2121 Norman Drive South Publication # eng02.027MCD
Waukegan, IL 60085 7/26/2002
(847) 887-7000
Page 2 of 3
The SGDG-04GT has terminals for connecting an external regen resistor of higher
capacity. However, the SGDG-04GT does not automatically recognize this external regen
resistor and activate the regen IGBT. Thus, when an external resistor is connected, the
regen energy is still processed by internal regen capacity and alarm #4 (over voltage) will
occur if the regen energy is too high. To add external regen capability to the SGDG-
04GT, the following method may be used:
1. Use external regen unit JUSP-RG08D. Refer to the information above for more
details. When this external regen unit is used, SW1-5 in the SGDG-01GT should
be turned OFF to avoid erroneous alarms.
Or
2. Use SGDG-04GTY22P for external regen application only. If the customer knows
that his application requires extra regen capacity, he must order this Y-mod unit.
With Y22P-mod, two (2) external regen resistors, RH500N25_ohmK, wired in
series must be connected to the SGDH-04GT at all times. These resistors should
be connected across terminals B1 and B2. The convection cool capacity of these
two resistors in series is 120W. The capacity increases to 300W with forced-air
cooling