VENTOMAXX Z-WRG RONDO IQ User manual

Montageanleitung
Z-WRG RONDO IQ
Bedienungsanleitung WRG-System
Security Note
For your safety, please read before initial operation of the device
the information through carefully. You get important
Advice for proper operation and maintenance of your new device.
VentomaxxInternational is not liable if the following instructions are not followed.
The decentralized
Residential ventilation
according DIN 1946 - Teil 6
measured b DIN EN 20140-10 y
Tested in accordance with the principles of building inspection approved
sound inspection bodies in coordination with the NABau UA DIN 4109 Supplement 1 00.71.02.
measured by D EN ISO 717-1; test bench by EN ISO 140-1
witht central
Control
for controlling of 1-6 stations
Subject to technical modifications 01.2015 © Ventomaxx International GmbH
Ventomaxx InternationalGmbH Herzog Georg Platz 4 84028 Landshut www.ventomaxx-international.com

› Z-WRG RONDO IQ 2
Safety instructions
ATTENTION!
Protect the device from moisture and wetness!
!Disconnect appliance from the mains before opening
All People who do the installation, commissioning and maintenance of the device must be appropriately
qualified. These operating instructions must be strictly observed! We will send you Possibly missing documents
on request at short notice
The ventilation unit is operated with extra-low voltage; the controller is connected directly to the mains.
The device controller may only be connected to the intended voltage and frequency that correspond
exactly to the name plate of the device.
The cable entry of flush mounted Control Panel not by pulling burden! There must always be out there a
sufficient cable lenght to the device. Otherwise, the cable may be damaged, which can lead to
fatal electric shocks..
When cleaning or revision of the device, this has to be taken out of operation; excessive dirt in and at the
device should only be removed by a skilled person; the current circuit must be interrupted to all poles.
The cleaning of the room-side cover should only be carried only with a damp cloth.
Ingress of water or other liquids enter the device must be avoided. Should this happen, immediately disconnect
the power supply by pulling the power cord or turn off the device fuse. Do not turn the power back on and
secure it so that no unauthorized Commissioning can take place.
First check for proper condition of the package and the individual accessories. Pay attention to in perfect
condition of the power cord and the current-carrying cable to the fan unit. It is essential to ensure that no
damage and kinks is found it.
safety instructions
Electrical installation
Operating instructions
Mounting instruction
Mounting template for preparing the wall openingPage 4
Mounting the roughconstruction ring module set, Mounting Type LAW, straight through the wallPage 5
Mounting the roughconstruction ring module set, Mounting Type LAL, concealed within the revealPage 6
General installation prerequisitesPage 3
Final assembly room side - Electrical connectionPage 7
Final assembly room side / inner casingPage 8
Mounting of the central controllerPage 9
General operating instructions / warrantyPage 10
Geräteaufbau / BedienfeldPage 11
General operating instructions / warrantyPage 12
Configuration mode / operating settingsPage 13
Status indications / filter changePage 14
Device maintenance / filter changePage 15

