Veeder-Root FUELQUEST Insite360 Connect User guide

Manual No: 577014-326 ●Revision: B
Insite360 Connect
Installation And Setup Manual

Notice
Veeder-Root makes no warranty of any kind with regard to this publication, including but not limited
to, the implied warranties of merchantability and fitness for a particular purpose.
Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages
in connection with the furnishing, performance, or use of this publication.
The information contained in this publication may be subject to change without notice.
This publication contains proprietary information which is protected by copyright. All rights reserved.
No part of this publication may be photocopied, reproduced, or translated to another language
without the prior written consent of Veeder-Root.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operation.
©Veeder-Root 2017. All rights reserved.
Slide off Default Plug
The Insite360 Connect power
source may be shipped with
an international plug in place.
Select the proper plug type
from those shipped with the
power source. If necessary,
slide off the default plug type.
Slide on the correct plug type
until it snaps into place.
Slide on U.S. Plug
NOTICE

iii
Introduction 1
Safety Precautions ........................................................................................................................................................ 1
Related Manuals ............................................................................................................................................................ 1
Insite360 Connect Description .................................................................................................................................. 2
Installation 3
Mounting The Insite360 Connect ............................................................................................................................. 3
Insite360 Connect Installation Option - Scenario 1 ............................................................................................. 4
Insite360 Connect Installation Option - Scenario 2 ............................................................................................. 7
Insite360 Connect Installation Option - Scenario 3 ............................................................................................. 9
Insite360 Connect Configuration ............................................................................................................................12
Troubleshooting 13
LED Status Lights .......................................................................................................................................................13
ATG Serial Port Setup ...............................................................................................................................................14
ATG EDIM Comm Port Setup ..................................................................................................................................16
Changing The Insite360 Connect Configuration ................................................................................................18
Replacing The Insite360 Connect ..........................................................................................................................19
Figures
Figure 1. Insite360 Connect Ports And LEDs............................................................................................................ 3
Figure 2. Scenario 1 Insite360 Connect Hookup - TLS-350 With DB9 Serial Port Connection.................. 6
Figure 3. Scenario 1 Insite360 Connect Hookup - TLS-300/350 With DB25 Serial Port Connection ...... 7
Figure 4. Scenario 2 Insite360 Connect Hookup - TLS-350 With EDIM Connection To POS..................... 9
Figure 5. Scenario 3 Insite360 Connect Hookup - TLS-3XX With DB25 Serial Comm Port And POS..... 11
Figure 6. Scenario 3 Insite360 Connect Hookup - TLS-350 With DB9 Serial Comm Port And POS........ 12
Figure 7. Locating Insite360 Connect GVR/FMS Site ID Number....................................................................... 13
Tables
Table 1. Kits Required For Insite360 Connect Installation .................................................................................... 2
Table 2. Insite360 Connect LED Status Lights ........................................................................................................ 14
Table 3. EDIM Data String Entries For Insite360 Connect .................................................................................... 18
Table 4. DIM Parameter Definitions (Reference) ...................................................................................................... 18

1
Introduction
The Insite360 Connect transfers station data (such as inventory, alarm history, dispenser volume events, etc.)
from an Automatic Tank Gauge (ATG) TLS-300 or TLS-350 having software version 24 or later, to secure Cloud
storage where it can be used for Insite360 FuelQuest services such as Insite360 Visibility, Inventory
Forecasting, Advanced Variance Analysis services, and more.
The Insite360 Connect communicates with the ATG via a serial connection to either the ATG’s Serial
Communications port or Electronic Dispenser Interface Module (EDIM) port and to the Cloud storage via a
secure hardwired Ethernet connection to the Internet.
Safety Precautions
The safety symbols used in this manual are to alert you to important safety hazards and precautions that must
be followed when installing the equipment described herein.
Related Manuals
576013-623 TLS-3XX Setup Manual
577013-776 TCP/IP Interface Module Installation Guide
CAUTION
Indicates a hazardous situa-
tion which, if not avoided,
could result in minor or moder-
ate injury.
READ ALL RELATED MANUALS
Knowledge of all related procedures
before you begin work is important.
Read and understand all manuals thor-
oughly. If you do not understand a pro-
cedure, ask someone who does.
WARNING
The Insite360 Connect is installed in the vicinity of high voltages which can be
lethal as well as low power devices that must be kept intrinsically safe.
FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY
PRECAUTIONS COULD CAUSE DAMAGE TO PROPERTY, ENVIRONMENT,
RESULTING IN SERIOUS INJURY OR DEATH.
1. Power to the ATG or to the POS does not have to be turned off when
installing this device.
2. Do not open the ATG door(s) when installing this device.

