aci SST5630 Installation instructions

Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 1
Version: 6.0
I0000701
FIGURE 1: ENCLOSURE DIMENSIONS
WIRELESS REMOTE/STRAP-ON
TEMPERATURE SENSORS
Installation & Operation Instructions
SST5630
Phone: 1-888-967-5224
Website: workaci.com
the data transmission has been received successfully. The Data-Link LED will continue to blink once for
every data transmission. The data transmission rate is programmed into the sensor (normally 75 second
intervals). To manually initiate a data transmission press the push button switch located by the negative
terminal of the battery.
MOUNTING INSTRUCTIONS
ENCLOSURE MOUNTING
The enclosure must be mounted outside of the freezer/cooler. On Vertical units, mount on the top of the
freezer see Figure 2. On Horizontal units, mount on the backside or side of the freezer. Attach the base
directly to the wall by using double sided tape.
WIRE INSTALLATION
ACI recommends installing the wire through the
door seal, probe access port, or cooler wall. On
horizontal units, the preferred method is using the
rear door seal as shown in Figure 3. On vertical
units, remove the rear panel. There is typically a
probe access hole. Probe and wires can be ran into
that access hole. Alternatively, you can drill a hole
just larger than the diameter of the wire (0.125”
(3.175 mm)) through the wall. From inside the
cooler/freezer, push the wire through the hole. Use
mounting clips to secure the wire to the interior wall
or shelving. Use silicone caulking to seal the hole
around the wire.
2.56"
4.53"
2.23"
Battery Positive
Terminal
Internal Link
Button
SST5630AE
Altech Water
Tight Fitting
NEMA 4X Enclosure
10' Cable
2.00" x 0.187" Probe
GENERAL INFORMATION
The SST5630 is a battery operated spread spectrum
wireless remote/strap-on temperature sensor. It is
designed for monitoring refrigeration or freezers
from -300°F (-184°C) to 300°F (149°C).
The RTD sensor is encapsulated in a 0.187” O.D. 304
stainless steel probe (2” probe length) for single
point pipe temperature monitoring.
ACI’s wireless sensors utilize reliable Spread
Spectrum Radio technology. They can be installed
easily in minutes eliminating hundreds of feet of
wire and saving installation cost while reducing
installation labor risks.
The sensor Data-Link LED conrms the data
transmission was received by the receiver for fast
and reliable positioning of the sensor during
installation. There is no need for special wireless installation equipment or tool.
Together with the ACI receivers and controllers, the ACI wireless sensors can be used with any LON works,
BACnet, Modbus, system or panel.
The maximum radio transmission distance is dependent on the building type. In a typical commercial
building with steel I-Beam construction, concrete oors with reinforcing rod, and metal stud walls, it can be
expected that transmissions will penetrate vertically typically one oor below and one oor above a
transceiver/receiver, and horizontally through 200 to 300 feet of walls, furniture and air.
MOUNTING INSTRUCTIONS
Wireless sensors should be installed within 200 to 300 feet of the receiver. RR2552 signal repeaters can be
installed as to increase transmission distance between sensors and receivers.
CAUTION:
Observe battery polarity when installing battery.
To select the proper sensor location, rst install and power the receiver. To activate the sensor insert the
battery observing the polarity.
While the sensor is attempting to connect to the receiver the Data-Link LED will blink rapidly 8–10 times
every 10 seconds. Once a connection has been established the Data-Link LED will blink once to indicate
SENSOR MOUNTING
Bullet Probe sensors can be wrapped around a shelf as shown in Figure 4 (p.2). Alternatively, the sensor
may be mounted on walls using a mounting clip. The sensor should be mounted in an area where air
circulation is well-mixed and not blocked by obstructions. Slide the sensor probe through the mounting
clip - see FIGURE 5 (p.2). Drill a 1/4”screw through the socket and tighten to the wall. If a thermal buer is
required, use a glycol kit (ACI Item #130127). Drill pilot holes for the provided mounting screws. Use the
mounting clip holes as a guide - see FIGURE 6 (p.2). Drill the #10-16 x 1/2“ screws through the bracket
holes and fasten it to the wall. Insert the bottle into the bracket, and make sure it is seated securely.
Note: When using in tank or glycol application, the sensor cannot be fully submerged. The back end of the
