
Part number 550-100-272/1021 – 3 –
ECO®Tec series 2 gas-fired water boiler – advanced manual
ECO Tec control setup
1. Set control parameters using the WIZARD option provided on ini-
tial start-up or manually enter parameters using control menus (see 
Figure26,page56 and following pages for information.)
2. See Express setup instructions beginning on page10 for basic 
systems and minimum settings required.
Boiler Model, Altitude and Fuel Type are critical settings. 
Failure to set correctly could result in severe personal injury, death or 
substantial property damage.
Temperature settings — You must ensure that the control is set for the 
proper water temperatures for the system. Excessive water temperature 
can cause signicant property damage in some applications. 
Multi-temperature systems — If the heating system includes circuits 
that require lower temperature water (radiant slab circuits, for example) 
as well as higher temperature circuits (DHW, nned tube baseboard, etc.), 
it is recommended to protect low-temperature circuits with limit controls 
that are wired to an control external limit circuit. Failure to provide 
regulation can result in substantial property damage.
Control Features
 Advanced interface and troubleshooting via Bluetooth®
communication. 
 Color touch-screen display for ease of operation monitoring and 
troubleshooting.
 Easy conguration with WIZARD step-by-step setup including 
on-screen help.
 e ECO Tec control can communicate to existing UnityTM controls 
in a multi-boiler network.
 ree (3) programmable priority assignments for up to four (4) 
heat inputs.
 Preset operating parameters for typical heating systems, including 
target temperatures, reset curves and circulator assignments.
 Integral outdoor reset option, with reset curves matched to the 
system type selected.
 ModBus communications for external communication and 
monitoring.
 0-10VDC input modulation or remote target input.
Figure 1 Control sequence of operation
Display 
status 
text
Control action 
(Also see Figure20,page50)
POWER 
UP
yCheck the boiler model listed on the power-up screen. 
If it is not correct, turn o the boiler. See page 59 for 
instructions to change setting.
yWhen power is turned on, the screen lists sensors that 
are detected. If any sensor is not listed, make sure it is 
connected correctly. Turn o power and restart.
Standby
yStandby - no calls for heat.
yToggles through no dots, 1 dot, 2 dots, then 3 dots 
while in standby (wrench symbol will show instead if 
maintenance is needed).
Blower 
ON
yCall for heat detected.
yDisplay on with BLUE banner (space heating) or 
PURPLE banner (DHW).
yStart min/max timers if more than one system is call-
ing - highest priority starts rst.
yStart circulators for this priority setup based upon 
settings.
yCalculate target temp — If sensor temp is below target 
temp, begin ring sequence.
yBlower to ignition speed for prepurge.
Ignition
yAer prepurge times out, begin ignition cycle.
yActivate gas valve and ignition spark.
yContinue ignition spark for ignition period.
yTurn o spark and use electrode to check for ame 
signal.
Space 
Heating
yFlame detected.
yRelease boiler to modulation.
yNOTE: If ame is not detected, the gas valve is turned 
o, blower turns on (postpurge), and control starts 
cycle again. Aer 5 failures, the control waits 60 
minutes, then tries again.
yIf priority timer times out, switch to next priority and 
start priority timer.
yIf demand satised, go to postpurge.
DHW 
Heating 
yFlame detected.
yRelease boiler to modulation.
yNOTE: If ame is not detected, the gas valve is turned 
o, blower turns on (postpurge), and control starts 
cycle again. Aer 5 failures, the control waits 60 
minutes, then tries again.
yIf priority timer times out, switch to next priority and 
start priority timer.
yIf demand satised, go to postpurge.
Blower 
OFF
yDemand satised (temperature reaches target tempera-
ture or limit setting).
yGas valve o.
yBlower to ignition speed for postpurge.
yReturn to standby aer purge.
Maintenance
yDisplay banner turns BLUE, toggling between graphic 
screen and maintenance screen (occurs if maintenance 
schedule timer times out).
yWill show during standby only.
yBoiler operates as normal.
Error/fault
yDisplay banner turns RED due to error or limit event.
WWSD
yWarm weather shut down - the boiler will not be 
allowed to re on space heating if the outdoor tem-
perature is greater than the WWSD setting.
yDHW operation is not aected by WWSD.
ECO Tec control overview
yControl inputs and outputs allow operation of multiple heating circuits 
(space heating and DHW, for example). 
yUp to three priority levels can be set, providing automatic switch-over 
on demand.
yis manual provides quick set-up information for boiler installations.
ECO Tec control operation
ye control responds to signals from the room thermostats, DHW 
aquastats (if used), boiler sensors (Boiler Out, Boiler In, ue temperature), 
outdoor temperature and system sensors, if used. Combi models will also 
respond to signals from DHW ow sensor and DHW temperature sensor.
ye control automatically adjusts blower speed to match boiler output to 
space heating and/or DHW heating demand. 
ye default control settings provides up to four (4) space heating zones. 
e control can be easily set up for operation with a DHW zone, with or 
without domestic priority.
ECO Tec control WIZARD
ye Wizard leads through a step-by-step setup procedure designed for 
the application chosen.
yContext-sensitive help is available to explain the purpose of key setup Items.
ECO Tec Control — Overview