Vertiv Liebert iCOM DP400/500 Installation and maintenance instructions

Liebert®
iCOM™
Installer/User Guide
Intelligent Communication and Monitoring for Liebert DSE Packaged Solution DP060,
DP400/500

Vertiv™ | Liebert® iCOM™Installer/User Guide
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this
manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.Vertiv.com/en-us/support/ for additional assistance.
The information contained in this document is subject to change without notice
and may not be suitable for all applications. While every precaution has been
taken to ensure the accuracy and completeness of this document, Vertiv
assumes no responsibility and disclaims all liability for damages resulting from
use of this information or for any errors or omissions. Refer to other local
practices or building codes as applicable for the correct methods, tools, and
materials to be used in performing procedures not specifically described in this
document.
The products covered by this instruction manual are manufactured and/or sold
by Vertiv. This document is the property of Vertiv and contains confidential
and proprietary information owned by Vertiv. Any copying, use or disclosure of
it without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of
the respective companies. Any questions regarding usage of trademark names
should be directed to the original manufacturer.

TABLE OF CONTENTS
1 Getting Started with iCOM™ 1
1.1 Touchscreen Display and User Interface 1
1.2 Touchscreen Status Dial 3
1.2.1 Dial Background Color Status Indication 5
1.3 Control Header 6
1.3.1 Powering On iCOM and Logging In/Unlocking Controls 6
1.3.2 Powering On the Thermal Management Unit 7
1.3.3 Powering Off the Thermal Management Unit 8
1.3.4 Logging Out 8
1.3.5 Calibrating the Touchscreen 8
1.3.6 Setting the Date and Time 9
1.3.7 Searching 9
1.4 Using Context Sensitive Help 9
1.5 About iCOM Version 10
1.6 Accessing the User, Service. and Advanced Menus 10
1.7 User Menu 10
1.7.1 User menu options 10
1.8 Service Menu 11
1.8.1 Service Menu Options 11
2 User Operation 13
2.1 Viewing and Editing Setpoints for the Cooling Unit 13
2.1.1 Editing Temperature Setpoints 13
2.2 Viewing Unit Alarms 14
2.2.1 To View Alarms 14
2.2.2 Silencing an Audible Alarm 15
2.2.3 Acknowledging Alarms 15
2.3 Viewing the Event Log 16
2.4 Viewing Sensor Data 17
2.5 Managing Run Hours for a Component 17
2.5.1 Setting Run Hours to Zero 17
2.6 Viewing Teamwork, Standby, andCascade Status 18
2.6.1 To View the Teamwork Details 18
3 Service Operation 19
3.1 Editing Setpoints for the Cooling Unit 19
3.1.1 Setpoints Options 19
3.1.2 Configuring Temperature Setpoints 19
3.1.3 Temperature Control –TemperatureSetpointsandCooling Operation 21
3.1.4 Compressor Control by Cooling Requirement 23
i