› Z-WRG RONDO IQ 3
Mounting instruction
If the device does not work correctly, please call for a authorized service provider.
Aside from the filter change / cleaning Device, no further maintenance is required. Please disconnect before each
filter change the power plug or turn off the power without power by turning off the fuse
The Z-WRG RONDO IQ is designed for the ventilation of dry indoor rooms. Please make sure that the air outlet
is not covered by any objects. A liability for other uses can not be accepted. To avoid moisture damage or injury
to health, pay due attention to sufficient ventilation. Depending on space utilization supporting window vents
(e.g. draft ventilation on the day) or the manufacture of indoor air network with multiple Z-WRG devices or the
support of a bathroom / toilet exhaust system are required..
A proper operation of ventilation systems with heat recovery presupposes the shutoff of available of
existing combustion air ducts.
Z-WRG RONDO IQ Ventilation units can be used in all conventional wall structures easy to assemble and close when
installed inside and outside almost flush..
The system is modular so that the device insert already in the construction phase in the desired mounting version
(e.g. LAW, straight through the wall; LAL, concealed within the soffit) can be prepared.
The Z-WRG concept is based on a central control of individual devices stations. Here is the central controller to the AC
mains voltage is 85-260V, 50 / 60Hz connected securely. The individual units are connected to the central control via
bell wire (sh. Wiring diagrams of
Control). The furthest distance between the controller and device should not exceed 50 meters..
Application limits:
Min. Working temperature + 5 ° C. At lower temperatures the rubber seals may lose their flexibility. Please avoid
damage due to high mechanical stress.
Please note:
To bring the unit inside the wall are openings outer wall-site manufacture in accordance with the following
description. The required standard wall opening is 200 mm in diameter to provide (other diameters, if necessary,
depending on the situation required). These installation instructions describe the installation of the fan part in a
monolithic outer wall. Please determine which wall structure is present and use only specified by the manufacturer
fasteners for the wall.
Depending on the characteristics of the wall, different regulations / safety precautions must be observed (eg when
asbestos-containing facade, etc).
The Assembly is therefore in principle be carried out by specialist companies. If you are not sure which trades for
installation comes into consideration or what tools and auxiliary materials for a professional installation is required,
so you hesitate to contact us!
In the execution of all work with machinery and devices the instructions of the machine supplier / device
manufacturer must be observed. All work must be performed with the recommended protective clothing (e.g., mouth,
eye protection, gloves, etc.)!!
When choosing your installation situation, note the following:
At the drilling no supply lines may pass; for multi-layered structure is to ensure that the pierced vapor barrier is sealed
according to the manufacturer; in weatherproof areas is impinged on the outside of the fan to provide a weather
protection (sh. This also hints respective Mounting)..
the room-side arrangement of the housing should be selected so that the accessibility of the revision of the device is
always possible. The air outlet on the unit must remain free in the range of about 25-30 cm and allowed to furniture
not be moved or disturbed etc..
General installation prerequisites

Cross-Connector
A B
CD
4
Z-WRG RONDO IQ › Preparation wall opening and electrical connection 04
Retractable cord
Connection input Connector output
The ventilation units of this series (max. 6 stations)
be operated via a central control unit and
a JY (ST) -Y 2x2x0.6 supplied with 12 volt low voltage.
The cable length should not exceed 60 meters / 18,29ft.
Preparing for installation:
For the current supply the central control unit ZS-IQ
is provide for in the distribution of a 230 volt power connection via NYM-J 3x1.5.
Protection is provided with 6 A.
Z-WRG RONDO IQ
230 Volt supply,
with 6 A .hedged
ZS-IQ Central control
12 Volt
low voltage
2x2x0,6
Electric wiring diagram
230 Volt Connection of ZS-IQ control
in the distribution / DIN rail mounting
Cor drilling 200 mm| 7,87 in
IQ-Design-Cover
200 x 200 x 12 mm
7,87x7,87x0,47 in
( 185-190 mm |7,28 - 7,48 in)without plaster / in renovation
Rough Construction-Ring
Module Set
The two VLE-centering (acc. Factory default setting)
can be prepared by Extension to 4 pieces,
mixed by reconnecting. Position A to D,be used
as additional mounting for the IQ-design panel.

CCA-IQ
CCA-IQ
CCA-IQ
CCA-IQ
CCA-IQ
CCA-IQ
Fan 1
Fan 2
Fan 3
Fan 4
Fan 5
Fan 6
ZS-IQ
› MOUNTENING INSTRUCTION / Wiringplan 5
Device Series: Z-WRG IQ
Wiringplan
Cross-Connector Type:
CCA-IQ
Control Type: ZS-IQ
Cable lenght:
A+B+C+D+E+F < 50 m: 2x2x0,8 mm
A+B+C+D+E+F > 60 < 90 m: 2x2x0,8 mm + Return circuit G (L-max 90 m)
2
2
A+B+C+D+E+F < 25 m: 2x2x0,6 mm