probe (where the wire enters), must be kept above the liquid.
Locate and record the sensor ID numbers located on a label inside the unit prior to mounting.
The sensor has a Low Battery LED that will start to blink continuously when the battery voltage is low. A
low battery signal is also sent to the receiver for remote indication that the battery should be replaced. If
the battery is not replaced in approximately 2 months, the battery voltage will become so low that the Low
Battery and Data-Link LEDs will not blink. Replace the battery and the Data-Link LED will start blinking
while the sensor is re-establishing communications with the receiver.
Then attach the cover of the sensor by installing the four screws.
PRECAUTIONS
SENSORS, REPEATERS AND RECEIVERS SHOULD NOT BE INSTALLED IN THE FOLLOWING AREAS:
• INSIDE METAL ENCLOSURE / PANEL
• INSIDE OR IMMEDIATELY NEXT TO ELEVATOR SHAFT / ELEVATOR BANKS
• IN FRONT OF OR IMMEDIATELY NEXT TO LARGE TREES OR LARGE BODY OF WATER
TRANSMISSION DISTANCE AND PERFORMANCE WILL BE DRASTICALLY REDUCED.
CAUTION:
DO NOT USE THIS PRODUCT IN ANY SAFETY RELATED APPLICATIONS WHERE HUMAN LIFE
MAY BE AFFECTED.
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 2
Version: 6.0
I0000701
the data transmission has been received successfully. The Data-Link LED will continue to blink once for
every data transmission. The data transmission rate is programmed into the sensor (normally 75 second
intervals). To manually initiate a data transmission press the push button switch located by the negative
terminal of the battery.
MOUNTING INSTRUCTIONS
ENCLOSURE MOUNTING
The enclosure must be mounted outside of the freezer/cooler. On Vertical units, mount on the top of the
freezer see Figure 2. On Horizontal units, mount on the backside or side of the freezer. Attach the base
directly to the wall by using double sided tape.
WIRE INSTALLATION
ACI recommends installing the wire through the
door seal, probe access port, or cooler wall. On
horizontal units, the preferred method is using the
rear door seal as shown in Figure 3. On vertical
units, remove the rear panel. There is typically a
probe access hole. Probe and wires can be ran into
that access hole. Alternatively, you can drill a hole
just larger than the diameter of the wire (0.125”
(3.175 mm)) through the wall. From inside the
cooler/freezer, push the wire through the hole. Use
mounting clips to secure the wire to the interior wall
or shelving. Use silicone caulking to seal the hole
around the wire.
GENERAL INFORMATION
The SST5630 is a battery operated spread spectrum
wireless remote/strap-on temperature sensor. It is
designed for monitoring refrigeration or freezers
from -300°F (-184°C) to 300°F (149°C).
The RTD sensor is encapsulated in a 0.187” O.D. 304
stainless steel probe (2” probe length) for single
point pipe temperature monitoring.
ACI’s wireless sensors utilize reliable Spread
Spectrum Radio technology. They can be installed
easily in minutes eliminating hundreds of feet of
wire and saving installation cost while reducing
installation labor risks.
The sensor Data-Link LED conrms the data
transmission was received by the receiver for fast
and reliable positioning of the sensor during
installation. There is no need for special wireless installation equipment or tool.
Together with the ACI receivers and controllers, the ACI wireless sensors can be used with any LON works,
BACnet, Modbus, system or panel.
The maximum radio transmission distance is dependent on the building type. In a typical commercial
building with steel I-Beam construction, concrete oors with reinforcing rod, and metal stud walls, it can be
expected that transmissions will penetrate vertically typically one oor below and one oor above a
transceiver/receiver, and horizontally through 200 to 300 feet of walls, furniture and air.
MOUNTING INSTRUCTIONS
Wireless sensors should be installed within 200 to 300 feet of the receiver. RR2552 signal repeaters can be
installed as to increase transmission distance between sensors and receivers.
CAUTION:
Observe battery polarity when installing battery.
To select the proper sensor location, rst install and power the receiver. To activate the sensor insert the
battery observing the polarity.
While the sensor is attempting to connect to the receiver the Data-Link LED will blink rapidly 8–10 times
every 10 seconds. Once a connection has been established the Data-Link LED will blink once to indicate
FIGURE 2: ENCLOSURE MOUNTING
FIGURE 3: WIRE ROUTING
FIGURE 4: SENSOR MOUNTING