3.1.5 Setting Temperature Compensation 27
3.1.6 Configuring High/Low Limit Setpoints 28
3.1.7 Configuring Fan Setpoints 28
3.1.8 Manual Fan Speed Control 30
3.1.9 Automatic Fan Speed Control 31
3.2 Scheduling Condenser and Cooling Unit Tasks 31
3.2.1 Scheduling Condenser Low-noise Operation 32
3.2.2 Scheduling Condenser Fan Reversal 33
3.2.3 Scheduling Sleep Times for Thermal Management Units 33
3.3 Setting General Thermal Management Unit Options 34
3.3.1 Setting Miscellaneous Options 34
3.3.2 Configuring Quick Start 35
3.3.3 Automatic Restart after Power Failure 37
3.3.4 Setting Fan Options 37
3.3.5 Setting Compressor Options 39
3.3.6 Setting Q15 Options 40
4 Managing Events: Alarms,WarningsandMessages 43
4.1 Event Properties 43
4.1.1 To Open the Panel 43
4.1.2 Alarms & Events Panel Fields 43
4.2 Enabling Events and EditingEventSettings 44
4.3 Selecting Event Type and SettingAlarm/WarningNotification 45
4.3.1 To Select Event Type and Notification 45
4.4 Enabling the Audible Alarm Notification 52
4.5 Remote Alarm Device and Customer Input Events 52
4.5.1 Setting Up Customer Input Events 53
5 Unit to Unit Networking 57
5.1 Preparing for U2U Group Set Up 57
5.2 Configuring U2U Network Settings 59
5.2.1 To Configure Unit to Unit Networking 59
5.2.2 U2U Display and Control Board Settings 59
5.2.3 Troubleshooting Network Settings Issues 61
5.2.4 Modifying U2U Network Settings 61
6 Teamwork, Standby and RotationforCoolingUnits 63
6.1 Continuous Control with Virtual Master 63
6.2 Teamwork Modes 63
6.2.1 To Set Up Team Work 63
6.2.2 No Teamwork—Multiple Zones in One Room 65
6.2.3 Teamwork Mode 1—Parallel Operation 66
6.2.4 Teamwork Mode 2—Independent Operation 66
Vertiv™ | Liebert® iCOM™Installer/User Guide
ii

6.2.5 Teamwork Mode3—Optimized Aisle Operation 66
6.3 Assigning Cooling Units to Standby (Lead/Lag) 67
6.3.1 To Set up Lead/Lag Operation 68
6.4 Setting a Rotation Schedule 68
6.4.1 Unit Rotation Options 69
6.4.2 Manually Rotating the Operating and Standby Units 69
7 Configuring Economizer Operation 71
7.1 Fluid Economizers 71
7.1.1 FluidEconomizer Control Options 71
7.1.2 Overriding Fluid Economizer Operation 72
7.1.3 Setting Up Fluid Economizer Operation 72
7.1.4 Temperature Control with a Fluid Economizer 74
7.1.5 Viewing Fluid Economizer Statuses 77
8 External Monitoring andBuilding managementSystems 79
8.1 BMS and IntelliSlot Settings 79
8.1.1 Configuring BMS Communication with IntelliSlot Card 80
8.1.2 Setting BMS Control Settings 80
8.1.3 Setting BMS Backup Setpoints 81
9 Configuring Auxiliary Devices 83
9.1 Power Monitoring 83
9.1.1 To Set Up Power Monitoring 83
9.2 Fluid Temperature Monitoring 84
9.2.1 Fluid Sensor Options 84
9.3 Configuring Analog Input Devices 84
9.4 Wired Remote Sensors 86
9.4.1 Wired Remote Sensor—Set Up Options 86
9.4.2 Wired Remote Sensor—Sensor Property Options 87
9.5 Supply Sensors 88
10 Administering Firmware, Settings and Security 89
10.1 iCOM Firmware Upgrades 89
10.1.1 Compatibility with Earlier Versions of iCOM 89
10.1.2 Updating iCOM Display Firmware 89
10.1.3 Updating iCOM Control Board Firmware 89
10.2 Backing Up, Importing, Exporting, and Restoring Display Settings 91
10.2.1 To Back Up or Restore 91
10.2.2 Resetting Display Settings to Defaults 91
10.3 Managing Access Permission and Passwords 92
10.4 Backing Up and Restoring Control Board Settings 92
10.4.1 Control Board Back Up and Restore Options 93
10.5 Managing Access Permission and Passwords 93
iii