Inside
Outside
sealing adhesive
Plaster cover
Inside
Outside
Plaster cover
Plaster cover
RS-LAW
Plaster cover
straight through the wall
› INSTALLATION INSTRUCTIONS / rough construction mounting Type LAW 6
Facade border
FA-LAW-K
Rough construction
Ring Module Set
RS-LAW
Equipment unit
Z-WRG RONDO IQ
The illustration shows a
Sectional view of Z-WRG RONDO IQ
in mounted version LAW,
straight through the wall
1. Preparing the wall breakthrough
3. Ring Module Set push it into the wall,
aligning and fixing free of tension
b) after adjusting the ring module set to the
Wall thickness (extending over VLE-Ring Module
and if necessary, cut the outer pipe
end are still existing connection
jointless diffusion-tight seal with VX-FK
5. With 2-component acoustic foam
Fix VX-2K peripherally in the wall
6. Protection units against pollution
7. Façade completion after completion
mount of plastering and painting work
4. For larger openings, cavities
additionally with rock wool, mineral wool
stuffed or isolate expertly
a) Room-side opening gap between wall and duct
diffusion-tight / permanently elastic sealing
(Ventomaxx assembly sealing adhesive VX-FK)
2. Overall length with ring modules manufacture
(thickness incl. Insulation and plaster)
a) opening round 200 mm or square W/H
200 x 190 mm Making or prepare in
rough construction
b) Empty tube provided or low-voltage cable
2x2x0.6 acc. Wiring plan laying!
b) so that the system support unit will not be
damaged with a fan during the construction
phase, it should be stored until final assembly
in a protected location
a) beforehand the cables are in the cable bags
introducing the ring module sets
The ring module set is designed for use in
Wall thicknesses from 300 mm designed;
ATTENTION: cut only on the outside!
c) at LAW-assembly is a incline of
rough construction ring module set of about
1.5-3 ° of provide inside to the outside..
a) thereto is the supplied protective cover
over the period of the construction phase
use (cleaning cover to RS-LAW)
Assembly instructions - Z-WRG RONDO IQ - Mounting Type LAW
d) after the completion of electrical work clipped
on the electric protection cover and hang the
appliance control panel
a) Before starting work, switch off the fuse /
Pull out the plug!
9. Electrical connection may only be made by
a qualified electrician!
8. Inside cover only shortly before the completion
of the construction project mounting
a) the room-side design panel can be applied to the
provided fixing points of the RS-LAW or attached
to the wall
b) to avoid deformations on the casing,
tighten the screws only moderately and evenly
b) Connection of max. 6 station per Z control
make according to the enclosed wiring diagram
f) further details should be available in time
bevore Beginning assembly, to clarify a project
basis; we are happy to help you on request
e) the device is now in the operating manual
ready for use.
c) Commissioning the stations according to
instructions in using the central controller
wall thickness Low-voltage installation cable
2x2x0.8 prepare
cable lenght > 60m
Low-voltage installation cable
2x2x0.6 prepare
cable lenght < 60m
Cut vertikal
Solid wall + insulation system
Preparing the total length
Inside
Slide in the Rough Construction -ring modul-Set
Outside
1,5 to 3° slope
by EPS mounting wedges
acoustically decoupled manufacturing
Ord-No: 9500-0030SP
mounting external
wall cover and
inner housing cover
In the lower area is an on-site sealing between rough construction Ring Module Set
and baseplate Façade close required (e.g. aluminum adhesive tape; sealing adhesive
Ventomaxx VX-FK sealing adhesive);at the top of the hood and sides of a Gasket on to the Façade
is necessary.
Please note mounting instructions for facade border!

