GP Series Portable Chillers 882.12047.00 • 11/15/2021 16
dierenal” value the controller will enable the compressor; if equipped with two compressors the
controller will enable the one with the least amount of hours. The second compressor will be
enabled if the leaving uid temperature remains above the setpoint plus the “compressor on
dierenal” value for more than 60 seconds.
The hot gas valve is designed to trim the load of one compressor and will modulate in order to meet
the desired leaving uid setpoint via a PID algorithm. Aer the compressor starts, the hot gas valve
is allowed to modulate. The compressor will shut o if the leaving uid temperature drops below
the “compressor o dierenal” and the hot gas valve is at 100% for the “compressor o delay”
me. The hot gas will reset to 0% when the compressor is o. There is a “compressor ancyle” mer
that will delay the me between compressor starts to prevent short cycling of the compressor. This
is a start to start mer set at 5 minutes. For example, if the compressor has been running for 5
minutes and shuts o, then the compressor can start immediately if the demand is there. If it has
only been running for 2 minutes, then it would not be able to start again for 3 minutes.
For a unit with two compressors, the second compressor or lag compressor starts when the lead
compressor is on, the hot gas is at 0%, and the leaving uid temperature is above the setpoint plus
the “compressor on dierenal”. There is also an adjustable “lag compressor on delay” mer.
Before starng either compressor, the compressor with the least amount of runme hours is
considered the lead compressor and the rst to start. When both compressors are running, the
compressor with the most hours is considered the lead compressor and is the rst to stop. The lead
compressor will shut o if the leaving uid temperature drops below the “compressor o
dierenal” and the hot gas valve is at 100% for the “lead compressor o delay” me. The
compressor an-cycle mers are acve with the two compressor units.
There will be two PID controls running simultaneously for determining the posion of the hot gas
valve. One PID output will be based on leaving uid temperature and the other based on a
minimum saturated sucon temperature for freeze protecon. The hot gas valve posion will be
determined by which output is greater. If it is controlling to the saturated sucon temperature to
prevent freezing, a warning will display on the screen that the hot gas is in this mode. Once the
control goes back to setpoint control, the warning will disappear. The saturated sucon temperature
is calculated from the sucon pressure and the type of refrigerant.
The discharge pressure is controlled using an analog output signal to drive a fan for air-cooled units
or a water regulang valve for water-cooled units. The output signal is determined from a PID
algorithm using a discharge pressure transducer as the process variable. The VFD or water
regulang valve is controlled from the analog output to an adjustable discharge pressure setpoint.
The analog output starts at the inial “discharge pressure start” % for a given me delay (discharge
pressure hold). Aer the me delay, it will control to the discharge pressure setpoint via the PID
control. There is also a seng to control the discharge pressure to the most ecient value.
2-3 Standard Features
Mechanical Features
Compressor – Hermec scroll compressors.
Evaporator – Stainless steel copper brazed plate evaporators.