10.6 Configuring with the Start Up Wizard 94
10.6.1 To Update System Information Using the Wizard 94
11 Performing Diagnostics 95
11.1 Cooling Unit Status LED 95
11.2 Enabling Manual Mode for Diagnostics 95
11.2.1 Disabling Diagnostics Manual Mode 96
11.3 Diagnosing Evaporator Fan Issues 96
11.3.1 Diagnostics—Evaporator Fan Options 96
11.4 Diagnosing Compressor Circuit Issues 97
11.4.1 Diagnostics—Compressor Circuit Options 97
11.4.2 Resetting High Pressure Alarm Code 98
11.4.3 Resetting Low Pressure Alarm Code 98
11.4.4 Resetting High-temperature Alarm Counter 98
11.5 Diagnosing Electronic Expansion Valve Issues 98
11.5.1 Diagnostics—Electronic Expansion Valve Options 99
11.5.2 Resetting Electronic Expansive Valve Battery Failure Counter 100
11.6 Diagnosing EconoPhase Issues 100
11.6.1 Diagnostics—EconoPhase Options 100
11.7 Diagnosing Digital Output Issues 101
11.7.1 Diagnostics—Digital Output Options 101
11.8 Diagnosing Analog Output Issues 101
11.8.1 Diagnostics—Analog Output Options 101
11.9 Diagnosing Customer Input Issues 101
11.9.1 Diagnostics—Customer Input Options 101
12 Customizing Your iCOM Display 103
12.1 Setting General Display Properties 103
12.1.1 Unit Display Options 103
12.2 Customizing Main Display Views 104
12.2.1 Moving Content 104
12.2.2 Resizing Content 104
12.2.3 Adding and Adjusting Content 105
12.2.4 Removing Content 106
12.3 Customizing Parameter and Field Labels 106
12.3.1 Exporting, Importing, and Customizing Labels Using a Text Editor 108
13 Hardware Installation 110
13.1 Installing Wired Remote Sensors 110
13.1.1 Setting DIP Switches and Labeling 2T Sensors 110
13.1.2 Terminating the Last Sensor on the CANbus Link 112
13.1.3 Installing 2T Sensors in the Racks to Monitor 115
13.1.4 Connect the CANbus Cable and Ground 117
Vertiv™ | Liebert® iCOM™Installer/User Guide
iv

13.2 Installing a Fluid Temperature Sensor 119
13.3 Installing Supply Control Sensors 121
13.3.1 Installing the Supply Air Temperature Sensor 121
13.3.2 Installing Aggregated Supply Air Temperature Sensors 122
13.4 Installing Analog Input Devices 125
13.5 Installing the Unit to Unit Network 126
13.5.1 Required Network Equipment 126
13.5.2 Planning Wiring Runs 126
13.5.3 U2U Wiring connection 127
13.5.4 Wiring Cooling Units without Wall Mount Displays 128
13.5.5 Wiring Cooling Units with Wall Mount Displays 130
Appendices 131
Appendix A: Technical Support and Contacts 131
Appendix B: Setpoints and Alarm Settings by Line ID 133
v

Vertiv™ | Liebert® iCOM™Installer/User Guide
vi
This page intentionally left blank

1 GETTING STARTED WITH iCOM™
The Liebert® iCOM offers the highest capability for unit control, communication, and monitoring of Liebert® Thermal
Management units. It is available factory installed on new units and assemblies or may be retrofitted in existing units.
NOTE: Your Liebert® DSE™ Packaged Solution does not offer humidification or dehumidification functions. Please
disregard those settings/fields when mentioned in this guide or displayed on the iCOM controller.
1.1 Touchscreen Display and User Interface
The Liebert® iCOM touchscreen and user interface speeds set up and installation and simplifies control of Liebert® thermal-
management units, literally putting cooling-system monitoring and management at your fingertips.
•The resistive touchscreen is used with a firm touch, or consider using a stylus when interacting with the
touchscreen.
•User and service menus are password protected to prevent unauthorized changes to cooling-unit operation.
•The touchscreen is back-lit and auto-dims after a period on non-use, then turns off. Touch the screen to
illuminate the main screen.
•iCOM ships with default settings for efficient and effective operation of most cooling-units and is easily
configured to meet any need.
•iCOM menus and displays are based on the options installed on the cooling units that it monitors and manages.
1 Getting Started with iCOM™ 1

