Programmable Multi-Level Motion Sensor
Instruction Manual
Add:
1501 Industrial Way N, Toms River, NJ 08755 Phone: 866-222-8866 E-mail: [email protected] Web: www.aboveallLighting.com ©2016 ABOVE ALL. Inc. All rights reserved
High Mode: When the sensor detects motion the dimming control output ramps up to the
selected HIGH light level.
1.
Low Mode: After the sensor stops detecting motion and the time delay expires the dimming
control output fades down to the selected LOW light level.
2.
Time Delay: The selected time period that must elapse after the last time the sensor detects
motion for the electric lights to fade to LOW mode.
3.
High Mode: When the sensor detects motion the dimming control output ramps up to the
selected HIGH light level.
4.
Sensitivity: The response of the PIR detector to motion within the sensor’s coverage area.5.
Setpoint: When enabled, the selectable ambient light level threshold that will hold the electric
lights off or at LOW level when the sensor detects motion.
The Auto option invokes an automatic calibration procedure to establish an appropriate
setpoint based upon the contribution of the electric light. As part of this procedure, the
controlled load is turned on for two minutes to warm up the lamp, and then switched off
and on eight times, terminating in an off state. After this process, a new setpoint value is
automatically calculated.
6.
Photocell On/Off: When enabled, the sensor will force the load OFF after the light level has
exceeded the selected photocell setpoint for at least a minute. It will also force the load ON
when the light level goes below the setpoint, even if no motion is detected.
Once ON (initially at High), the load will dim to Low following the Time Delay, and to OFF
following the Cut Off time. To ensure dusk to dawn control, Cut Off must be disabled.
The photocell On/Off setpoint is automatically set to maintain a deadband of at least 10 fc
above the Hold Off Setpoint to prevent cycling if the two features are used together.
7.
Ramp Up Time: Time period for light level to increase from LOW to HIGH.8.
Fade Down Time: Time period for light level to decrease from HIGH to LOW.9.