2
Insite360 Connect Description
Table 1 lists the kits required for Insite360 Connect installation and Figure 1 describes the Insite360 Connect’s
communication ports and indicator LEDs.
Figure 1. Insite360 Connect’s Ports And LEDs
Table 1. Kits Required For Insite360 Connect Installation
Part Number Description
330020-833 Insite360 Connect, cables and mounting fasteners for ATG with no POS connection
330020-834 POS Upgrade kit (additional cables and adapters for ATG with POS connection)
Ethernet
Port
Charging electronic
devices with the Insite360 Connect’s
unused USB ports could cause
overheating and equipment damage.
DO NOT charge electronic devices
with these unused USB ports.
USB 1
(To ATG)
USB 2 (To POS)
Unused
USB
Ports
Status
(Green LED)
Unused
Power
(Red LED)
Communication Ports
Indicator LEDs

3
Installation
Mounting The Insite360 Connect
The Insite360 Connect must be installed within 7 feet of, and in the same area and environment as, your ATG.
The Insite360 Connect requires access to a 100 to 240Vac wall outlet for its power supply. Mount the
Insite360 Connect using either the provided screws (Method A) or the hook and loop self-fastening strips
(Method B).
Method A
Method B
1. Cut out template (inside back cover of this manual)
2. Drill 2 pilot holes
4. Push slots in back of the unit onto
mounting screws (1) and slide down (2)
3. Install wall anchors
12
2. Remove the
paper cover from
the adhesive side
of one of the self-
fastening strips
and press it onto
the cleaned wall
surface.
1. Open one alcohol
packet from the kit
and clean the back of
the Insite 360
Connect and the wall
surface where you
want to attach the
unit.
3. Remove the paper cover from
the adhesive side of the other
self-fastening strip and press it
onto the cleaned back of the unit.
4. Ater waiting 20- 30 minutes
for the self-fastening strips to
bond to their surfaces, align the
Insite360 Connect strip over the
wall strip and push the unit
firmly against the wall.

4
Insite360 Connect Installation Option - Scenario 1
Scenario 1 applies to sites where the Insite360 Connect connects to a free serial port in the TLS-300 or TLS-
350. If the TLS-350 has the optional BIR and a Dispenser Interface Module (DIM), Dispenser Volume Events will
be sent to the GVR cloud. The steps in this Insite360 Connect installation require cables contained in kit 330020-
833.
All wiring should be installed and connected in accordance with local regulations. To avoid
injury or property damage, use only the power supply provided with the Insite360 Connect.
1. Connect the Insite360 Connect’s USB 1 Port to an available RS232 serial port on the ATG, using the USB
to Serial Adapter cable connected to either the DB9 female / DB9 male 6’ cable (Figure 2) or the DB9
female / DB25 male 6’ cable (Figure 3), depending on the ATG’s available serial port connector type.
The USB to Serial Adapter cable’s thumb screws need to be fully threaded into the 6' cable’s
standoffs, and the 6' cable’s thumb screws need to be fully threaded into the RS232 serial port.
2. Connect the Ethernet Port on the Insite360 Connect to a modem, router, or network switch on your local
area network (LAN) using the kit’s Ethernet cable.
3. Plug the power supply into the Insite360 Connect. Use the cable clamps and cable ties from the kit as
needed to properly route and secure the cables.
4. Plug the power unit of the Insite360 Connect power supply into an available wall outlet.
5. Review the Insite360 Connect Configuration section on page 12 to confirm device activation