FIGURE 5: SENSOR MOUNTING
ON WALL
BULLET PROBE
MOUNTING CLIP
FIGURE 6: GLYCOL SENSOR
w/ BRACKET
SENSOR WIRES
GLYCOL BOTTLE AND
STANDARD 4”SENSOR
PROBE
STEEL MOUNTING
BRACKET
SENSOR MOUNTING
Bullet Probe sensors can be wrapped around a shelf as shown in Figure 4 (p.2). Alternatively, the sensor
may be mounted on walls using a mounting clip. The sensor should be mounted in an area where air
circulation is well-mixed and not blocked by obstructions. Slide the sensor probe through the mounting
clip - see FIGURE 5 (p.2). Drill a 1/4”screw through the socket and tighten to the wall. If a thermal buer is
required, use a glycol kit (ACI Item #130127). Drill pilot holes for the provided mounting screws. Use the
mounting clip holes as a guide - see FIGURE 6 (p.2). Drill the #10-16 x 1/2“ screws through the bracket
holes and fasten it to the wall. Insert the bottle into the bracket, and make sure it is seated securely.
Note: When using in tank or glycol application, the sensor cannot be fully submerged. The back end of the
probe (where the wire enters), must be kept above the liquid.
Locate and record the sensor ID numbers located on a label inside the unit prior to mounting.
The sensor has a Low Battery LED that will start to blink continuously when the battery voltage is low. A
low battery signal is also sent to the receiver for remote indication that the battery should be replaced. If
the battery is not replaced in approximately 2 months, the battery voltage will become so low that the Low
Battery and Data-Link LEDs will not blink. Replace the battery and the Data-Link LED will start blinking
while the sensor is re-establishing communications with the receiver.
Then attach the cover of the sensor by installing the four screws.
PRECAUTIONS
SENSORS, REPEATERS AND RECEIVERS SHOULD NOT BE INSTALLED IN THE FOLLOWING AREAS:
• INSIDE METAL ENCLOSURE / PANEL
• INSIDE OR IMMEDIATELY NEXT TO ELEVATOR SHAFT / ELEVATOR BANKS
• IN FRONT OF OR IMMEDIATELY NEXT TO LARGE TREES OR LARGE BODY OF WATER
TRANSMISSION DISTANCE AND PERFORMANCE WILL BE DRASTICALLY REDUCED.
CAUTION:
DO NOT USE THIS PRODUCT IN ANY SAFETY RELATED APPLICATIONS WHERE HUMAN LIFE
MAY BE AFFECTED.
the data transmission has been received successfully. The Data-Link LED will continue to blink once for
every data transmission. The data transmission rate is programmed into the sensor (normally 75 second
intervals). To manually initiate a data transmission press the push button switch located by the negative
terminal of the battery.
MOUNTING INSTRUCTIONS
ENCLOSURE MOUNTING
The enclosure must be mounted outside of the freezer/cooler. On Vertical units, mount on the top of the
freezer see Figure 2. On Horizontal units, mount on the backside or side of the freezer. Attach the base
directly to the wall by using double sided tape.
WIRE INSTALLATION
ACI recommends installing the wire through the
door seal, probe access port, or cooler wall. On
horizontal units, the preferred method is using the
rear door seal as shown in Figure 3. On vertical
units, remove the rear panel. There is typically a
probe access hole. Probe and wires can be ran into
that access hole. Alternatively, you can drill a hole
just larger than the diameter of the wire (0.125”
(3.175 mm)) through the wall. From inside the
cooler/freezer, push the wire through the hole. Use
mounting clips to secure the wire to the interior wall
or shelving. Use silicone caulking to seal the hole
around the wire.
GENERAL INFORMATION
The SST5630 is a battery operated spread spectrum
wireless remote/strap-on temperature sensor. It is
designed for monitoring refrigeration or freezers
from -300°F (-184°C) to 300°F (149°C).
The RTD sensor is encapsulated in a 0.187” O.D. 304
stainless steel probe (2” probe length) for single
point pipe temperature monitoring.
ACI’s wireless sensors utilize reliable Spread
Spectrum Radio technology. They can be installed
easily in minutes eliminating hundreds of feet of
wire and saving installation cost while reducing
installation labor risks.
The sensor Data-Link LED conrms the data
transmission was received by the receiver for fast
and reliable positioning of the sensor during
installation. There is no need for special wireless installation equipment or tool.
Together with the ACI receivers and controllers, the ACI wireless sensors can be used with any LON works,
BACnet, Modbus, system or panel.
The maximum radio transmission distance is dependent on the building type. In a typical commercial
