smartServo BL 4000
October 2022 Prevention of property damage EN
smartServo BL 4000_Beiblatt_1446849_R1a_EN.docx Parameterisation interfaces Seite 4 von 4
1Parameterisation interfaces
Valid for BL 4000 with IEF-Werner parameter set.
1.) Download and install the "ServoCommander" programme from metronix.
Link: https://www.metronix.de/metronixweb/downloads/software/
The necessary drivers for the BL 4000 parameterisation interfaces are also
installed.
2.) Connect PC with LAN cable to [X21] „RTE0“.
IEF Default-IP: 10.1.16.254, Subnetmask: 255.255.00
3.) Open the "ServoCommander" program from metronix and select communication
interface "Ethernet“.
Select Ethernet interface
The PC requires a suitable, fixed IP setting, such as:
IP: 10.1.x.x, Subnetmask: 255.255.0.0
Notes:
•The USB interface [X19] is not recommended! It is only suitable for data
transmission without controller enable.
Attention: No galvanic isolation. No protection in case of reverse polarity of
24V / GND.
Danger for USB interface on PC!
•The interface [X18] "Ethernet" is automatically deactivated if [X21] Realtime
Ethernet (RTE0) is active (IEF default setting = [X21] active).