WarmFlow Air Source A-Series User manual

High Efficiency
Variable Speed
Air Source Heat Pumps
Models covered by this manual:
A-Series
Air Source AS01 AS02 AS03
Incorporating: User Instructions
Installation Instructions
Service Instructions
Guarantee Terms & Conditions

INSTALLATION, COMMISSIONING & SERVICING
This appliance must be installed as described herein and the installation commissioned by
competent persons as instructed. The Installation/Commissioning Certificate supplied with the
product must be completed and returned to the manufacturer with proof of purchase (e.g.
receipts / invoices).
This appliance must be serviced annually by competent persons, the Service Record completed
on each occasion and proof of servicing (e.g. receipts / invoices) retained.
The complete guarantee policy statement is included in Section 4.
FAILURE TO COMMISSION, REGISTER AND ANNUALLY SERVICE THIS
PRODUCT WILL INVALIDATE ALL GUARANTEES
TECHNICAL, SPARES & GUARANTEE CLAIMS
For technical advice about the installation, commissioning, servicing or use of this appliance,
please contact the Warmflow Customer Care Centre by post, phone, fax or email at the
addresses below. Please also refer to our website.
In the unlikely event that replacement components might be required within the guarantee
period, please notify the Customer Care Centre in writing, by post, fax or email, stating the
nature of the fault and the part number of the replacement components required.
Warmflow Customer Care Centre
Warmflow Engineering
Lissue Industrial Estate
Moira Road
Lisburn
BT28 2RF
Northern Ireland
Telephone
United Kingdom: 028 9262 1515
Republic of Ireland: 048 9262 1515
Facsimile
United Kingdom: 028 9262 0869
Republic of Ireland: 048 9262 0869
Email
Website
www.warmflow.co.uk

Page 1
CONTENTS
Contents ......................................................................................................................................................................1
1USER INSTRUCTIONS........................................................................................................................................3
1.1 Intended Use.................................................................................................................................................................3
1.2 Compliances .................................................................................................................................................................3
1.3 Basic Operation.............................................................................................................................................................3
1.4 Product Data .................................................................................................................................................................4
1.4.1 Starting Current.....................................................................................................................................6
1.5 Construction..................................................................................................................................................................7
1.6 Supplied Components...................................................................................................................................................7
1.7 Storage / Transport .......................................................................................................................................................8
2USER INTERFACE..............................................................................................................................................9
2.1 Home Screen Icons.......................................................................................................................................................9
3AIR SOURCE HEAT PUMP INSTALLATION ...................................................................................................28
3.1 General .......................................................................................................................................................................28
3.2 Access.........................................................................................................................................................................30
3.3 Unpacking...................................................................................................................................................................31
3.4 Heating Circuit Connection..........................................................................................................................................31
3.4.1 Heating Medium..................................................................................................................................31
3.4.2 Heating Connections to the Heat Pump .............................................................................................31
3.4.3 Heating Circuit and Integrated Circulator............................................................................................31
3.4.4 Bypass / Open Zones .........................................................................................................................31
3.4.5 Freeze Protection................................................................................................................................32
3.4.6 Heating Circuit Line Components.......................................................................................................32
3.5 Defrosting....................................................................................................................................................................34
3.6 Air Vent .......................................................................................................................................................................34
3.7 Buffer tank...................................................................................................................................................................34
3.8 Bypass Valve...............................................................................................................................................................34
3.9 3-Port Motorised Valve................................................................................................................................................34
3.10 Electrical Installation....................................................................................................................................................35
3.10.1 Incoming Supply .................................................................................................................................35
3.10.2 Digital Inputs .......................................................................................................................................36
3.10.3 Digital Outputs ....................................................................................................................................37
3.10.4 Temperature Sensors.........................................................................................................................38
3.10.5 User Interface (Controller) ..................................................................................................................39
3.11 Parameter List.............................................................................................................................................................40
3.12 Commissioning............................................................................................................................................................44
3.12.1 Recorded Details ................................................................................................................................44
3.12.2 Testing Flow Rate...............................................................................................................................44
3.12.3 Weather Compensation Mode............................................................................................................44
3.12.4 DHW Cylinder Heat Up Test...............................................................................................................45
3.12.5 Sign Off...............................................................................................................................................45
3.13 System Hand Over......................................................................................................................................................46
3.14 Servicing .....................................................................................................................................................................46
3.14.1 Servicing Schedule.............................................................................................................................46
3.15 Alarms and Troubleshooting .......................................................................................................................................47
3.16 Alarms.........................................................................................................................................................................47