Figure 1.1 iCOM Main Display
Item Description
1 Alarms present. Displays the number of active alarms.
2 Menu icon. When unlocked, displays a menu for user or service options depending on which icon is selected.
3
User icon. When selected, the user options are available on the main display and menu.
NOTE: You must unlock the display with the User PIN to access the menu and options.
See Powering On iCOM and Logging In/Unlocking Controls on page6.
4
Service icon. When selected, the service options are available on the main display and menu.
NOTE: You must unlock the display with the Service PIN to access the menu and options.
See Powering On iCOM and Logging In/Unlocking Controls on page6.
5
Advanced icon. When selected, the advanced options are available on the main display and menu.
NOTE: You must unlock the display with the Service PIN to access the menu and read-only options.
See Powering On iCOM and Logging In/Unlocking Controls on page6.
6 Cooling-unit parameters. Status display of selected system parameter settings. See Adding and Adjusting Content on page105
7 Unit Identification. You may customize the unit name up to 6 characters/numbers.
8 Search icon. Open the keyboard to search for controls and setting locations. See Searching on page9.
9 Date/Time.
10
Lock/Unlock icon. Indicates whether or not the user and service options are accessible.
•Locked icon: Display is read-only
•Unlocked icon: User or service is logged-in and options are accessible.
See Powering On iCOM and Logging In/Unlocking Controls on page6.
Table 1.1 Main Display controls and options
Vertiv™ | Liebert® iCOM™Installer/User Guide
2

Item Description
11 Secondary-content panel. When accessing settings/configuration via the menus, the settings display in the right, secondary panel.
12 Summary of current unit function. You can customize to show fan speed, cooling, percentages from any installed device, and any physical
(sensor) values.
13 Status Dial. Circular display of setpoints and environmental conditions of the unit. See Touchscreen Status Dial below.
14 Teamwork-mode icon. In a panel with Status content, the Teamwork Mode icon indicates the mode selected. For details and descriptions of the
teamwork controls, see Teamwork Modes on page63.
15 Control header. Controls to access the user and service menus. See Control Header on page6.
16 Status Header. Displays the alarm status, unit identification, and the current date and time.
Table 1.1 Main Display controls and options (continued)
1.2 Touchscreen Status Dial
The dial in the primary control panel displays read-only control sensors, setpoints, and environmental conditions for unit
status at a glance. See Figure 1.2 on the next page.
The center of the dial displays sensor readings and changes color according to alarm thresholds as the readings rise and
fall, see Dial Background Color Status Indication on page5.
Touching the center of the dial cycles through a set of sensor settings, and you can select the readings displayed, see
Adding and Adjusting Content on page105.
1 Getting Started with iCOM™ 3

Figure 1.2 Dial Sections
Item Description
1
Control sensor and its setpoint. The sensors and setpoints displayed depend on the configuration of your unit.
You may see only temperature-control, or if the unit includes humidity control, that displays on the dial as well.
If the sensor selected for fan control is the same as that selected for temperature control, the dial displays the fan-control sensor and setpoint, as
shown in Figure 1.2 above.
2 Single or multiple sensor readings. Cycle through readings by touching the displayed reading.
Table 1.2
Vertiv™ | Liebert® iCOM™Installer/User Guide
4

1.2.1 Dial Background Color Status Indication
The background color of the dial indicates whether or not the unit is powered on, and it also responds to threshold settings
of the control-sensor reading, see Figure 1.3 below. Table 1.3 below describes the background color displayed if the
selected sensor reading has threshold limits set.
Figure 1.3 Dial Background Colors
Item Description
1 Sensor reading is within threshold limits.
2 Unit is powered off.
3 Sensor reading is above threshold limit or the unit is in an alarm condition.
4 Sensor reading is below threshold limit
Sensor/Value Selected Threshold Limit Background Color
Return Temp
None Blue
High return temperature Red
Return Humidity
Low return humidity Blue
High return humidity Red
Dew Point
Low dew point Blue
High dew point Red
Supply Temp
Low supply temperature Blue
High supply temperature Red
Average Rack Temp
Low remote temperature Blue
High remote temperature Red
Max Rack Temp
Low remote temperature Blue
High remote temperature Red
Table 1.3 Background Color Displayed by Selected Value
and Threshold Limit
1 Getting Started with iCOM™ 5