building with steel I-Beam construction, concrete oors with reinforcing rod, and metal stud walls, it can be
expected that transmissions will penetrate vertically typically one oor below and one oor above a
transceiver/receiver, and horizontally through 200 to 300 feet of walls, furniture and air.
MOUNTING INSTRUCTIONS
Wireless sensors should be installed within 200 to 300 feet of the receiver. RR2552 signal repeaters can be
installed as to increase transmission distance between sensors and receivers.
CAUTION:
Observe battery polarity when installing battery.
To select the proper sensor location, rst install and power the receiver. To activate the sensor insert the
battery observing the polarity.
While the sensor is attempting to connect to the receiver the Data-Link LED will blink rapidly 8–10 times
every 10 seconds. Once a connection has been established the Data-Link LED will blink once to indicate
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 3
Version: 6.0
I0000701
SENSOR MOUNTING
Bullet Probe sensors can be wrapped around a shelf as shown in Figure 4 (p.2). Alternatively, the sensor
may be mounted on walls using a mounting clip. The sensor should be mounted in an area where air
circulation is well-mixed and not blocked by obstructions. Slide the sensor probe through the mounting
clip - see FIGURE 5 (p.2). Drill a 1/4”screw through the socket and tighten to the wall. If a thermal buer is
required, use a glycol kit (ACI Item #130127). Drill pilot holes for the provided mounting screws. Use the
mounting clip holes as a guide - see FIGURE 6 (p.2). Drill the #10-16 x 1/2“ screws through the bracket
holes and fasten it to the wall. Insert the bottle into the bracket, and make sure it is seated securely.
Note: When using in tank or glycol application, the sensor cannot be fully submerged. The back end of the
probe (where the wire enters), must be kept above the liquid.
Locate and record the sensor ID numbers located on a label inside the unit prior to mounting.
The sensor has a Low Battery LED that will start to blink continuously when the battery voltage is low. A
low battery signal is also sent to the receiver for remote indication that the battery should be replaced. If
the battery is not replaced in approximately 2 months, the battery voltage will become so low that the Low
Battery and Data-Link LEDs will not blink. Replace the battery and the Data-Link LED will start blinking
while the sensor is re-establishing communications with the receiver.
Then attach the cover of the sensor by installing the four screws.
PRECAUTIONS
SENSORS, REPEATERS AND RECEIVERS SHOULD NOT BE INSTALLED IN THE FOLLOWING AREAS:
• INSIDE METAL ENCLOSURE / PANEL
• INSIDE OR IMMEDIATELY NEXT TO ELEVATOR SHAFT / ELEVATOR BANKS
• IN FRONT OF OR IMMEDIATELY NEXT TO LARGE TREES OR LARGE BODY OF WATER
TRANSMISSION DISTANCE AND PERFORMANCE WILL BE DRASTICALLY REDUCED.
CAUTION:
DO NOT USE THIS PRODUCT IN ANY SAFETY RELATED APPLICATIONS WHERE HUMAN LIFE
MAY BE AFFECTED.
WARRANTY
The ACI Wireless Series are covered by ACI’s Two (2) Year Limited Warranty, which is located
in the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website:
www.workaci.com.
W.E.E.E. DIRECTIVE
At the end of their useful life the packaging and product should be disposed of via a suitable recycling
centre. Do not dispose of with household waste. Do not burn.
PRODUCT SPECIFICATIONS
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 4
Version: 6.0
I0000701
Input Voltage:
Battery Life:
Operating Temperature Range:
Operating Humidity Range:
Storage Temperature Range:
Sensor Range:
Accuracy:
Probe Dimensions:
Cable Length | Cable Type:
Fitting:
Data Protocol:
RF Characteristics:
Sensor Data Transmission Time:
Transmission Distance:
Enclosure Material |
Flammability Rating:
Battery; 1 (Duracell DL123A), Lithium 3V 1400 mAh 45 mA maximum
2-3 years typical
14 to 140ºF (-10 to 60ºC)
5 to 65%, Non-condensing
0 to 140ºF (-17.70 to 60ºC), 5 to 65% RH, Non-condensing
-300 to 300ºF (-184 to 149ºC)
+/- 1ºF (+/- 0.555ºC) 12 bit resolution
Length: 2.0” (50.80 mm) | Diameter: 0.188” (4.78 mm) | Material: 304 stainless steel
10’ (3.05m) | CL2P plenum rated
Nylon 6/6, Flammability rating UL94V-2
IEEE 802.15.4-2003/2006
900 MHz, Operating Frequency 10 channels between 902 – 928 MHz
Transmitter Power: 11 dBm | Receiver Sensitivity: -11 dBm
75 seconds (default) | 300 seconds (optional)
200 – 300 ft horizontally depending on building type and construction, and typically one oor
above and below the transceiver vertically
Polycarbonate Plastic | UL94-HB