5
Figure 2. Scenario 1 Insite360 Connect Hookup - TLS-350 With DB9 Serial Port Connection
USB-to-Serial adapter cable
Ethernet cable
Local
Area
Network GVR Cloud
Internet
TCP/IP
DB9F
DB9M
To DIM
(Requires
optional BIR)
DB9M
USB 1
ALARM
WARNING
POWER
T1: PREMIUM UNLEADED
VOLUME
ULLAGE
90% ULLAGE
TC VOLUME
HEIGHT
WATER VOL
WATER
TEMP
T1: REGULAR GASOLINE
VOLUME
ULLAGE
90% ULLAGE
TC VOLUME
HEIGHT
WATER VOL
WATER
TEMP
4208 GALS
5792 GALS
4792 GALS
4194 GALS
41.02 INCHES
0 GALS
0.00 INCHES
65.0 DEG F
9038 GALS
962 GALS
0 GALS
8950 GALS
81.37 INCHES
28 GALS
1.37 INCHES
74.9 DEG F
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
ATG
( TLS-350)
POS
9-pin to 9-pin
Null modem cable
NOTICE To ensure successful communication,
for consoles with an available DB9 RS232 port,
do not connect the USB to Serial adapter cable
directly to the console’s serial port.
NOTICE
Ethernet
Power
USB 2
USB 1
USB 4
USB 3
MODEL P/N: 330020-833
DEVICE S/N:
MAC Address:
GVR/FMSSite ID:
ContainsFCC ID: 2ABCB-RPI32
To avoid overheating and equipment
damage, DO NOT charge electronic
devices with the unused USB ports.
NOTICE

6
Figure 3. Scenario 1 Insite360 Connect Hookup - TLS-300/350 With DB25 Serial Port Connection
Ethernet cable
GVR Cloud
Internet
TCP/IP
DB9F
DB25M
DB9M
USB 1
ALARM
WARNING
POWER
T1: PREMIUM UNLEADED
VOLUME
ULLAGE
90% ULLAGE
TC VOLUME
HEIGHT
WATER VOL
WATER
TEMP
T1: REGULAR GASOLINE
VOLUME
ULLAGE
90% ULLAGE
TC VOLUME
HEIGHT
WATER VOL
WATER
TEMP
4208 GALS
5792 GALS
4792 GALS
4194 GALS
41.02 INCHES
0 GALS
0.00 INCHES
65.0 DEG F
9038 GALS
962 GALS
0 GALS
8950 GALS
81.37 INCHES
28 GALS
1.37 INCHES
74.9 DEG F
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
ATG
( TLS-300 or
TLS-350)
POS
To TLS 350 DIM
(Requires
optional BIR)
USB-to-Serial adapter cable
9-pin to 25-pin
Null modem cable
Local
Area
Network
Ethernet
Power
USB 2
USB 1
USB 4
USB 3
MODEL P/N: 330020-833
DEVICE S/N:
MAC Address:
GVR/FMSSite ID:
ContainsFCC ID: 2ABCB-RPI32
To avoid overheating and equipment
damage, DO NOT charge electronic
devices with the unused USB ports.
NOTICE