Sensor/Value Selected Threshold Limit Background Color
Min Rack Temp
Low remote temperature Blue
High remote temperature Red
Static Pressure
Low static pressure Blue
High static pressure Red
Outdoor Temp None Green
Outdoor Humidity None Green
Table 1.3 Background Color Displayed by Selected Value
and Threshold Limit (continued)
1.3 Control Header
The control header contains the controls to access the user and service settings. The display is locked when started initially
and when restarted after a period of inactivity.
1.3.1 Powering On iCOM and Logging In/Unlocking Controls
iCOM is powered on when power is switched on at the cooling unit’s disconnect switch and you activate the display by
touching it.
iCOM is locked when started and also locks after a period of inactivity to prevent unauthorized changes. A four digit
password is required to access the user and service menus and options, and the advance menu displays as read only when
logged in at the service level.
NOTE: The factory default inactivity period is one minute. To change the inactivity period, see Setting General Display
Properties on page103.
NOTE: The factory-default passord for user and service login are provided. We recommend you change passwords as
necessary to prevent unauthorized changes. See Managing Access Permission and Passwords on page93.
•Default User password: 1490
•Default Service password: 5010
To unlock the controls:
1. On the header, touch . The keypad opens.
2. Touch the numbers/characters for your password, then touch .
Depending on the password entered and your level of access, the User and/or Service options, and view only
access to the Advanced menu are accessible. See Accessing the User, Service. and Advanced Menus on
page10.
Vertiv™ | Liebert® iCOM™Installer/User Guide
6

1.3.2 Powering On the Thermal Management Unit
NOTE: Depending on the operating state, there are start/stop priority switches that may prevent the cooling unit from
operating even though power to the unit is switched on and you have turned it on via iCOM.
The cooling unit operates only when all switches are closed. For example, even though you have turned on the unit
through iCOM, if the BMS remote monitoring system is sending a command to turn off the unit, the cooling unit
remains off.
NOTE: You must be logged in to access the menu options. See Powering On iCOM and Logging In/Unlocking Controls
on the previous page.
To power-on the unit:
1. Touch , then >Turn Unit On. The TURN UNIT ON dialog opens.
2. Touch Turn Unit On. The cooling unit starts and the operating status is displayed as shown in Figure 1.4 below.
Figure 1.4 Unit Status on iCOM Display
Item Description
1 Current status of the unit. See Table 1.4 below.
2 Teamwork icon. See Viewing Teamwork, Standby, andCascade Status on page18.
Unit Status
Text Description
ALARM OFF An alarm forced the unit to turn off. See Viewing Unit Alarms on page14.
MANUAL Controlled by a service technician. See Enabling Manual Mode for Diagnostics on page95.
DISPLAY OFF Unit is turned Off at the iCOM display. See Powering On the Thermal Management Unit above.
ALARM
STANDBY In stand-by because of an active alarm on the unit. See Viewing Unit Alarms on page14.
Table 1.4 Cooling Unit Statuses Displayed
1 Getting Started with iCOM™ 7