Page 2
3.17 Troubleshooting...........................................................................................................................................................52
4YOUR GUARANTEES, TERMS & CONDITIONS.............................................................................................53
4.1 Period of Guarantee....................................................................................................................................................53
4.2 Warmflow’s Obligations...............................................................................................................................................53
4.3 Your Obligations..........................................................................................................................................................53
4.4 Exclusions of Guarantee .............................................................................................................................................54
4.4.1 Repairs................................................................................................................................................54
4.4.2 Other property.....................................................................................................................................54
4.4.3 General ...............................................................................................................................................54
5End-of-Life Information....................................................................................................................................56
5.1 Safety Risks ................................................................................................................................................................56
5.2 Disassembly of the Product.........................................................................................................................................56
6APPLIANCE SERVICE RECORDS...................................................................................................................61

Page 3
1 USER INSTRUCTIONS
1.1 Intended Use
The Warmflow Air Source Heat Pump units are intended for the production of hot water for
space heating and sanitary water. The units can be used to provide heating and domestic hot
water (DHW) via underfloor heating circuits, radiators and approved hot water cylinders. The
units are designed to extract heat from the air.
1.2 Compliances
The Warmflow AS01, AS02 and AS03 air source heat pump units are Microgeneration
Certification Scheme (MCS) approved and CE marked. They are approved on the Renewable
Heat Incentive Eligibility list and can be found on both the Product Characteristics Database
(PCDB) as well as the Home-heating Appliance Register of Performance (HARP) database. As
such the units comply with the following directives and are tested to the following standards:
MCS 007 Issue 3.0 - Product Certification Scheme Requirements: Heat Pumps.
2006/95/EC - Low Voltage Directive.
2004/108/EC - Electromagnetic Compatibility Directive.
97/23/EC - Pressure Equipment Directive.
EN14511 - Air conditioners, liquid chilling packages and heat pumps with electrically
driven compressors for space heating and cooling.
EN14825 - Air conditioners, liquid chilling packages and heat pumps, with electrically
driven compressors, for space heating and cooling. Testing and rating at part load
conditions and calculation of seasonal performance.
EN 60335-1 - Household and similar electrical appliances. Safety. General requirements.
EN 60335-2-40 - Household and similar electrical appliances. Safety. Particular
requirements for electrical heat pumps, air-conditioners and dehumidifiers.
EN 61000 - Electromagnetic compatibility (EMC). Limits.
EN 378 - Refrigerating systems and heat pumps. Safety and environmental
requirements.
ENV 12102 - Air conditioners, liquid chilling packages, heat pumps and dehumidifiers
with electrically driven compressors for space heating and cooling. Measurement of
airborne noise. Determination of the sound power level.
1.3 Basic Operation
Heat flows from an area of higher temperature to an area of lower temperature. In much the
same way that a water pump, pumps water from a low level to a higher level, a heat pump
pumps heat from a source at a low temperature to a source at a higher temperature. The
benefit of this is that natural sources such as the air and ground, which are at relatively low
temperatures, can be used to heat buildings at a higher temperature. In order to do this the
heat pump uses a relatively small amount of electrical energy. The proportion of electrical
energy used to do this is much smaller than the heat power delivered to the building. The ratio
of the heat power delivered to the electrical energy used determines the efficiency of the heat
pump and is commonly known as the coefficient of performance (COP).

