Vertical Stack Units (Universal Cabinet) –Installation Operational Manual
17
© Copyright 2013 CGC Group Inc. Installation Operation Maintenance Manual is Subject to Change without Notice. Last Revised: Aug, 2020
time the flash code 6 will be initiated on the red diagnostic LED. Compressor operation
will be restored in accordance with the “Intelligent Reset” algorithm.
b. If the suction pressure drops below the set point of the low pressure switch, the switch
will open and if it remains open beyond the 5 minute ignore period after start up,
compressor operation will be terminated within 10 seconds. Compressor operation will
be restored in accordance with the “Intelligent Reset” algorithm. A flash code of 5 on
the red diagnostic LED will be initiated at this time.
c. Intelligent Reset Algorithm –If a low or high pressure switch opens, the compressor will
be shut down. There is a 10 minute delay before the system is automatically reset, after
which if there is a cool call in place and all other enablers are within the start
parameters, the compressor will again be put into operation. Should either of the
pressure switches open again, the shutdown procedure will cycle again, followed by a
restart. The intelligent reset will allow two open switch shutdowns and restarts in a 24
hour period, but a third shutdown within 24 hours will put the refrigeration system into
a full and hard lockout requiring a power down to reset. If two or less switch open
shutdowns occur within a 24 hour period, they will be erased from memory and will not
contribute to a future hard lockout. (A hard lockout will prevent compressor operation
until the controls are powered down for at least 20 seconds, while a soft lockout is a
compressor shutdown that will be restored once the conditions causing the shutdown
have been rectified.
d. During compressor operation, refrigerant temperature, system fluid temperature and
discharge air temperature are continuously monitored. If the refrigerant temperature
drops below 40F, compressor operation will be disabled. After 10 minutes an auto
reset occurs and the compressor will be enabled as soon as the temperature rises above
65F. Actual compressor restart will be delayed a minimum of 5 minutes by the anti-
recycle timer. A flash code of 2 will be initiated upon a low refrigerant temperature
shutdown.
e. During compressor operation, if the condenser leaving temperature rises above 140F,
compressor operation will be disabled. After 10 minutes an auto reset occurs and the
compressor will be enabled as soon as the temperature drops below120F. The
outgoing system fluid sensor is mounted on the leaving fluid pipe. Actual compressor
restart will be delayed a minimum of 5 minutes by the anti-recycle timer. A flash code of
3 will be initiated upon a high outgoing system fluid temperature shutdown.
f. If the discharge air temperature drops below 40F compressor operation will be
disabled. After 10 minutes an auto reset occurs and the compressor will be enabled as
soon as the temperature rises above 55F. The discharge air temperature sensor is
mounted on the fan housing. Actual compressor restart will be delayed a minimum of 5
minutes by the anti-recycle timer. A flash code of 4 will be initiated upon a low
discharge air temperature shutdown.
g. The condensate level sensor is a 100 ohm thermistor that is heated for 15 seconds every
4 minutes. Its temperature is measured at the beginning of the heat cycle, and again at
the end of the heating cycle. If the condensate level rises above the sensor it will not
warm up during the warm up cycle, and the temperature change will be insignificant. It
is this lack of temperature change that the controller sees as an impending condensate
overflow. When high condensate level is detected, compressor operation is immediately
terminated, and at the same time the fan is stopped for 30 seconds, and then restarted.
At this time a flash code of 7 will be initiated. The 4 minute cycle will continue until the