concealed within of the reveal
5. With 2-component acoustic foam
Fix VX-2K peripherally in the wall
7. Unit protection against pollution
8. Fassadenabschluss nach Fertigstellung
der Putz- und Malerarbeiten montieren
a) thereto is the enclosed, room-side protection
cover throughout the building phase
use; In addition, we recommend using of
VX-LAL-plaster cover for the flat duct
a) Room-side opening gap between wall and duct
diffusion-tight / permanently elastic sealing
(Ventomaxx assembly sealing adhesive VX-FK)
9. Inside cover only shortly before the completion
of the construction project mounting
b) um Deformationen am Gehäuse zu vermeiden,
Schrauben nur mäßig, gleichmäßig anziehen
10. Electrical connection
may only be made by a qualified electrician!
a) VBefore starting work, switch off the fuse /
Pull out the plug! Further steps like
Mounting Type LAW; see also the
following pages.
1. Preparing the wall breakthrough
a) Opening round 200 mm or square W/H
200 x 190 mm Making or prepare in
rough construction
b) damit die Systemträgereinheit mit Ventilator
während der Bauphase keinen Schaden nimmt,
sollte diese bis zur Endmontage an einem
geschützten Ort zwischengelagert werden.
a) den verstellbaren Laibungsanschluss bündig
zum späteren Putzniveau der Laibungsecke
einjustieren / umlaufend abkleben
6. Flachkanal-System innerhalb der
Dämmebene einhausen
b) Schnittstelle zwischen Flachkanal, Dämm-
ebene und Putzanschlusses mit Kompriband
andichten
4. For larger openings, cavities
additionally with rock wool, mineral wool
stuffed or isolate expertly
Preparing low voltage cabel
2x2x0,6
a) the room-side design panel can be applied to the
provided fixing points of the RS-LAL or attached
to the wall
2. Manufacture fan length with ring modules
(At desired location within of the reveal)
The standard ring module set is for a
Fan nominal length prepared by about 330 mm;
Ring modules possibly expand; shorten and sealing
Caution: cut only on the outside!
3. Ring Module Set push it into the wall,
aligning and fixing free of tension
c) when LAL-mounting of the telescopic unit has a
incline of approx 1.5-3 ° must be provided from
the inside to the outside; at flat duct it is 5 °(degrees)
d) Flachkanal außenbündig auf Laibungsniveau
justieren; ggf. einkürzen; mittels passendem
Flachkanalhalter an der Außenwand befestigen
Outside
View sidwise
wall thickness
Manufacture of the
total length
Slide in the operating unit
Plaster cover
RS-LAL
Inside
Outside
cut vertikally
sealing adhesive
1,5 bis 3° slope
by EPS mounting wedges
acoustically decoupled manufacturing
Ord-No: 9500-0030SP
Plaster cover
Outside
Schnitt vertikal
mounting external
wall cover and
inner housing cover
Inside
channel junction with
ventilation tape
sealing encircle
When plaster facades we recommend a flat duct insulation of approximately 30 mm.
b) Empty tube provided or low-voltage cable
2x2x0.6 acc. Wiring plan laying!
b) after adjusting the ring module set to the
Wall thickness (extending over VLE-Ring Module
and if necessary, cut the outer pipe end are still
existing connection jointless diffusion-tight seal
with VX-FK
a) beforehand the cables are in the cable bags
introducing the ring module sets
The illustration shows a
Sectional view of Z-WRG RONDO IQ
in mounted version LAL,
für die verdeckte Integration
concealed within the reveal
Flachkanalhalter FKH
3-dimensional verstellbar
Rough construction
Ring Module Se
RS-LAL
Device unit
Z-WRG RONDO IQ
telescopable façade connection
with integrated condensate drain
Facade border
FA-LAx 37
IQ-Design-Cover
› INSTALLATION INSTRUCTIONS / rough construction mounting Type LAL 7
Cut vertikal
Solid wall + insulation system
Assembly instructions - Z-WRG RONDO IQ - Mounting Type LAW

