&B A 142 154 189 208 211 237 268 284 331 378 416 454
Maximum unit current draw (Un) (4)
Circuit A&B - Standard Unit A131 142 174 192 195 218 247 261 305 348 383 419
Circuit A&B - Unit with option 231 A 98 108 131 146 148 164 188 197 230 262 291 321
Maximum start-up current, standard unit (Un) (5)
Circuit A&B A305 353 349 402 405 392 458 436 479 523 594 629
Max. start-up current, unit with soft starter (Un) (5)
Circuit A&B A 259 279 302 329 332 346 384 389 433 476 520 556
(1) Conditions equivalent to the standardised Eurovent conditions (evaporator water input-output temperature = 12 °C/7 °C, outside air temperature = 35 °C).
(2) Power input, compressors and fans, at the unit operating limits (saturated suction temperature 15 °C, saturated condensing temperature 68.3 °C) and nominal voltage
of 400 V (data given on the unit nameplate).
(3) Maximum unit operating current at maximum unit power input and at 360 V.
(4) Maximum unit operating current at maximum unit power input and at 400 V (values given on the unit nameplate).
(5) Maximum instantaneous starting current at operating limits (maximum operating current of the smallest compressor(s) + current of the fan(s) + locked rotor current of
the largest compressor).
Fan motor electrical data reported upstream of the variable drive at Eurovent equivalent conditions and motor ambient air temperature of 50 °C at 400 V: Current 3.8
A; Start-up current 20 A; Power input: 1.75 kW.
4 - PHYSICAL AND ELECTRICAL DATA FOR 30RQM AND 30RQP UNITS
18

4.5 - Short circuit stability current
Short circuit stability current (TN system(1))
30RQM/30RQP 160 180 210 230 240 270 310 330 380 430 470 520
Rated Short-Time Withstand Current (Icw), (1s) rms value/peak lpk
Circuits A & B kA/kA 8/30 8/30 8/30 8/30 8/30 8/30 15/65 15/65 15/65 15/65 20/80 20/80
With fuses upstream - maximum fuse values assigned (gL/gG)
Circuits A & B A 200 200 200 250 250 250 315 315 400 400 630 630
With fuses upstream - Conditional Short-Circuit Current (Icc)/Icf
Circuits A & B kA 50 50 50 50 50 50 50 50 50 50 50 50
(1) Type of system earthing
IT system: The short circuit current stability values given above for the TN system are not valid for IT, modications are
required.
4.6 - Electrical data notes for the hydraulic module
The pumps that are factory-installed in these units have motors with efciency class IE3. The additional electrical data
required(1) is as follows:
For the low pressure single pump motors for 30RQM/30RQP 160-520 units (option 116T)
No.(2) Description(3) Units 30RQM/30RQP
160 180 210 230 240 270 310 330 380 430 470 520
1Nominal efciency at full load and nominal voltage % 86,4 86,4 86,4 86,4 87,5 87,5 87,5 89,6 89,6 89,6 89,7 89,7
Nominal efciency at 75% full load and nominal voltage % 86,9 86,9 86,9 86,9 88,2 88,2 88,2 90,4 90,4 90,4 90,0 90,0
Nominal efciency at 50% full load and nominal voltage % 85,7 85,7 85,7 85,7 87,5 87,5 87,5 89,9 89,9 89,9 89,0 89,0
2Efciency level -IE3
3 Year of manufacture -This information varies depending on the manufacturer and model
at the time of incorporation. Please refer to the motor nameplates.
4Manufacturer’s name or trademark, commercial registration
number and registered address - Same as above
5Product’s model number - Same as above
6Number of motor poles - 2222222222 2 2
7-1 Nominal shaft power output at full load and nominal voltage
(400 V) kW 2,2 2,2 2,2 2,2 3334 4 4 5,5 5,5
7-2 Maximum input power (400 V)(5) kW 2,80 2,80 2,80 2,80 3,81 3,81 3,81 4,96 4,96 4,96 6,80 6,80
8Nominal input frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
9-1 Nominal voltage V 3 x 400
9-2 Maximum current drawn (400 V)(6) A 4,92 4,92 4,92 4,92 6,81 6,81 6,81 8,27 8,27 8,27 11,30 11,30
10 Nominal speed r/s - r/min 48 - 2900
11 Product disassembly, recycling or disposal at end of life -Disassembly using standard tools. Disposal and recycling using an
appropriate company.
12
Operating conditions for which the motor is specically designed
I - Altitudes above sea level m < 1000(4)
II - Ambient air temperature °C < 40
III - Maximum operating temperature °C Please refer to the operating conditions given in this manual or in
the specic conditions in the Carrier selection programs.
IV - Potentially explosive atmospheres -Non ATEX environment
(1) Additional electrical data required by regulation No. 640/2009 concerning the application of directive 2005/32/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
(5) To obtain the maximum input power for a unit with hydraulic module, add the maximum unit input power from the electrical data table to the pump power input.
(6) To obtain the maximum unit operating current draw for a unit with hydraulic module add the maximum unit current draw from the electrical data table to the pump current
draw.
4 - PHYSICAL AND ELECTRICAL DATA FOR 30RQM AND 30RQP UNITS
19