Page 4
Heat is extracted from the air by blowing air through a finned radiator, known as the evaporator,
with a fan. The extracted energy from the air is transferred into the refrigerant which circulates
around the evaporator. The heat pump then converts this low grade heat to a high grade by
compressing the refrigerant using the compressor. The compression of the refrigerant
increases the pressure and the temperature. This high grade heat is then transferred to the
heating system via another heat exchanger known as the condenser. The heat can now be
used to provide space heating and DHW. The pressure of the refrigerant is then released
through a throttling valve known as the expansion valve which also causes the temperature to
drop and allows the cycle to start over again.
1.4 Product Data Table 1 Product data
Product Data
AS01
AS02
AS03
Dimensions
(mm)
Width
1055
980
990
Depth
490
465
440
Height
790
910
1320
Weight (kg)
100
110
165
Electrical Supply
230V Single Phase
@50Hz
230V Single Phase
@50Hz
230V Single Phase
@50Hz
Maximum Current (Amps)
9
18+
27
Nominal Sound Level (dBA)*
54
54
58
Performance
COP @ A7W35
4.42
4.84
4.49
COP @ A2W30
3.47
3.85
3.79
COP @ A7W27
6.50
5.10
5.07
COP @ A12W30
6.64
7.09
6.90
COP @ A-7W34
2.66
2.70
2.71
COP @ A7W55
2.97
2.52
2.44
COP @ A-10W55
1.44
1.68
1.58
Heat Output Range
2 - 6kW
3 - 11kW
5 - 17kW
ErP Efficiency Class
(35°C / 55°C)^
A++ / A+
A++ / A+
A++ / A++
Operating Temp.
(◦C)
Ambient Air, min/max
-15/43
-20/52
-20/52
Heating Flow, min/max
20/60
20/60
20/60
Flow Rates (l/m)
Heating, min/max
10/20
16/30
28/60
Refrigerant
Type
R410A
R410A
R410A
Charge (kg)
1.70
2.40
3.20
Connections
Heating Flow & Return
1” female BSP
1” female BSP
1 ¼” female BSP
*Nominal Sound Levels have been independently tested in accordance with EN 12102.
^ ErP ratings have been independently tested in accordance with EN 14825.
+This unit features an integrated immersion heater which if used requires an additional 14Amp supply.

Page 5
Table 2 Product information
Model
AS01
AS02
AS03
Air-to-water heat pump
Yes
Water-to-water heat pump
No
Brine-to-water heat pump
No
Low-temperature heat pump
No
Equipped with a supplementary heater
No
Heat pump combination heater
No
Symbol
Value
Unit
Rated heat output
Prated
6
11
17
kW
Declared Capacity of heating for part load at indoor temp. 20°C and outdoor temp., Tj
Tj= -7°C
Pdh
2.8
7.0
9.8
kW
Tj= 2°C
Pdh
2.0
4.4
6.0
kW
Tj= 7°C
Pdh
2.6
3.7
6.2
kW
Tj= 12°C
Pdh
3.1
4.5
7.6
kW
Tj= bivalent temperature
Pdh
2.8
7.0
9.8
kW
Tj= operation limit temperature
Pdh
2.8
6.2
8.9
kW
Bivalent temperature
Tbiv
-7
-7
-7
°C
Cycling interval capacity for heating
Pcych
-
-
-
kW
Degradation coefficient
Cdh
-
-
-
Seasonal Space Heating Energy Efficiency
ηs
113
122
128
%
Tj= -7°C
COPd
1.85
1.93
1.89
Tj= 2°C
COPd
2.59
2.84
3.15
Tj= 7°C
COPd
4.37
4.51
4.47
Tj= 12°C
COPd
6.64
7.09
6.90
Tj= bivalent temperature
COPd
1.44
1.93
1.89
Tj= operation limit temperature
COPd
1.85
1.68
1.58
Operation limit temperature
TOL
-10
-10
-10
°C
Cycling interval capacity for heating
COPcyc
-
-
-
Heating water operating limit temperature
WTOL
55
55
55
°C
Power consumption in modes other than active
Off mode
POFF
0.011
0.013
0.009
kW
Thermostat-off mode
PTO
0.011
0.000
0.000
kW
Standby mode
PSB
0.011
0.013
0.009
kW
Crankcase heater mode
PCK
0.045
0.000
0.000
kW
Other items
Capacity control
Variable
Sound power level indoors
LWA
54
54
58
dB
Annual energy consumption
QHE
2246
4890
6949
kWh
Rated air flow rate
-
3.3
5.2
7.6
m3/h

Page 6
Table 3 Product Fiche
Supplier
Warmflow
Warmflow
Warmflow
Model
AS01
AS02
AS03
Energy Efficiency Class
A++
A++
A++
Rated Heat Output (kW)
6
11
17
Seasonal Space Heating Energy Efficiency
159
153
157
Annual Energy Consumption, GCV (kWh)
1766
2648
6342
Sound Power Level, LWA (dB)
54
54
58
Rated Heat Output in Colder Climate (kW)
6
11
17
Seasonal Space Heating Energy Efficiency in Colder Climate
159
153
157
Annual Energy Consumption in Colder Climate, GCV (kWh)
2107
3159
7567
Rated Heat Output in Warmer Climate (kW)
8
11
17
Seasonal Space Heating Energy Efficiency in Warmer Climate
159
153
157
Annual Energy Consumption in Warmer Climate, GCV (kWh)
1142
1712
4101
1.4.1 Starting Current
The AS01, AS02 and AS03 air source heat pump units are all inverter driven. This means they
ramp up slowly and therefore do not require a large starting current which is required with fixed
speed units. In the majority of situations the starting current will be less than 1Amp. The
starting current will also always be below the rated current of the unit. Below is the typical
starting profile showing the compressor frequency (left side scale) and current draw (right side
scale) from off to typical running speed.
Figure 1 Starting Current

