
Part number 550-100-086/0809 13
COMMERCIAL GAS-FIRED WATER BOILER — Boiler Manual
Install water piping
Use two wrenches when tightening water piping at boiler,
using one of the wrenches to prevent the boiler interior
piping from turning. Failure to support the boiler piping
connections to prevent them from turning could cause
damage to boiler components.
General piping information
Additional controls, when required
The U-Control module uses temperature sensors to
provide both high limit protection and modulating tem-
perature control, and is UL353 Limit Controls certified
to meet ASME CSD-1 and Section IV requirements. The
U-Control module also provides low water protection,
both with a low water cut-off inside the boiler jacket
and by sensing the temperature of the heat exchanger.
Some codes/jurisdictions may require additional external
controls.
Additional limit controls
Consult local requirements for other codes/standards to determine1.
if additional limit devices are needed.
-ULTITEMPERATURESYSTEMS — If the heating system
includes circuits that require lower temperature water
(radiant slab circuits, for example) as well as higher
temperature circuits, it is recommended to protect low-
temperature circuits with limit controls that are wired to
a U-Control external limit circuit (P13 terminals 1 and 2
for manual reset, or P13 terminals 3 and 4 for automatic
reset).
See instructions beginning on2. page 51 for wiring information.
Manual reset operation: If external limit controls are to causea.
MANUALRESET of the U-control module, connect series-wired
isolated contacts to P13 terminals 1 and 2 (see page 51 for wir-
ing information).
Automatic reset operation: If external limit controls are tob.
cause AUTOMATIC RESET of the U-control module, connect
series-wired isolated contacts to P13 terminals 3 and 4 (see
page 51 for wiring information).
Low water cutoff
A push-to-test low water cutoff is included with the boiler. The1.
low water cutoff is mounted on the boiler supply manifold, and is
available for test by removing the boiler jacket.
Operation of the low water cutoff is manual reset through the2.
U-control.
Backflow preventer
Use backflow check valve in cold water supply as re-1.
quired by local codes.
Install relief valve
Install relief valve on the ¾” nipple in the 2x¾” bush-1.
ing on the boiler supply piping tee (Figure 5, page 12).
The relief valve must be piped with no smaller than ¾”
pipe and fittings.
Connect discharge piping to safe disposal location, fol-2.
lowing guidelines in the 7!2.).' below.
4OAVOIDWATERDAMAGEORSCALDING
DUETORELIEFVALVEOPERATIONASPER
LOCALORSTATECODES:
Discharge line must be connected to re-
lief valve outlet and run to a safe place
of disposal. Terminate the discharge
line in a manner that will prevent
possibility of severe burns or property
damage should the valve discharge.
Discharge line must be as short as pos-
sible and be the same size as the valve
discharge connection throughout its
entire length.
Discharge line must pitch downward
from the valve and terminate at least
6” above the floor drain where any
discharge will be clearly visible.
The discharge line shall terminate
plain, not threaded, with a material
serviceable for temperatures of 375 °F
or greater.
Do not pipe the discharge to any place
where freezing could occur.
No shutoff valve shall be installed be-
tween the relief valve and boiler, or in
the discharge line. Do not plug or place
any obstruction in the discharge line.
Test the operation of the valve after
filling and pressurizing system by
lifting the lever. Make sure the valve
discharges freely. If the valve fails to
operate correctly, replace it with a new
relief valve.
Failure to comply with the above guide-
lines could result in failure of the relief
valve to operate, resulting in the pos-
sibility of severe personal injury, death
or substantial property damage.