Unit Status
Text Description
STANDBY In standby because of service-menu setting. See Assigning Cooling Units to Standby (Lead/Lag) on page67.
TIMER OFF Scheduled on a timer and is in “sleep” mode waiting for the next start interval. See Scheduling Condenser and Cooling Unit Tasks on
page31.
UNIT ON Operating normally without alarms or warnings.
WARNING ON Active warning, but still operating. See Viewing Unit Alarms on page14.
ALARM ON Active alarm, but still operating. See Viewing Unit Alarms on page14.
TIMER Scheduled on a timer to operate, and is in operating mode. See Scheduling Condenser and Cooling Unit Tasks on page31.
REMOTE OFF
Turned-off by remote shutdown terminal.
Occurs when a normally-closed set of 24V contacts opens. The Remote On/Off and Display On/Off switches are in series, and the cooling
unit will only turn-on if both switches are on/closed. If one is off/open, the unit turns off.
MONITORING
OFF Turned-off by remote monitoring system. Check the remote monitoring device or call Vertiv™ technical support for assistance.
BACK-DRAFT Unit is non-operational, but EC fan is operating as a back draft damper.
RESTART
DELAY Not yet operational after a power cycle because the restart-delay timer is active.
Table 1.4 Cooling Unit Statuses Displayed (continued)
1.3.3 Powering Off the Thermal Management Unit
NOTE: You must be logged in to access the menu options. See Powering On iCOM and Logging In/Unlocking Controls
on page6.
1. Touch , then >Turn Unit Off. The TURN UNIT OFF panel opens.
2. Touch Turn Unit Off. The unit begins a power-off countdown then powers off.
1.3.4 Logging Out
Log out occurs automatically when the display back light turns off for inactivity.
NOTE: The factory-default inactivity period is one minute. To change the inactivity period, see Setting General Display
Properties on page103
•To log-out manually, touch the lock icon. The icon indicates “locked.”
1.3.5 Calibrating the Touchscreen
Use a firm touch or a stylus for the best response. To improve interaction with quicker and more accurate touch response,
calibrate the touchscreen.
1. On the User menu, touch Display Options >Display Properties.
2. On the UNIT DISPLAY panel, touch Calibrate Screen and follow the prompts to calibrate.
•If you cannot access the calibration because of screen response, continue with step 3.
3. At the cooling unit disconnect switch, power off the unit and then back on.
4. Touch your finger to the screen and hold it there while the display boots.
Vertiv™ | Liebert® iCOM™Installer/User Guide
8

5. When the LED begins flashing, remove your finger. Cross hairs appear in each corner and in the center of the
display.
6. Touch the center of each cross hair ONCE ONLY. (Touching more than once interrupts the calibration and you
must start over at step 3.)
Cross hairs disappear and the display reboots when calibration is complete.
1.3.6 Setting the Date and Time
The correct date and time is critical for warnings, alarms, and scheduling.
1. Touch , then > Display Options >Display Properties >Date &
Time.
2. Touch the date field, use the arrows to select the date, and touch OK.
– or –
Touch the time field, use the arrows to set the time, and touch OK.
3. Select the date and time format if necessary.
4. Touch Save.
1.3.7 Searching
When logged in, you can use the display search to find the location of settings options based on a term, service code, or
parameter. You can also search by the line ID used in the iCOM before the touchscreen model. For a listing of the line IDs,
see Setpoints and Alarm Settings by Line ID on page133.
NOTE: You must be logged in to access the display search. See Powering On iCOM and Logging In/Unlocking
Controls on page6.
1. In the control header, touch the search field. The keyboard opens.
2. Type the term and touch . A list of locations that contain the searched term opens.
3. To go to a listed location, touch an item, then touch Go. The panel for the selected location opens.
– or –
To view the service codes and parameter entries related to the searched term, touch View Parameter Directory
Entries (the number of related entries is included in the option).
The Parameter Directory opens. You may further refine the search in the directory.
1.4 Using Context Sensitive Help
Touching the Help icon, , on the right-hand side of the display opens the Help drawer with information about the
panel or dialog currently on the display.
You can use search and the topic index to find further information.
To close the Help drawer, touch the close arrow, .
1 Getting Started with iCOM™ 9