7
Insite360 Connect Installation Option - Scenario 2
Scenario 2 applies to sites where the ATG has an EDIM module connected to a POS and no free serial port for
a dedicated connection to Insite360 Connect. In this scenario, the Insite360 Connect communicates with the
ATG through the EDIM to retrieve data to be pushed to the Cloud, while allowing normal communications
between the EDIM and the POS to pass through uninterrupted. The steps in this Insite360 Connect installation
require cables contained in kit 330020-833 and kit 330020-834.
All wiring should be installed and connected in accordance with local regulations. To avoid
injury or property damage, use only the power supply provided with the Insite360 Connect.
1. At the ATG EDIM board, disconnect the existing DB25M connector of the POS cable.
2. Plug this disconnected POS cable into the DB25F end of the DB25 female / DB9 female mini gender
changer adapter (330020-834 kit) (see Figure 4).
The POS cable’s thumb screws (if equipped) need to be fully threaded into the gender
changer adapter’s standoffs.
3. Connect the DB9M end of the USB to Serial Adapter cable (330020-834 kit) to the DB25 female / DB9
female mini gender changer adapter connected to the POS cable.
The USB to Serial Adapter cable’s thumb screws need to be fully threaded into the gender
changer adapter’s standoffs.
4. Connect the USB end of the USB to Serial Adapter cable to the Insite360 Connect’s USB port 2.
5. Connect the Insite360 Connect’s USB 1 Port to the EDIM serial port on the ATG, using the USB to Serial
Adapter cable (330020-833 kit) connected to the DB9 female / DB25 male 6’ cable (330020-833 kit).
The USB to Serial Adapter cable’s thumb screws need to be fully threaded into the 6'
cable’s standoffs, and the 6' cable’s thumb screws need to be fully threaded into the EDIM
serial port.
6. Connect the Ethernet Port on the Insite360 Connect to a modem, router, or network switch on your local
area network (LAN) using the Ethernet cable (330020-833 kit).
7. Plug the power supply into the Insite360 Connect. Use the cable clamps and cable ties from the kit as
needed to properly route and secure the cables.
8. Plug the power unit of the Insite360 Connect power supply into an available wall outlet.
9. Review the Insite360 Connect Configuration section on page 12 to confirm device activation

8
Figure 4. Scenario 2 Insite360 Connect Hookup - TLS-350 With EDIM Connection To POS
9-pin to 25-pin cable
Ethernet cable
Straight 9-pin to
25-pin Adapter
GVR Cloud
Internet
TCP/IP
DB9F
DB25M
DB25M
DB9M
DB9M
USB 1
USB 2
ALARM
WARNING
POWER
T1: PREMIUM UNLEADED
VOLUME
ULLAGE
90% ULLAGE
TC VOLUME
HEIGHT
WATER VOL
WATER
TEMP
T1: REGULAR GASOLINE
VOLUME
ULLAGE
90% ULLAGE
TC VOLUME
HEIGHT
WATER VOL
WATER
TEMP
4208 GALS
5792 GALS
4792 GALS
4194 GALS
41.02 INCHES
0 GALS
0.00 INCHES
65.0 DEG F
9038 GALS
962 GALS
0 GALS
8950 GALS
81.37 INCHES
28 GALS
1.37 INCHES
74.9 DEG F
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
POS
USB-to-Serial
adapter cable
ATG
( TLS-350)
Local
Area
Network
Ethernet
Power
USB 2
USB 1
USB 4
USB 3
MODEL P/N: 330020-833
DEVICE S/N:
MAC Address:
GVR/FMSSite ID:
ContainsFCC ID: 2ABCB-RPI32
To avoid overheating and equipment
damage, DO NOT charge electronic
devices with the unused USB ports.
NOTICE