Assembly instructions - Z-WRG RONDO IQ - Connection Preparation
1. Room side devices cabling
a) Remove room-side plaster cover and
Low-voltage cable J-Y (ST) -Y strip the
insulation..
c) The excess length of the stripped connection
Cables and the cross-connector in
Pockets of the rough construction ring module sets
store carefully
d) the ventilator power cable to the plug
from the electric-bag over the top
Cable slot carry into the pipe.
Connection preparation ZS-IQ
b) The wires shown beside
Connection diagram on the cross-connector
apply (short depression of
Latch on the Clamp)
Connection further
Z-WRG-units possible
(total max. 6)
J-Y(St)-Y
2x2 x 0,6 bzw
2x2 x 0,8
J-Y(St)-Y
2x2 x 0,6
Hygro
extern
2
Cross-Connector
Conection on the unit
weiss
braun
grün
Cross-Connector CCA-IQ
1
with
braun
geen
Cross-Connector
Conection on the unit
Cross-Connector CCA-IQ
ohne Maßstab
ATTENTION - MAINS VOLTAGE!
Installation has to be done by expert staff.
CAUTION
VOLTAGE!!
Montage hat durch
Fachpersonal zu erfolgen.
Low voltage
12VExtra- low voltage
2. Installation of control in distribution box
a) thereto attach the controller to the DIN rail
b) all wires according to wiring diagram page 8
installing
All following workings done when
current-voltage-free! Please make sure that
fuse and FI switch the 230 volt connection turn
without power!
ON
DIP
95-260VAC 50/60 Hz
Speed
+12V
A
GND
pot.
B
NON
Speed
nc
1600-1760VX
ZS-IQ
S
series switch
extern
L1
1.1
S
1.2
› INSTALLATION INSTRUCTIONS / ELECTRICAL INSTALLATION 8

Circuit diagram of ZS-IQ control
Assembly instructions - Z-WRG RONDO IQ - final assembling room side
Z-WRG RONDO IQ
Functions
ON
DIP
95-260VAC 50/60 Hz
Speed
+12V
A
GND
pot.
B
NON
Speed
nc
1600-1760VX
ZS-IQ
S
series switch
extern
L1
1.1
S
1.2
Netzspannung
wählbare Funktionen
› INSTALLATION INSTRUCTIONS / ELECTRICAL INSTALLATION 9
Programming interface
ON LED: operating status on/ off green
slow stage
fast stage
reached filter time
Internal Buzzer 2 min / h (interval)
controll off
controll on
slow fan speed
fast fan speed
Filter reset (Time frame 5 sec)
supply voltage
selctable function
SPEED SELECTION
SPEED STAGES 3/5
SPEED STAGES 2/4
SPEED STAGES 1/3
ext Hygrostat active (Prog.0)
ext Hygrostat active (Prog.1)
5 times seesaw

Final assembly room side
Filter in the 3er guide according
to behind slide; at the stopper
with 3 locking hooks locking
Filter insert
IQ-Cover with
the three locking hooks
on the base plate
plugging ( TOP )
56
7
7./8. Fitting the Room-side IQ design cover
a) IQ-Cover with the three locking hooks on the
IQ-Base plate plugged (sh. TOP / ABOVE)
The filter change is done in reverse
Direction on the release latch of
three clips and remove the
Filter frame on the middle clip
Retaining clip forward bend;
Replace filter frame at the three guides
and until it engages the latch hook,
Press successively backwards
5./6. Filter insert
b) the low-voltage fan (12V DC) is connected via a
quick plug connection with the low voltage line
to the central controller
a) First the ceramic heat exchanger in
the tube insert (until just before the pipe end)
Strip the low-voltage cable
1
4
Base plate of IQ Design
cover mount and
the heat exchanger
insert in the wall
3
Fan assembly
insert
2. connectLow-voltage line
a) Strip the wires
3. Room side IQ Base plate mounting
a) Base plate with the connecting piece in the
rough construction ring set insert and fix.
(Screws; or point gluing)
Remove plaster cover
Strip wires and according
Circuit diagram side 7, on
Cross-Connector apply;
Pay attention to polarity!
2
Please ensure that
the room side cover
is always open!
8
4. Fan unit insert
a) Fan unit carefully into the tube
flush push to the heat exchanger;
the fan gritt shows to the room side
1. Low-voltage line at the station
b) Low voltage power cable 2x2x0.6 in
slot of the ring module bend upward,
shorten to about 15 cm and removal of isolation;
a) Remove plaster cover
b) Wires according to the diagram apply on the cross
Connector
c) Cross-Connector with Cables in the cable bags
storing
3. Ceramik-heat exchanger insert
b) Set the desired opening cross section through
the locking features of the IQ-cover
› MOUNTING INSTRUCTION 10
Assembly instructions - Z-WRG RONDO IQ - final assembling room side