1.5 About iCOM Version
The version, build, and other firmware information for the iCOM display board may be helpful when servicing or
troubleshooting. To locate the firmware version of the iCOM control board, see Updating iCOM Control Board Firmware on
page89.
•Touch , then > About. The ABOUT panel opens.
1.6 Accessing the User, Service. and Advanced Menus
iCOM operating functions that monitor and control a cooling unit are accessed via the User and Service menus.
NOTE: You must be logged in to access the menu options. See Powering On iCOM and Logging In/Unlocking Controls
on page6.
1. To access a menu, touch the icon for the menu you want, , or , in the control header, see
Control Header on page6. The orange bar appears below the menu name when selected indicating that this is
the menu content that will be displayed.
2. Touch the menu icon, . The menu opens.
1.7 User Menu
The user menu lets you view system and unit statuses and edit some setpoints.
1.7.1 User menu options
Setpoints
Opens the SETPOINTS panel. See Viewing and Editing Setpoints for the Cooling Unit on page13.
Active Alarms
Opens the ALARMS panel. See Viewing Unit Alarms on page14.
Event Log
Opens the EVENT LOG panel. See Viewing the Event Log on page16.
Sensor Data
Opens the SENSOR DATA panel. See Viewing Sensor Data on page17.
Display Options
Opens the Display Options menu:
•Customize Layout: See Customizing Main Display Views on page104.
•Custom Labels: See Customizing Parameter and Field Labels on page106.
•Date & Time: See Setting the Date and Time on the previous page.
Vertiv™ | Liebert® iCOM™Installer/User Guide
10

Total Run Hours
Opens the RUN HOURS panel. See Managing Run Hours for a Component on page17.
EconoPhase
Opens the ECONOPHASE - PUMP MODE panel.
About
Opens the ABOUT panel. See About iCOM Version on the previous page.
Turn Unit On/Off
Depending on unit’s status, open the TURN UNIT ON or TURN UNIT OFF dialog. See Powering On the Thermal
Management Unit on page7, or Powering Off the Thermal Management Unit on page8.
1.8 Service Menu
The service menu lets you view and edit setpoints and perform many other functions.
1.8.1 Service Menu Options
Setpoints
Opens the SETPOINTS panel. See Editing Setpoints for the Cooling Unit on page19.
Diagnostic/Service
Opens the Diagnostic/Service menu:
•Diagnostics: See Performing Diagnostics on page95.
•EconoPhase View: Opens the ECONOPHASE - PUMP MODE panel.
•Technical Support: Contact information for the cooling unit and iCOM display.
Alarm/Event Setup
Opens the ALARMS & EVENTS panel. See Managing Events: Alarms,WarningsandMessages on page43.
BMS & Teamwork
Opens the BMS & Teamwork menu:
•U2U Setup—See Configuring U2U Network Settings on page59.
•Teamwork/Standby—See Teamwork, Standby and RotationforCoolingUnits on page63.
•BMS Setup—See BMS and IntelliSlot Settings on page79.
Scheduler
Opens the SCHEDULER panel. See Scheduling Condenser and Cooling Unit Tasks on page31.
1 Getting Started with iCOM™ 11

Options Setup
Opens the OPTIONS SETUP panel. See Setting General Thermal Management Unit Options on page34.
Auxiliary Device Setup
Opens the Auxiliary Device Setup menu:
•Sensors: See Wired Remote Sensors on page86.
•Analog Input: See Configuring Analog Input Devices on page84.
•Modbus Devices
•CapCom
Backup & Security
Opens the Backup & Security menu:
•Display Backup and Restore: See Backing Up, Importing, Exporting, and Restoring Display Settings on
page91.
•Control Backup and Restore: See Backing Up and Restoring Control Board Settings on page92.
•Display Upgrade: See Updating iCOM Display Firmware on page89.
•Control Upgrade: See Updating iCOM Control Board Firmware on page89.
•Manage Permissions: See Managing Access Permission and Passwords on page93.
Turn Unit On/Off
Depending on unit’s status, open the TURN UNIT ON or TURN UNIT OFF dialog. See Powering On the Thermal
Management Unit on page7, or Powering Off the Thermal Management Unit on page8.
Vertiv™ | Liebert® iCOM™Installer/User Guide
12
Table of contents
Popular Thermostat manuals by other brands

Celect
Celect DRF3 instruction manual

Honeywell Home
Honeywell Home RTH7600 user manual

Honeywell
Honeywell DG115EZIAQ - TrueIAQ Digital IAQ Control owner's guide

Tech Controllers
Tech Controllers WIFI 8S MINI user manual

Herschel
Herschel T-MKS Installation and operating instructions

EPH Controls
EPH Controls RFRA operating instructions