© 2015 UTC Fire & Security. All rights reserved. 1 / 2 P/N 10-5221-501-ZSU1-01 • ISS 05FEB15
ZP752-2 Monitored Dual Output Module
Installation Sheet
Description
The ZP752-2 provides two conventional output circuits (Circuit
1 and Circuit 2) for operating polarized sounders, visual
indicators, and controls for ancillary equipment. Output 1 and
Output 2 share the same address and therefore switch on and
off at the same time.
The module comprises a front plate and a backbox. The front
plate houses the electronic components and plugs into the
backbox. The backbox provides the screw terminals for
connecting the field wiring.
The bicolor LED on the front plate indicates the status of the
module (off = normal condition, red = active condition, amber =
fault condition). There is space provided next to the LED to
attach an address label, if desired.
WARNING: This module will NOT operate without electrical
power. As fires frequently cause power interruption, we
suggest you discuss further safeguards with your local fire
protection specialist.
Installation
1. Remove the front plate from the backbox.
2. Drill out center hole in the backbox and run wires into the
module.
3. Remove appropriate knockouts on the backbox for
mounting to a conduit box. Mount the backbox to the
conduit box.
4. Make all wiring connections as shown in the wiring
diagram (Figure 2).
5. Set the address switch for the module. See “Address
switch settings” below (Figure 1).
6. Attach the address label to the indent that is on the front of
the module.
7. Secure the front plate to the backbox with the two screws
provided.
Address switch settings
SW1 is used to assign device addresses. Each switch segment
has a decimal value as shown in Figure 1.
The sum of all the switch segments in the ON position
determines the device address. You can set the device
address to any value between 001 and 127 that is not used by
another device on the same loop. For example, to select a
device address of 007 you must set SW1-1, SW1-2, and SW1-
3 to the ON position and the remaining switch segments to the
OFF position.
Figure 1: Address switch settings
Address
ON
OFF
Front plate - rear view
64
32
16
8
4
2
1
FUSES 1.0 A
Device address = 007
ON
1 2 3 4 5 6 7
1 2 4 8 16 32 64
Wiring
Field wiring connections are shown in Figure 2.
Run the wires through a hole in the backbox and connect them
to the screw terminals as shown.
Specifications
Application Indoor use
Power supply requirements
External power supply
Loop power
Max line drop
22 to 30 VDC
20 volt pulsed analogue loop
2V
Current
Standby
Activated
600 µA
700 µA
IP rating 42
Mounting Surface
Construction Moulded ABS
Colour White
Dimensions (W × H × D) 120 × 120 × 40 mm
Gross weight 310 g
Initiating device circuits (IDC)
Output current
EOL resistor value
1 A at 24 VDC per circuit
2.2 KΩ
Operating environment
Temperature
Relative humidity
−10 to +70°C
20 to 95% noncondensing
Storage temperature −10 to +70°C
2 / 2 P/N 10-5221-501-ZSU1-01 • ISS 05FEB15
Figure 2: Wiring diagram
Notes
1. Screened cable.
2. EOLR required if circuit is not used.
3. Terminal marking (plus/minus)
indicates signal polarity when the
circuit is active. The polarity
reverses when the circuit is not
active.
4. Signal source must be CE and
EN54-4 compliant. The jumper must
be connected.
5. Each output circuit provides up to 1
A at 24 VDC. Each output circuit
has a 1 A fuse. Fuses are monitored
by the panel.
6. Devices connected to the output
circuit must be polarized as shown.
If non-polarized devices are used,
insert a 1N4002/7 diode in the
positive leg of each device, with the
stripe facing the device. For
inductive loads (relays etc), fit a
Bipolar Transient Protector
(P/N 235196P) across the coil.
7. Attach the supplied ferrites to cables
as shown in Figure 2 (internal to the
module).
8. The following ferrite core needs to
be fitted to all cables (externally to
the module): TDK ZCAT3055-1330.
Regulatory information
This section includes both regulatory information and a
summary on the declared performance according to the
Construction Products Regulation 305/2011. For detailed
information refer to the product Declaration of Performance.
Certification
Certification body 0370
Declaration of
Performance number 360-5221-0199
Year of first CE marking 10
Product Identification ZP752-2
Intended use See DoP point 3
Essential characteristics See DoP point 9
Manufacturer United Technologies Safety System Co.,
Ltd.
80,
Changjiang East Road, QETDZ, 066004
Qinhuangdao HEBEI, China
Authorized EU manufacturing
representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
European Union
directives
1999/5/EC (R&TTE directive): Hereby, UTC
Fire & Security declares that this device is
in compliance with the essential
requirements and other relevant provisions
of Directive 1999/5/EC.
2012/19/EU (WEEE directive): Products
marked with this symbol cannot be
disposed of as unsorted municipal waste in
the European Union. For proper recycling,
return this product to your local supplier
upon the purchase of equivalent new
equipment, or dispose of it at designated
collection points. For more information see:
www.recyclethis.info.
Contact information
For contact information, see www.utcfssecurityproducts.eu.

Other Ziton I/O System manuals

Ziton ZP752-2 Assembly instructions

Ziton

Ziton ZP752-2 Assembly instructions

Ziton ZCR452 User manual

Ziton

Ziton ZCR452 User manual

Ziton ZR451-3 User manual

Ziton

Ziton ZR451-3 User manual

Popular I/O System manuals by other brands

National Instruments FieldPoint FP-1300 quick start guide

National Instruments

National Instruments FieldPoint FP-1300 quick start guide

WAGO WAGO-I/O-SYSTEM 750 XTR Series manual

WAGO

WAGO WAGO-I/O-SYSTEM 750 XTR Series manual

National Instruments DAQPad-1200 user manual

National Instruments

National Instruments DAQPad-1200 user manual

hager TYA608A manual

hager

hager TYA608A manual

Grundfos IO 113 instructions

Grundfos

Grundfos IO 113 instructions

Akytec MV210-101 user guide

Akytec

Akytec MV210-101 user guide

Nittan EV-Mini IP2 installation instructions

Nittan

Nittan EV-Mini IP2 installation instructions

esera automation 11218 user guide

esera automation

esera automation 11218 user guide

WAGO 750 Series manual

WAGO

WAGO 750 Series manual

ProSoft PLX51-HART-4I user manual

ProSoft

ProSoft PLX51-HART-4I user manual

M-system R7L-DAC16 instruction manual

M-system

M-system R7L-DAC16 instruction manual

Allen-Bradley 1794-IT8 installation instructions

Allen-Bradley

Allen-Bradley 1794-IT8 installation instructions

Acces USB-II-16 user manual

Acces

Acces USB-II-16 user manual

Stahl 9472/35 Series operating instructions

Stahl

Stahl 9472/35 Series operating instructions

Digital Equipment StorageWorks DS-BA35X-MN installation guide

Digital Equipment

Digital Equipment StorageWorks DS-BA35X-MN installation guide

Datum 5091-P8e Technical description

Datum

Datum 5091-P8e Technical description

M-system R8-SS4NJ instruction manual

M-system

M-system R8-SS4NJ instruction manual

National Instruments NI 9236 Getting started guide

National Instruments

National Instruments NI 9236 Getting started guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.