ELECTRICAL CONNECTIONS
HRAT/HRAN8English 10/99
HRAT-HRAN chillers leave the factory completely cabled
and ready for connection to the mains electricity supply
and for the flow switch,remote ON/OFF switch and pump
to be connected to the terminals provided. Electrical con-
nections must be carried out by qualified personnel in
respect of current legislation.
For all electrical work, refer to the electrical wiring dia-
grams in this manual.
You are also recommended to check that:
-the characteristics of the mains electricity supply are
adequate for the absorptions indicated in the electrical
characteristics table below, also bearing in mind the pos-
sible of other equipment being used at the same time.
Power to the unit must be turned on only
after installation work (mechanical, hydraulic and
electrical) has been completed.
All electrical connections must be carried out
by qualified personnel in accordance with current
legislation in the country concerned.
Respect instructions for connecting phase, neu-
tral and earth conductors.
The power line should be fitted upstream with a
suitable device to protect against short-circuits and
leakage to earth, isolating the installation from
other equipment.
Voltage must be within a tolerance of ±10% of
the rated power supply voltage for the unit (for
three phase units, the unbalance between the pha-
ses must not exceed 3%).
If these parameters are not respected, contact the
electricity supply company.
For electrical connections use double insulation
cable in conformity with current legislation in the
country concerned.
Install,if possible near the unit,an appropriate pro-
tection device to isolate the unit from the mains
supply with delayed characteristic curve, contacts
opening by at least 3 mm and an adequate interrup-
tion and differential protection capacity.
If this device is not visible visible from the elec-
trical switchboard of the unit,it should be lockable.
An efficient earth connection is obligatory.
Failure to earth the appliance absolves the manufac-
turer of all liability for damage.
In the case of three phase units ensure the pha-
ses are connected correctly.
Do not use water pipes to earth the unit.
power supply F.L.I. F.L.A. L.R.A. F.L.I. F.L.A. F.L.I. F.L.A. F.L.I. F.L.A. FU1 FU1* FU2 FU3
(kW) (A) (A) (kW) (A) (kW) (A) (kW) (A)
Rated values (1) FUSES
Model
Electrical Compressors Fans Total Max.values (2) Glass 5x20mm 250V
0011 230~50 1,6 8 45,0 0,08 0,37 1,8 8,51 2,08 11,1 2,5A 4A 1A 0,63
0021 230~50 2,0 9,8 58,5 0,16 0,73 2,2 10,71 2,66 14,4 2,5A 4A 1A 0,63
0025 230~50 2,3 12,2 73,0 0,16 0,73 2,5 12,98 3,12 16,8 3,15A 5A 1A 0,63
0031 230~50 2,7 13,0 95,0 0,16 0,74 2,9 14,1 3,6 19,3 4A 5A 2A 0,63
0021 400-3N~50 1,97 3,72 31,0 0,16 0,73 2,24 4,94 2,77 5,5 2,5A 4A 1A 0,63
0025 400-3N~50 2,25 4,09 38,5 0,16 0,73 2,62 5,74 3,3 6,4 3,15A 5A 1A 0,63
0031 400-3N~50 2,6 4,6 43,5 0,16 0,74 2,92 6,23 3,81 7,3 4A 5A 2A 0,63
0041 400-3N~50 3,2 6,2 51,0 0,32 1,46 3,6 7,78 4,57 9,4 4A 5A 2A 0,80
0051 400-3N~50 4,2 7,1 59,5 0,32 1,46 4,5 8,6 5,78 11,5 4A 5A 2A 0,80
0061 400-3N~50 5,0 8,5 70,5 0,32 1,46 5,3 10,09 7,69 14,8 4A 5A 2A 0,80
0071 400-3N~50 6,0 11,2 94,0 0,67 3,3 6,9 14,63 8,4 17,9 10A 15A 5A 1A
0091 400-3N~50 7,5 13,2 116,0 0,67 3,3 8,2 18,0 10,3 21,2 10A 15A 5A 1A
0101 400-3N~50 8,1 15,1 127,0 0,76 3,9 9,0 20,6 11,1 23,1 10A 15A 5A 1A
0121 400-3N~50 10,5 18,9 159,0 0,76 3,9 11,3 24,3 13,3 26,9 10A 15A 5A 1A
F.L.I. Absorbed power
F.L.A. Absorbed current
L.R.A. Compressor start-up current
(1) External air temperature 35°C -Water temperature at evaporator 12/7°C.
(2) Values refer to the lower rated voltage (50 Hz).
These values should be used to dimension protection switches and power cables.
FU1* Fuse to replace FU1 if a storage tank pump + pump on unit are connected (supplied inside the electrical switchboard).
HRAT-HRAN ELECTRICAL DATA