GOLD CGs Gas-Fired Water Boiler — Boiler Manual
Prepare boiler location — air openings1e
Special considerations
Tight construction
ANSI Z223.1 defines unusually tight construction
where:
1. Walls and ceilings exposed to the outside atmo-
spherehaveacontinuouswatervaporretarderwith
a rating of 1 perm or less with openings gasketed,
and .. .
2. Weather-stripping has been added on openable
windows and doors,and . ..
3. Caulking or sealants are applied to areas such as
joints around windows and door frames, between
sole plates and floors, between wall-ceiling joints,
between wall panels,at penetrations for plumbing,
electrical, and gas lines,and in other openings.
Forbuildingswithsuchconstruction,provideairopen-
ings into the building from outside, sized per the ap-
propriatecaseinFigure 3ifappliancesaretouseinside
air for combustion and ventilation.
Exhaust fans and air movers
The appliance space must never be under a negative
pressureunlessallappliancesareinstalledasdirectvent.
Alwaysprovideairopeningssizednotonlytothedimen-
sions required for the firing rate of all appliances, but
alsotohandletheairmovementrateoftheexhaustfans
or air movers using air from the building or space.
Motorized air dampers
If the air openings are fitted with motorized dampers,
electrically interlock the damper to:
• Prevent the boiler from firing if the damper is not
fully open.
• Shuttheboiler downshouldthedamperclosedur-
ing boiler operation.
To accomplish this interlock, wire an isolated contact
(proving the damper open) in series with the thermo-
stat input to the boiler. The boiler will not start if this
contact is open, and will shut down should it open
during operation.
Combustion air options ✷
Using inside air — direct exhaust vent
The CGs boiler can use inside air if no contaminants are present in the
boilerspace.If contaminantsarelikelyto bepresent,install theCGs boiler
as a direct vent appliance, using the appropriate vent supplement and the
instructions in this manual.
Using outside air — direct vent
Combustion air can be ducted directly from outside to the CGs boiler
air intake fitting. This method is defined as direct vent (also referred to
as sealed combustion). Refer to the appropriate vent supplement and the
instructions in this manual. Two options are available: sidewall or vertical
direct vent. Each requires a special vent component kit.
Sizing air openings ✷
Airopenings provide forventilation(as wellascombustionair) toprevent
overheating of the boiler controls and boiler space. Air is also needed for
other appliances located in the same space.
Use Figure 3, page 11, selecting the appropriate installation conditions.
Notethatthesizing giveninFigure3appliesonlytoCGsinstallationswith
clearances no smaller than shown in Figure 1, page 7 of this manual.
Forsmallerclearances,regardlessof howtheairopeningsarearranged,two
openings providing free area of 1 square inch per 1,000 Btuh input of all
appliances in the space are required.
Airopeningsmustbesizedtohandle allappliancesand
air movers (exhaust fans,etc.) using the air supply.
The sizing given in Figure 3 is based on the National Fuel Gas Code,ANSI
Z223.1, allowing adequate air opening for gravity-vented gas appliances
(Category I).TheCGs boilerisratedCategoryIIIorIV(pressurizedvent),
andhasdifferentrequirementsforcombustionandventilationair,reflected
bythespecialsizinginstructionsgiveninFigure3.Theairopeningsrecom-
mendedinFigure3willallowadequateventilationand
combustion air provided the boiler room is not sub-
jectedtonegativepressureduetoexhaustfansor other
mechanical ventilation devices. Refer to the National
Fuel Gas Code for dealing with other conditions.
Louver allowance
The free area of openings means the area after reduc-
tion for any installed louvers or grilles. Be sure to
consider this reduction when sizing the air openings.
Combustion air opening location and sizing
requirements depend on the clearances around
the boiler. Checktheboilerplacementcomparedto
Figure 1,page 7.
If all clearances are at least equal to Figure 1,
page 7,applythesizingandplacementof openings
given on pages 10 and 11.
If ANY clearance is less than Figure 1, page 7,
you must provide air openings sized and located
as shown in Figure 2, page 7. DO NOT apply the
sizing and location information shown on page 10
or 11.TheFigure 2airopeningsarerequiredevenif
the boiler is direct vented (outside air piped to the
boilerairintakeasdescribedinthismanual).These
openingsensureadequateaircirculationaroundthe
boiler for cooling, even if the boiler does not use
inside air for combustion.
✷