Page 7
1.5 Construction
The Warmflow air source heat pumps are housed in a powder-coated galvanised metal casing
complete with enclosure box in which a cable entry terminal is mounted.
Figure 2 Typical Construction
Upon delivery, it is important that the unit is unpacked carefully and checked for any sign of
damage. If something is missing or damaged please report it to Warmflow immediately. The
units are secured to the shipping pallet using screws which must be removed.
NOTE: For coastal areas or other areas subjected to higher levels of corrosion, units can
be supplied with a Blygold coating applied to the evaporator to help protect it. Please
contact Warmflow for more details.
1.6 Supplied Components
Together with the unit, a number of additional components are supplied to aid installation. The
following items are supplied with each unit:
1no. Y-strainer complete with 700μm Filter Gauze
2no. 1” flexible hoses (1¼” to 1” adapter supplied with AS03)
2no. 1” Male to Female Brass Elbows
2no. 1” Isolating Ball Valves
1no. DHW Cylinder Temperature Sensor
4no. Anti-Vibration Mounts
1no. Touchscreen Controller complete with wiring and wall mount
Upon delivery, it is important to check that all components are included. If something is missing
or damaged please report it to Warmflow immediately.
Fan
Feet Supports
Front Grill
Top Lid
Installer’s
Wiring Cover
Heating Flow
& Return
Connections

Page 8
1.7 Storage / Transport
The units come on a pallet (Dimensions of shipping sizes are shown below) and are secured to
the pallet using screws. If the units are to be stored prior to installation, they must be kept
indoors in storage conditions at a temperature of between 5°C and 60°C with a humidity level
between 10%RH and 80%RH in order to provide a non-condensing environment. The units
must not be stacked in storage or during transport. During transport the units must be kept in an
upright position and should never be allowed to tilt more than 45° during loading or unloading.
Table 4 Shipping Details
Product Data
AS01
AS02
AS03
Shipping
Dimensions
(mm)
Width
1070
1050
1290
Depth
510
500
530
Height
950
1060
1480
Shipping Weight (kg)
115
123
180

Page 9
2 USER INTERFACE
The appliance’s user control interface (see Figure 3) has been designed to maximise the ease
of use and efficiency of the heating system. The interface is a touchscreen with all interactions
being performed on the screen itself.
On powering the unit up, the following start up screen will be displayed. The screen displays
the firmware and software version which are installed on the controller. If the version number is
not shown, this means there is a communication fault and the screen will turn off after 15
seconds. Check the wiring connections between the controller and the unit if this occurs. On
first start up, the controller will give out a long beep indicating that it has been successfully set
up.
Figure 3 User Interface Start-Up Screen
2.1 Home Screen Icons
All interactions with the heat pump are via this user interface which should be located in a
suitable location in the property. The interface allows the modification of parameters such as
time clocks, temperature set points, heating & DHW functions, together with commissioning and
service settings. The home screen appears as shown in Figure 4.

Page 10
Figure 4 Screen Icons
There are a number of icons/buttons on the home screen as shown above. The meaning and
features of these are explained in the points below:
ON/OFF Button - Press this button to switch the unit from OFF to ON or vice versa.
When the unit is switched ON, the symbol on the button will be red and the screen will
appear in full colour as shown above. When the unit is switched OFF, the symbol on the
button will be grey and the screen will be greyed out as shown in the image below.
1
2
3
4
5
6
7
8
10
11
9
1

Page 11
Figure 5 Unit OFF Screen Display
MODE Button - Press this button to switch between operating MODES. Pressing the
button will bring up the following menu screen where the required MODE can then be
selected.
Figure 6 MODE Menu Screen
2