9
Insite360 Connect Installation Option - Scenario 3
Scenario 3 applies to sites where the ATG has an RS232 serial comm port connected to a POS and no
additional free serial port for a dedicated connection to the Insite360 Connect. In this scenario, the Insite360
Connect communicates with the ATG through the RS232 serial comm port to retrieve data to be pushed to the
Cloud, while allowing normal communications between the RS232 serial comm port and the POS to pass
through uninterrupted. In this configuration, there is no BIR performed and no sales data is processed or
transmitted. The steps in this Insite360 Connect installation require cables contained in kit 330020-833 and kit
330020-834.
All wiring should be installed and connected in accordance with local regulations. To avoid
injury or property damage, use only the power supply provided with the Insite360 Connect.
1. At the ATG RS232 serial comm port, disconnect the existing DB9M or DB25M connector of the POS
cable, if applicable.
2. Plug the end of this POS cable into either the DB25F end of the DB25 female / DB9 female mini gender
changer adapter (if the POS cable end is a DB25M, see Figure 5) or into either side of the DB9 female /
DB9 female mini gender changer adapter (if the POS cable end is a DB9M, see Figure 6). Both adapters
are included in the 330020-834 kit.
The POS cable’s thumb screws (if equipped) need to be fully threaded into the gender
changer adapter’s standoffs.
3. Connect the DB9M end of the USB to Serial Adapter cable (330020-834 kit) to the DB9 female end of
the mini gender changer adapter connected to the POS cable.
The USB to Serial Adapter cable’s thumb screws need to be fully threaded into the gender
changer adapter’s standoffs.
4. Connect the USB end of the USB to Serial Adapter cable to the Insite360 Connect’s USB port 2.
5. Connect the Insite360 Connect’s USB 1 Port to the RS232 serial comm port on the ATG, using the USB
to Serial Adapter cable connected to either the DB9 female / DB9 male 6’ cable (Figure 5) or the DB9
female / DB25 male 6’ cable (Figure 6), depending on the ATG’s available serial port connector type.
The USB to Serial Adapter cable’s thumb screws need to be fully threaded into the 6'
cable’s standoffs, and the 6' cable’s thumb screws need to be fully threaded into the RS232
serial port.
6. Connect the Ethernet Port on the Insite360 Connect to a modem, router, or network switch on your local
area network (LAN) using the Ethernet cable (330020-833 kit).
7. Plug the power supply into the Insite360 Connect. Use the cable clamps and cable ties from the kit as
needed to properly route and secure the cables.
8. Plug the power unit of the Insite360 Connect power supply into an available wall outlet.
9. Review the Insite360 Connect Configuration section on page 12 to confirm device activation.

10
Figure 5. Scenario 3 Insite360 Connect Hookup - TLS-3XX With DB25 Serial Comm Port And POS
9-pin to 25-pin cable
Ethernet cable
Straight 9-pin to
25-pin Adapter
GVR Cloud
Internet
TCP/IP
DB9F
DB25M
DB25M
DB9M
DB9M
USB 1
USB 2
ALARM
WARNING
POWER
T1: PREMIUM UNLEADED
VOLUME
ULLAGE
90% ULLAGE
TC VOLUME
HEIGHT
WATER VOL
WATER
TEMP
T1: REGULAR GASOLINE
VOLUME
ULLAGE
90% ULLAGE
TC VOLUME
HEIGHT
WATER VOL
WATER
TEMP
4208 GALS
5792 GALS
4792 GALS
4194 GALS
41.02 INCHES
0 GALS
0.00 INCHES
65.0 DEG F
9038 GALS
962 GALS
0 GALS
8950 GALS
81.37 INCHES
28 GALS
1.37 INCHES
74.9 DEG F
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
POS
USB-to-Serial
adapter cable
ATG
( TLS-300 or
TLS-350))
Local
Area
Network
Ethernet
Power
USB 2
USB 1
USB 4
USB 3
MODEL P/N: 330020-833
DEVICE S/N:
MAC Address:
GVR/FMSSite ID:
ContainsFCC ID: 2ABCB-RPI32
To avoid overheating and equipment
damage, DO NOT charge electronic
devices with the unused USB ports.
NOTICE

11
Figure 6. Scenario 3 Insite360 Connect Hookup - TLS-350 With DB9 Serial Comm Port And POS
9-pin to 9-pin cable
Ethernet cable
Straight 9-pin to
9-pin Adapter
GVR Cloud
Internet
TCP/IP
DB9F
DB9M
DB9M
DB9MDB9M
USB 1
USB 2
ALARM
WARNING
POWER
T1: PREMIUM UNLEADED
VOLUME
ULLAGE
90% ULLAGE
TC VOLUME
HEIGHT
WATER VOL
WATER
TEMP
T1: REGULAR GASOLINE
VOLUME
ULLAGE
90% ULLAGE
TC VOLUME
HEIGHT
WATER VOL
WATER
TEMP
4208 GALS
5792 GALS
4792 GALS
4194 GALS
41.02 INCHES
0 GALS
0.00 INCHES
65.0 DEG F
9038 GALS
962 GALS
0 GALS
8950 GALS
81.37 INCHES
28 GALS
1.37 INCHES
74.9 DEG F
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
POS
USB-to-Serial
adapter cable
ATG
(TLS-350))
Local
Area
Network
NOTICE To ensure successful communication,
for consoles with an available DB9 RS232 port,
do not connect the USB to Serial adapter cable
directly to the console’s serial port.
NOTICE
MINI GENDER CHANGER
Ethernet
Power
USB 2
USB 1
USB 4
USB 3
MODEL P/N: 330020-833
DEVICE S/N:
MAC Address:
GVR/FMSSite ID:
ContainsFCC ID: 2ABCB-RPI32
To avoid overheating and equipment
damage, DO NOT charge electronic
devices with the unused USB ports.
NOTICE

