Ziton I/O Unit Installation Guide
General
The Ziton input / output (I/O) unit is available under the
following part numbers:
PART NO VARIANT TYPE
ZR451-3 Ziton wireless single I/O unit
ZR452-3 Ziton wireless dual I/O unit
The address of the unit is set when programming the
device to the Ziton loop interface (see programming
manual for details). The installation must conform to
BS5839:Part 1 (or applicable local codes). The Ziton I/O
unit is suitable for indoor use only.
Installation of Ziton I/O unit
Ensure that all Ziton I/O units are sited in accordance
with the survey and design details.
Remove the four front plate retaining screws. Retain
these for re-assembly when installation is complete.
Remove the front plate.
Drill required cable entry points for input and output
connections. Recommended cable entry points are
shown in Figure 1.
Position the Ziton I/O unit in the required location and
mark the four xing positions. These are shown in Figure
1.
Using suitable screws and xings attach the device
securely to the wall.
To ensure correct operation, connect the power jumper
across the PIN header on the PCB. The location of header
is shown in Figure 1.
The Ziton IO unit is powered by 6 x AA alkaline batteries.
These are supplied tted. Should batteries require
replacement, only use specied batteries whilst
observing correct polarity as shown in Figure 1.
Fixing
Position 1
Fixing
Position 2
Fixing
Position 3
Fixing
Position 4
Power
Jumper
Cable
Entry Points
Cable
Entry Points
Batteries that have been removed must be disposed of in
accordance with your country’s relevant Waste Electrical
and Electronic Equipment (W.E.E.E) regulations.
Please see commissioning manual for log on procedure
details.
Indication LED operation
The Ziton I/O unit has six indication LEDs. Illumination of
these is enabled by pressing the LED enable button
(shown in Figure 2). If the enable button is pressed, the
following LEDs will be illuminated for a time period of 10
minutes and then automatically time out.
Output LEDs:-
Each relay output has a red LED associated with it. If the
output is activated (output bit set to 1) the LED will
illuminate.
Notes
Figure 1
www.acornfiresecurity.com
www.acornfiresecurity.com

OUTPUT 2OUTPUT 1
3VDC SET RST
INPUT 1 INPUT 2
LED
ENABLE
PO WER
INPUT 1
INPUT 2
FAULT
CLOSED
0 1
1
64
F-SAFE
N/O COM N/C
SERIAL NO
LOGON
IP- IP+ IP- IP+
3VDC SET RST N/O COM N/C
EXPAN1 EXPAN2
RELAY ON
RELAY ON
2
4
8
16
32
ANTENNA
KEEP CABLES AWAY FROM THIS AREA
LR6 AA
LR6 AA
LR6 AA
LR6 AA
LR6 AA
LR6 AA
Figure 2
Relay
LEDs
Input
LEDs
LED
Enable
Button
Input Fault LEDs:-
Each input contact has a yellow fault LED associated with
it. If the input is in a fault condition the LED will be
illuminated.
Input Switch Closed LEDs:-
Each input contact has a red switch closed LED
associated with it. If the input is closed the LED will be
illuminated.
Output connection Wiring
The Ziton I/O unit has clean contact relay outputs
capable of switching 2A @ 24V DC. The location of the
output connections are shown in Figure 2.
0 Common and normally closed connected
1 Common and normally open connected
On power up the relay outputs will be reset to output bit
state 0.
Output fail to safe mode
This function is enabled/disabled by loop address switch
8. Switch 8 to the 1 position enables this mode of
operation and switch 8 to the 0 position disables the
mode. As default this mode is disabled.
When the function is enabled, the relay outputs will
assume the output bit state 0 in the event of:-
• Communication loss to the Ziton loop interface
• Failure of any battery pack
Note: Switches 1 to 7 are not used
Output bit
state Relay State
N/O
INPUT
CONNECTION
20k
EOL
IP -
IP +
4K7
INPUT 1
Figure 3
20K resistor colour coded as red / black / orange
4K7 resistor colour coded as yellow / violet / red
20K = normal condition
3K8 = alarm condition
Open circuit = tamper condition
Short circuit = tamper condition
Functional testing
When polled by a compatible panel, the Ziton I/O unit, in
its normal condition will return an analogue value of 90*.
Input open (normal condition) 90* N/A 0
Input closed (alarm condition) 213 N/A 1
Open circuit N/A 118 N/A
Short circuit N/A 118 N/A
Tamper N/A 181 N/A
* The Slot 5 analogue value for the open input conditions
are shown in relation to the device’s signal strength.
Therefore these can vary between analogue value 90, 85,
80 or 75.
Fault condition Analogue value Input
status
Slot 5 Slot 6
Specication
Operating
Temperature -10 to +50°C
Storage
Temperature -20 to +60°C
Humidity Up to 95% non-condensing
Supply 6x AA Alkaline (Panasonic LR6AD
Powerline / Varta 4006 Industrial)
IP Rating IP65
Output Rating 2A @ 24V DC
Operating
Frequencies 868 MHz
Output Transmitter
Power Variable 0-14 dBm
Dimensions 120mm (H) 240mm (W) 50mm (D)
Weight 0.60kg
Regulatory information
Manufacturer EMS Ltd.
Technology House, Sea Street,
Herne Bay, Kent, CT6 8JZ,
United Kingdom
Year of
manufacture See serial number label inside unit
Certication
Certication body
CPR Certicate
DOP 0359-CPR-0171
Approved to EN54-18
EN54-25
Application Indoor use only
European Union
directives
EMS declares that the radio
equipment type Ziton Wireless
Input / Output Unit is in compliance
with Directive 2014/53/EU. The full
text of the EU declaration of
conformity is available at the
following internet address:
www.utcfssecurityproducts.eu/dop/
2012/19/EU (WEEE directive):
Products marked with this symbol
cannot be disposed of as unsorted
municipal waste in the European
Union. For proper recycling, return
this product to your local supplier
upon purchase of equivalent new
equipment, or dispose of it at
designated collection points. For
more information see
www.recyclethis.info
Contact information
For contact information, see www.utcreandsecurity.com
Input
connections
Output
connections
0359
12
Input connection wiring
The location of the Ziton I/O unit’s input connections are