Other aci Temperature Controllers manuals

aci DH2630A Owner's manual

aci

aci DH2630A Owner's manual

aci WH2630A Installation instructions

aci

aci WH2630A Installation instructions

aci ROOM Series Installation instructions

aci

aci ROOM Series Installation instructions

aci SST2630 User manual

aci

aci SST2630 User manual

aci WH2630AR/P User manual

aci

aci WH2630AR/P User manual

aci BACnet Series Installation instructions

aci

aci BACnet Series Installation instructions

Popular Temperature Controllers manuals by other brands

Cryo-con 24C user guide

Cryo-con

Cryo-con 24C user guide

AMX AXC-TEMP AND RTS-1 TEMPERATURE CONTROL CARD AND ROOM TEMPERATURE... instruction manual

AMX

AMX AXC-TEMP AND RTS-1 TEMPERATURE CONTROL CARD AND ROOM TEMPERATURE... instruction manual

Crestron C2N-RTHS Operations & installation guide

Crestron

Crestron C2N-RTHS Operations & installation guide

TiEmme SY250 manual

TiEmme

TiEmme SY250 manual

dixell COOL MATE XLH360 operating instructions

dixell

dixell COOL MATE XLH360 operating instructions

Ephy-Mess PR-SPA-EX-WKF manual

Ephy-Mess

Ephy-Mess PR-SPA-EX-WKF manual

DeDietrich AD251 Assembly instructions

DeDietrich

DeDietrich AD251 Assembly instructions

Carrier ZS Standard installation guide

Carrier

Carrier ZS Standard installation guide

MULTISPAN TC-49 quick start guide

MULTISPAN

MULTISPAN TC-49 quick start guide

Kingspan Temperature differential controller Installation and operating instructions

Kingspan

Kingspan Temperature differential controller Installation and operating instructions

Panasonic CZ-64ESMC3 quick reference

Panasonic

Panasonic CZ-64ESMC3 quick reference

nilan Combi 302 Polar Top user manual

nilan

nilan Combi 302 Polar Top user manual

Carel PVPRO user manual

Carel

Carel PVPRO user manual

Intertec Data Systems TC D operating instructions

Intertec Data Systems

Intertec Data Systems TC D operating instructions

Ropex CIRUS UPT-6010 operating instructions

Ropex

Ropex CIRUS UPT-6010 operating instructions

Stahl 8146/5051 Series operating instructions

Stahl

Stahl 8146/5051 Series operating instructions

Gira System 3000 operating instructions

Gira

Gira System 3000 operating instructions

Velleman VMA335 user manual

Velleman

Velleman VMA335 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.