12
Insite360 Connect Configuration
After physically setting up the Insite360 Connect and powering it up, the device will boot and if the device has
already been commissioned for your site (indicated by the presence of a GVR/FMS Site ID number on the
Insite360 Connect’s label [see Figure 7]), it will automatically connect to the GVR Cloud to register and configure
itself within several minutes. Refer to Table 2 (Insite360 Connect LED Status Lights) in the Troubleshooting guide
on the following page to confirm device activation. If the activation does not complete automatically as indicated
by the status LEDs, please contact Insite360 FuelQuest Fuel Management Services at 800-997-7725.
If the GVR/FMS Site ID number on the Insite360 Connect’s label is blank (indicating the device has not already
been commissioned for your site [See Figure 7]), please contact Insite360 FuelQuest Fuel Management Services
at 800-997-7725.
Figure 7. Locating Insite360 Connect’s GVR/FMS Site ID Number
Ethernet
Power
USB 2
USB 1
USB 4
USB 3
MODEL P/N: 330020-833
DEVICE S/N:
MAC Address:
GVR/FMSSite ID:
ContainsFCC ID: 2ABCB-RPI32
To avoid overheating and equipment
damage, DO NOT charge electronic
devices with the unused USB ports.
NOTICE

13
Troubleshooting
LED Status Lights
The Insite360 Connect’s LED status lights indicate operational status (see Table 2).
Table 2. Insite360 Connect’s LED Status Lights
LED Status Description
Power (Red) On Power is connected.
Status* (Green)
On Insite360 Connect fully booted, registered and running.
Off Insite360 Connect application not running, reboot Insite360
Connect.
1 blink pattern No GVR Cloud communication. Check Internet connection.
2 blink pattern No ATG communication. Check connection between Insite360
Connect and ATG.
3 blink pattern No POS communication. Check connection between Insite360
Connect and POS.
4 blink pattern
Insite360 Connect not registered. Check label on front of
Insite360 Connect for correct GVR/FMS Site ID and address.
Call 800-997-7725 if missing.
5 blink pattern Insite360 Connect software download in progress.
*The blinking patterns for all codes occur in series, repeating. For example, if there is no GVR Cloud commu-
nication (1 blink) and no ATG communication (2 blinks), the pattern would be: [1 blink, pause, 2 blinks,
pause] and will repeat until one of both of those issues are resolved.

14
ATG Serial Port Setup
The ATG serial port settings must be configured to 9600 Baud, Data Bits 7, Parity Odd, Stop Bits 1. At the
console’s front keypad press the MODE key until the display reads System Setup in the display.
Press FUNCTION until you see the message:
Press STEP until you see the message:
This display allows you to access the communication settings—Baud Rate, Parity, Stop Bit and Data Length—for
any Comm board installed in the console’s Comm Bay.
Press ENTER to display the message:
The system labels the communications module in the leftmost slot as “COMM BOARD: 1”. If this is not the Comm
board to which you connected the Insite360 Connect, press TANK/SENSOR until the Insite360 Connect
connected Comm board displays.
The correct Baud Rate for Insite360 Connect is 9600. If the rate shown on the display is 9600, press STEP. If the
Baud Rate is incorrect, press CHANGE until you see the correct baud rate of 9600. Press ENTER to confirm
your choice. The system displays the message:
Press STEP to continue.
COMMUNICATIONS SETUP
PRESS <STEP> TO CONTINUE
PORT SETTINGS
PRESS <ENTER>
COMM BOARD: X (Type)
BAUD RATE: 1200
BAUD RATE: 9600
PRESS <STEP> TO CONTINUE
COMM BOARD: X (Type)
PARITY: ODD