Z-WRG RONDO IQ
a) thereto the heat exchanger and the fan unit
slide into the tube and
by plugs connect (sh. and MI Page
10, step 3-8).
7. New Filter insert
Double switch
1
2. Filter-Reset after filter change
3. Remove room side IQ cover
a) the cover can be by pulling gently
without tools remove from the base plate
Device adjustment via
Operating Instructions - Z-WRG RONDO IQ
1. User condition
b) On the right rocker Should the
desired speed selection take place
LOW = small stage
HIGH = big stage
a) left rocker: Device ON / OFF switching
In conjunction with the filter change
it is advisable to clean the device
unit from inside and outside!
A filter change is after approx 4000
operating hours via a signal buzzer on the
control display.
The filter change signal, by 5 times
Switching the HIGH / LOW - switch
( within a time window of 5 Sec)
then it is deactivated and thus "reseted".
ON
OFF LOW
HIGH
Double switch (5x HIGH/LOW)
2
Filter-reset via
Filter changes / equipment cleaning
IQ-Cover remove
3
polluted filter to
the lower lip slightly
attracting and thereby from
the three locking points loosen
4
5
Fan unit
remove
heat exchanger
remove
6
insert new filter
7
Please ensure that
the room side cover
is always open!
8
4. Remove contaminated filter
a) pulling gently on of the lower clip of the filter
at the same time the three locking points by
press loosen
b) Dispose of the filter in the household waste
a) the ceramic heat exchanger pulling out over
the red revision btton without tools from the tube
6. ceramic-heat exchangerRemove
b) the low-voltage fan (12V DC)
can for cleaning purposes at the quick
Plug connection from the central controller
be disconnected
5. Remove fan unit
a) Fan unit out from the tube
remove; Clean with a soft brush;
b) for thorough cleaning of the heat exchanger can
either mechanically (in a dishwasher), or manually,
e.g. be cleaned under the shower
c) the entire inner ventilation unit is now for
cleaning accessible; the outer device
and the device environment should be at least
checked once a year and as required
be cleaned
b) Holder clip forward bend; filter frame at the
three guids replace and press until it engages
the latch hook, successively press backwards
› OPERATION MANUAL 11
ON
OFF LOW
HIGH
5 x
8. Fitting the Room-side IQ design cover
a) IQ-Cover with the three locking hooks on the
IQ-Base plate plugged (sh. TOP / ABOVE)
b) Set the desired opening cross section through
the locking features of the IQ-cover

TECHNICAL DATA
Z-WRG-RONDO IQ
Z-WRG Rondo IQ / LAW
ZS-IQ / via light switch program
1|3 2|4 3|5
3
17 m /h
3
22 m /h
3
25 m /h
3
35 m /h
3
43 m /h
> 90 %
HEX regenerativ
EC, axial, digital
1,4 – 3,4 Watt
85 – 260 Volt – AC
12V DC
Fixed network / electrical distribution
~ 17,5 – 41 dB
41 dB, D (gem. Prüfung Z38)
new
Hygienic filter G3
ABS white
ca. 200x200x12 mm
optional, Color to your choise
300 mm (380 mm)
ca. 3 – 4 kg
A
› TECHNICAL DATA 12
Power levels selectable
Air power level 1
Air power level 2
Air power level 3
Air power level 4
Air power level 5
Heat recovery
High performance heat exchanger
Fan typ
Power consumption (fan speed min - max)
Connection voltage (control), at 50 Hz (international wide range)
Operating voltage (station)
Power connection
Series / device version
Regulation / control
Sound pressure levels stage 1 – 5 *
Sound insulation (from outside noise) ** (standard sound level difference)
Filter (F6 optional)
Design-Room cover IQ160 (similar RAL 9003)
Casing dimensions HxWxD
facade border
(conform to the system made of stainless steel or aluminum with condensate drain)
Nominal length (with optional add-on module VLE 150)
Weight
Energy efficiency class
** Surface sound pressure level, Lpf
measurement in exhaust air mode
** WRG Plus measured by EN 140-10/EN ISO
140-2/EN ISO 717, according to test
certificate ift-Rosenheim
The suitable rough opening (about 185-200 mm) is a project basis (round
or square) to define so that it is always sufficiently covered by the selected
device aperture during the final assembly. We will gladly provide the
necessary dimensional drawings available on request.
Subject to technical modifications . Pictures and information without obligation.

