4| Installation and Operation Guide
Mounting
The ADAM-6050 is supplied with a mounting bracket that can be can be
installed onto any selected surface, or a DIN rail adapter, that allows it to be
mounted onto any compatible DIN rail.
Wiring and Connections
Power Wiring (power supply not included)
The ADAM-6050 is designed for a standard industrial unregulated 24 VDC
power supply, but accepts any power unit that supplies with the range of +10 -
+30 VDC. Screw terminals +Vs and GND are for power supply wiring (wires
should be at least 2 mm); +Vs (R) is for red and GND (B) is for black wire.
I/O Wiring
The ADAM-6050 uses a plug-in screw terminal block for the interface between
the I/O modules and field devices.
Connection to the Valerus System
In order to find the ADAM-6050 on the network and assign it an IP address,
download the ADAM.NET Utility software that is on the CD provided with the
unit. Once the Utility is downloaded, a shortcut to the Utility will be placed on
the PC desktop.
Notes
Installation of ADAM.NET requires that .NET Framework 1.1 or later is
installed.
The utility searches for the ADAM unit on the LAN and might not be able to
find it if it’s behind a router or a wireless device. If this happens, plug the unit
to the same switch the PC is on for the configuration steps.
Double click the shortcut icon. The ADAM-6050 (Advantech) GUI displays.
Select ADAM5000 TCP_6000 from the Module list on the left. The following
screen displays.
.