15
The choices are NONE, ODD, and EVEN. The correct Parity for Insite360 Connect is ODD. If the Parity shown
on the message is ODD, press STEP. To choose the correct Parity setting, press CHANGE until you see the
correct selection. Press ENTER to confirm your choice. The system displays the message:
Press STEP to continue.
The choices are 1 or 2. The correct stop bit selection for Insite360 Connect is 1. If the Stop Bit shown on the
message is 1, press STEP. To choose the correct Stop Bit setting press CHANGE and press ENTER to
confirm your choice. The system displays the message:
Press STEP to continue.
The choices are 7 or 8. The correct Data Length selection for Insite360 Connect is 7. If the Data Length shown
in the message is 7, press MODE to exit the System Setup mode. To choose the correct Data Length press
CHANGE and press ENTER to confirm your choice. The system displays the message:
Press Mode to exit the System Setup mode.
PARITY: ODD
PRESS <STEP> TO CONTINUE
COMM BOARD: X (Type)
STOP BIT: 1 STOP
STOP BIT: 1 STOP
PRESS <STEP> TO CONTINUE
COMM BOARD: X(Type)
DATA LENGTH: 7 DATA
DATA LENGTH: 7 DATA
PRESS <STEP> TO CONTINUE

16
ATG EDIM Comm Port Setup
The ATG EDIM Comm port settings must be configured for Insite360 Connect operation. At the console’s front
keypad press the MODE key until the display reads Diag Mode in the display.
Press FUNCTION until you see the message:
Press STEP until you see the message:
Press ENTER to display the message:
The first two characters in this display ‘X1’ indicate the DIM type in Comm slot 1: ‘M’ for MDIM module; ‘E’ for any
other DIM type. You are looking for the EDIM Comm board (an E type DIM) so If this is not the Comm board to
which you connected the Insite360 Connect, press TANK/SENSOR until the correct Comm board displays, e.g.,
if the Insite360 Connect is connected to the EDIM in slot 3 (3rd from left), then you press TANK/SENSOR until
you see E3:)
Press STEP until you see the message:
The correct selection depends on the BIR reporting units for your site and if your site has a Gilbarco Protocol or
VR Protocol DIM. See Table 3 below for the correct EDIM Data String entry for Insite360 Connect. Table 4 is for
reference and defines the letters used in EDIM Data String entries.
SYSTEM DIAGNOSTIC
PRESS <STEP> TO CONTINUE
DIM DIAGNOSTIC DATA
PRESS <ENTER>
X1:SWARE#XXXXXX-XXX-X
CREATED - YY-MM-DD-HH-MM
DISP. MODULE DATA STRING
EDIM X:

17
.
If the entry shown in the display is correct for your EDIM protocol/BIR reporting units, press STEP. If the entry
is incorrect, press CHANGE and enter the correct entry for your site as shown in Table 3. Press ENTER to
confirm your choice. The system displays the message:
The display above shows the correct entry Gfor a North American site in which the Insite360 Connect is
plugged into a VR protocol EDIM.
Press Mode to exit the System Setup mode.
Table 3. EDIM Data String Entries For Insite360 Connect
EDIM Protocol
EDIM Data String Selection
For U.S. Units For Metric Units For Imperial Units
VR Protocol GNo entry - leave blank I
Gilbarco Passport B9OHVG B9OHV B9OHVI
Table 4. DIM Parameter Definitions (Reference)
Baud Parity Stop Bits Data Bits Conversion
String Rate String Type String Bits String Bits String Unit
B9 9600 NNone H 1 V 7 G Gallons
B4 4800 EEven S 2 D 8 M Metric
B2 2400 OOdd IImperial
B1 1200
B6 600
B3 300
BG ***
EDIM X: G
PRESS <STEP> TO CONTINUE
Table of contents