For the low pressure dual-pump motors for 30RQM/30RQP 160-520 units (option 116U)
No.(2) Description(3) Units 30RQM/30RQP
160 180 210 230 240 270 310 330 380 430 470 520
1
Nominal efciency at full load and nominal voltage % 85,9 86,4 87,5 87,5 87,5 87,5 87,5 89,6 89,6 89,6 89,7 89,7
Nominal efciency at 75% full load and nominal voltage % 86,4 86,9 88,2 88,2 88,2 88,2 88,2 90,4 90,4 90,4 90,0 90,0
Nominal efciency at 50% full load and nominal voltage % 84,9 85,7 87,5 87,5 87,5 87,5 87,5 89,9 89,9 89,9 89,0 89,0
2Efciency level -IE3
3 Year of manufacture -This information varies depending on the manufacturer and model
at the time of incorporation. Please refer to the motor nameplates.
4Manufacturer’s name or trademark, commercial registration
number and registered address - Same as above
5Product’s model number - Same as above
6Number of motor poles - 2222222222 2 2
7-1 Nominal shaft power output at full load and nominal voltage
(400 V) kW 1,5 2,2 333334 4 4 5,5 5,5
7-2 Maximum input power (400 V)(5) kW 1,94 2,80 3,81 3,81 3,81 3,81 3,81 4,96 4,96 4,96 6,80 6,80
8Nominal input frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
9-1 Nominal voltage V 3 x 400
9-2 Maximum current drawn (400 V)(6) A3,41 4,92 6,81 6,81 6,81 6,81 6,81 8,27 8,27 8,27 11,30 11,30
10 Nominal speed r/s - r/min 48 - 2900
11 Product disassembly, recycling or disposal at end of life -Disassembly using standard tools. Disposal and recycling using an
appropriate company.
12
Operating conditions for which the motor is specically designed
I - Altitudes above sea level m < 1000(4)
II - Ambient air temperature °C < 40
III - Maximum operating temperature °C Please refer to the operating conditions given in this manual or in
the specic conditions in the Carrier selection programs.
IV - Potentially explosive atmospheres -Non ATEX environment
(1) Additional electrical data required by regulation No. 640/2009 concerning the application of directive 2005/32/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
(5) To obtain the maximum input power for a unit with hydraulic module, add the maximum unit input power from the electrical data table to the pump power input.
(6) To obtain the maximum unit operating current draw for a unit with hydraulic module add the maximum unit current draw from the electrical data table to the pump current
draw.
For the high pressure single and dual-pump motors for 30RQM/30RQP 160-520 units (options 116R and 116V)
No.(2) Description(3) Units 30RQM/30RQP
160 180 210 230 240 270 310 330 380 430 470 520
1
Nominal efciency at full load and nominal voltage % 87,5 87,5 89,6 89,6 89,6 89,7 89,7 89,7 89,7 90,8 90,8 90,8
Nominal efciency at 75% full load and nominal voltage % 88,2 88,2 90,4 90,4 90,4 90,0 90,0 90,0 90,0 90,8 90,8 90,8
Nominal efciency at 50% full load and nominal voltage % 87,5 87,5 89,9 89,9 89,9 89,0 89,0 89,0 89,0 89,6 89,6 89,6
2Efciency level -IE3
3 Year of manufacture -This information varies depending on the manufacturer and model at the
time of incorporation. Please refer to the motor nameplates.
4Manufacturer’s name or trademark, commercial
registration number and registered address - Same as above
5Product’s model number - Same as above
6Number of motor poles - 2 2 2 2 2 2 2 2 2 2 2 2
7-1 Nominal shaft power output at full load and nominal
voltage (400 V) kW 334 4 4 5,5 5,5 5,5 5,5 7,5 7,5 7,5
7-2 Maximum input power (400 V)(5) kW 3,81 3,81 4,96 4,96 4,96 6,80 6,80 6,80 6,80 9,16 9,16 9,16
8Nominal input frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
9-1 Nominal voltage V 3 x 400
9-2 Maximum current drawn (400 V)(6) A 6,81 6,81 8,27 8,27 8,27 11,30 11,30 11,30 11,30 15,30 15,30 15,30
10 Nominal speed r/s - r/min 48 - 2900
11 Product disassembly, recycling or disposal at end of life -Disassembly using standard tools. Disposal and recycling using an
appropriate company.
12
Operating conditions for which the motor is specically designed
I - Altitudes above sea level m < 1000(4)
II - Ambient air temperature °C < 40
III - Maximum operating temperature °C Please refer to the operating conditions given in this manual or in the
specic conditions in the Carrier selection programs.
IV - Potentially explosive atmospheres -Non ATEX environment
(1) Additional electrical data required by regulation No. 640/2009 concerning the application of directive 2005/32/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
(5) To obtain the maximum input power for a unit with hydraulic module, add the maximum unit input power from the electrical data table to the pump power input.
(6) To obtain the maximum unit operating current draw for a unit with hydraulic module add the maximum unit current draw from the electrical data table to the pump current
draw.
4 - PHYSICAL AND ELECTRICAL DATA FOR 30RQM AND 30RQP UNITS
20
This manual suits for next models
23
Table of contents
Other United Technologies Heat Pump manuals
Popular Heat Pump manuals by other brands

Sanyo
Sanyo SAP120FCH Service manual

Daikin
Daikin Altherma 3 R F installation manual

York
York AFFINITY YZB brochure

Carrier
Carrier PHR524000K 0B1 Series installation instructions

Heat Controller
Heat Controller VMH 09 installation manual

Atlantic
Atlantic alfea S14 excellia 3-phase Installation and operating manual

American Standard
American Standard 4A7A3 Installation and operation manual

Panasonic
Panasonic Aquarea WH-SXC09H3E5 quick guide

Daikin
Daikin VRV reference guide

Panasonic
Panasonic Aquarea WH-ADC0309J3E5B quick guide

Panasonic
Panasonic WH-MDC06E3E5 Service manual

Sime
Sime SHP M PRO 010 Installation and owner's manual