Page 12
The required MODE can be selected by pressing one of the five MODE buttons. Details of each
MODE are below. After selection, the display will return to the Home Screen with the
appropriate symbols for the selected MODE enabled.
Modes
No.
Mode
Description
1
Hot Water
This enables Hot Water only.
2
Heating
This enables Heating only.
3
Cooling
This enables Cooling only.
4
Hot Water & Heating
This enables both Heating & Hot Water with Hot Water taking priority.
5
Hot Water & Cooling
This enables both Cooling & Hot Water with Hot Water taking priority.
Temperature Setting Button - Press this button to set the desired temperatures.
Pressing the button will bring up the following menu screen where the required
temperature can then be set.
Figure 7 Temperature Setting Menu Screen
Depending on the current mode of the unit, the Temperature Setting Menu Screen will display
the relevant temperatures available to be modified. For example, the image of the display
above means that Hot Water & Cooling Mode is enabled so the ‘Tap’ symbol and the ‘Snow
3

Page 13
Flake’symbol are displayed representing Hot Water and Cooling Temperature settings
respectfully. The Temperature to be adjusted can be selected by pressing the required
temperature button. This will then bring up a keypad as shown below.
Figure 8 Temperature Setting Menu Screen
The required setting should be entered using the keypad and then confirmed with the ‘Enter’
button. To return to the setting screen, press the ‘Return’ button. To modify another setting,
repeat the above procedure. To return to the Home Screen press the ‘Return’ button located at
the top left of the Temperature Setting Menu Screen.
Lock Button - Press this button to lock the display. This function prevents unwanted
adjustments of parameters or changing of functions and timeclock on/off periods. When
the lock function is activated, the display will ignore all key presses. To unlock the
device, press the Lock Button again and then enter the password. The password is
‘0022’. Once entered, all functionality will be restored.
4

Page 14
Timeclock Button - Press this button to set the internal timeclock. When the button is
green, it indicates that the timeclock function is active. If the timeclock function is not
active, the button will be white. Pressing the button will bring up the following setup
screen where the required timeclock can then be set.
Figure 9 Timeclock Setup Screen
The Timeclock Setup Screen allows the on and off times for the current MODE to be set. The
functionality can be enabled or disabled by pressing the desired hourly sector on the clock as
shown above. Pressing the hourly sector will turn it green, indicating it is active and the right
hand side of the display will show that this has been set. Set the desired on-periods for the AM
times and then do the same for the PM times as required. Repeat this process for the other
days of the week.
5

Page 15
Settings Button - Press this button to enter the Setting Menu. Pressing the button will
bring up the following menu screen where five further Settings Menus can be found.
Figure 10 Settings Menu Screen
The Settings Menu Screen features six further Setting Sub-Menus. These include Status,
Clock, Electric heating, Mute, Factory & Curve as shown above and detailed below.
6

Page 16
Status –Press this button to enter the Status Sub-Menu. Pressing the button brings up the
following display screen which displays the current status of the unit, the current mode the unit
is running in and live data for a number of parameters. These parameters include Inlet Water
(Heating Return) Temperature, Outlet Water (Heating Flow) Temperature, Water Tank (DHW
Cylinder) Temperature and the Ambient Outdoor Temperature.
Figure 11 Status Display Screen

Page 17
Clock –Press this button to enter the Clock Sub-Menu. This sub-menu allows the clock to be
set to the current time and date. This must be accurately set to enable the timeclock
functionality and monitoring system to operate correctly. The clock sub-menu is shown below.
Figure 12 Clock Sub-Menu Screen
The date and time can be set using the up and down arrows shown in the display above (hold
the buttons down to speed up the adjustment). Confirm with the enter key to save the new time.
Return to the Setting Menu Screen with the return button at the top left side of the screen.

Page 18
Electric Heating - Press this button to enable or disable Fast Heating (when available). Fast
Heating is only available on models when parameter R12 is active and an auxiliary electric
immersion heater is fitted. Pressing the button will bring up the following menu screen, where
the fast heating function can be enabled or disabled.
Figure 13 Fast Heating Pop Up Screen
The Fast Heating Pop Up Screen has two options, ON or OFF. Select the required setting by
pressing the appropriate button. To return to the previous screen press any other place on the
display.
Fast Heating function is not available when the unit is in cooling mode. When in cooling mode,
the Fast Heating Button will be grey and will not be selectable.
This manual suits for next models
3
Table of contents
Other WarmFlow Heat Pump manuals