* Surface sound pressure level, Lpf
measurement in exhaust air mode
** WRG Plus measured by EN 140-10/EN ISO
140-2/EN ISO 717, according to test
certificate ift-Rosenheim
*** with 48 dB, D
new a fan-nominal length of
360 mm is required
TECHNICAL DATA
Z-WRG-RONDO IQ
Z-WRG Rondo IQ / LAL
ZS-IQ / via light switch program
› TECHNICAL DATA 13
1|3 2|4 3|5
3
17 m /h
3
22 m /h
3
25 m /h
3
35 m /h
3
43 m /h
> 90 %
HEX regenerativ
EC, axial, digital
1,4 – 3,4 Watt
85 – 260 Volt – AC
12V DC
Fixed network / electrical distribution
~ 17,5 – 41 dB
Sound protection (from outside noise) ** (normalized level difference)
without additional sound insulation (SD)
optional with 1 SD (1 SD 160; Art.-No.: Z-1000-0152)
optional with 2 SD (1 SD 150; Art.-No.: Z-1000-0151 und 1 SD 160)
45 dB, D (according to test Z03)
new
47 dB, D (according to test Z04)
new
48 dB, D ***(according to test Z05)
new
Filter (F6 optional) Hygienically filter G3
ABS white
ca. 200x200x12 mm
optional, Color to your choise
330 mm (360 mm)
ca. 3 – 4 kg
Notes
Energy efficiency class A
for
request
+49 2361 499450
+49 2361 499456
www.Ventomax x International-International.com
info@Ventomaxx International -International.com
®
Ventomaxx International International GmbH
Herzog Georg Platz 4 • 84028 Landshut
Telefon
Telefax
Internet
E-Mail
Technical changes reserved © Ventomaxx International International GmbH
Power levels selectable
Air power level 1
Air power level 2
Air power level 3
Air power level 4
Air power level 5
Series / device version
Regulation / control
Heat recovery
High performance heat exchanger
Fan typ
Power consumption (fan speed min - max)
Connection voltage (control), at 50 Hz (international wide range)
Operating voltage (station)
Power connection
Sound pressure levels stage 1 – 5 *
Design-Room cover IQ160 (similar RAL 9003)
Casing dimensions HxWxD
facade border
(conform to the system made of stainless steel or aluminum with condensate drain)
Nominal length (with optional add-on module VLE 150)
Weight
The suitable rough opening (about 185-200 mm) is a project basis (round
or square) to define so that it is always sufficiently covered by the selected
device aperture during the final assembly. We will gladly provide the
necessary dimensional drawings available on request.
Table of contents
Other VENTOMAXX Fan manuals
Popular Fan manuals by other brands

atomi smart
atomi smart AT2003 quick start guide

Ebmpapst
Ebmpapst W2S130-AB03-34 operating instructions

Oriental motor
Oriental motor ORIX MRS18V2 operating manual

Air King
Air King ASLC120 Specifications

Mitsubishi Electric
Mitsubishi Electric Lossnay VL-100U5-E operating instructions

Sealey
Sealey HVD42B instructions

Panasonic
Panasonic FV-05VFL2 installation instructions

Duco
Duco DucoBox Silent Series installation guide

Mitsubishi Electric
Mitsubishi Electric Lossnay LGH-15RX5-E operating instructions

BLAUBERG Ventilatoren
BLAUBERG Ventilatoren Moon user manual

Siegenia
Siegenia AERO Assembly and operating instructions

Carrier
Carrier 39CZ Installation, operation and maintenance instructions