Adams 1_1 online mp series User manual

1_1 ONLINE MP SERIES
UPS
Single phase in / Single phase out
5/6/10kVA
USER MANUAL
UNINTERRUPTIBLE POWER SUPPLY UPS
ENGLISH 1
Table of Contents
1. Important Safety Instruction……………………………………………..2
1.1. An Important Notice……………………………………………………..2
1.2. Storage Instruction……………………………………………………….3
2. Product Introduction……………………………………………………..4
2.1. General Characteristics…………………………………………………..4
2.2. Symbols on the LCD Display Panel……………………………………..5
2.3. Panel explanation………………………………………………………...8
2.4. Communication Port Explanation………………………………………..11
3. Installation and Operation………………………………………………..12
3.1. Unpacking………………………………………………………………..12
3.2. Selecting Installation Position……………………………………………13
3.3. Installation of Accessories Kit…………………………………………...14
3.4. Terminal Block Explanation……………………………………………..15
3.5. Operation Test and Installation Instruction………………………………17
4. Troubleshooting Guide…………………………………………………..28
4.1. Trouble Shooting…………………………………………………………28
5. Bundled Software Installation Guide…………………………………….30
5.1. Hardware Installation…………………………………………………….30
5.2. Software Installation……………………………………………………..30
6. Customer Options Slots………………………………………………….31
6.1. R2E(2nd RS-232 ) card…………………………………………………. 31
6.2. RSE(RS-485) card……………………………………………………….31
6.3. USE(USB) card…………………………………………………………. 31
6.4. DCE(Dry Contact)-B card……………………………………………….32
6.5. SNMP Cards……………………………………………………………..32
7. Specifications…………………………………………………………….33

2
1 Important Safety Instruction
1.1. An Important Notice
1.1.1For parallel system installation, please refer to parallel installation guide.
1.1.2Because of “LITTLE LEAKAGE CURRENTS” generated by EMI Filter of
the UPS, it is necessary to double ensure if the earth of the UPS is properly
grounded before AC mains is connected with.
1.1.3To ensure safety in all applications where a UPS is hard wired to the
Electrical Supply, ensure that the system is installed by a Qualified Electrical
Contractor.
1.1.4The UPS has its own internal energy source (battery). Should the battery
be switched on when no AC power is available, there could be voltage at the
output terminals.
1.1.5Make sure that the AC Utility outlet is correctly grounded.
1.1.6Do not open the case, as there are no serviceable parts inside. Your
Warranty will be void.
1.1.7Do not try to repair the unit yourself; contact your local supplier or your
warranty will be void.
1.1.8Please make sure that the input voltage of the UPS matches the supply
voltage.
1.1.9Use a certified input power cable with the correct plugs and sockets for
the appropriate voltage system.
1.1.10 To eliminate any overheating of the UPS, keep all ventilation openings
free from obstruction, and do not store "things" on top of the UPS. Keep the
UPS 30 cm away from the wall.
1.1.11 Make sure the UPS is installed within the proper environment as
specified. (0-40℃and 30-90% non-condensing humidity)
1.1.12 Do not install the UPS in direct sunlight. Your warranty may be void if
the batteries fail.
1.1.13 Install the UPS indoors as it is not designed for installation outdoors.
1.1.14 Dusty, corrosive and salty environments can do damage to any UPS.
1.1.15 Install the UPS away from objects that give off excessive heat and areas
that are excessively wet.
1.1.16 If liquids are split onto the UPS or foreign objects dropped into the unit,
the warranty will be null and void.
1.1.17 The battery will discharge naturally if the system is unused for any
length of time.
1.1.18 It should be recharged every 2-3 months if unused. If this is not done,
then the warranty will be null and void. When installed and being used, the
batteries will be automatically recharged and kept in top condition.
1.1.19 This UPS supports electronic equipment in offices, telecommunications,
process control, medical and security applications. Non-authorized technician
is not allowed to install the UPS in the following areas.
3
a. Medical equipment directly related to human life
b. Elevator, Metro (Subway) system or any other equipment related to
human safety.
c. Public system or critical computer systems.
1.1.20 Do not install the UPS in an environment with sparks, smoke or gas.
1.1.21 Make sure the UPS is completely turned off when moving the UPS from
one place to another. It might cause electrical shock if the output is not cut
completely.
1.1.22 The UPS offers CVCF (Constant Voltage Constant Frequency) setting
function. To set RT series to be a CVCF shall be required by a qualified
technician.
a. For correct setting and wiring, please contact with your local agent.
b. Do not do it by yourself; otherwise, your warranty will be void.
1.1.23 This UPS has been designed and constructed to protect your assets
from the wide range of power aberrations experienced on Utility power lines
today. It is your insurance for reliable, clean and stable voltage supply. It is
worth taking care to install the system correctly and to have it maintained
correctly by your local dealer.
1.1.24 SAVE THESE INSTRUCTIONS - This Manual Contains Important
Instructions that should be followed during Installation and Maintenance of
the UPS and Batteries.
1.1.25 Intended for Installation in a Controlled Environment.
1.1.26 CAUTION - Adisconnect switch shall be provided by others for ac
output circuit. To reduce the risk of fire, connect only to a circuit provided with
branch circuit overcurrent protection for 30 amperes rating in accordance
with the National Electric Code, ANSI/NFPA 70.
1.1.27 CAUTION - To reduce the risk of fire, unit input connect only to a circuit
provided with branch circuit overcurrent protection for 40 amperes rating in
accordance with the National Electric Code, ANSI/NFPA 70.
1.1.28 Use No. 10 AWG, 60°C copper wire and 22.1 lb-in Torque force when
connecting to terminal block.
1.2. Storage Instruction
For extended storage through moderate climate, the batteries should be
charged for 12 hours every 3 months by plugging the UPS power cord into the wall
receptacle and turn on input breaker on front panel. Repeat this procedure every 2
months under high temperature environment.

4
2 Product Introduction
2.1. General Characteristics
2.1.1True online architecture continuously supplies in your critical device with a
stable, regulated, transient-free pure sine waveAC Power.
2.1.220KHz PWM sine-wave topology yields an excellent overall performance.
The high crest factor of the inverter handles all high-inrush current loads
without a need to upgrade the power rating.
2.1.3Multi-functional LCD/LED panel may display various status of the UPS.
The LED display may show UPS working status, Utility Status and UPS
Abnormal status, in the mean while, the LCD display may show Input/Output
Voltage, Frequency, Load Status, Inner cabinet temperature, and Abnormal
Phenomenon.
2.1.4To protect the unit from overloading, it automatically switches to bypass
mode in 160seconds, app 40msec if loading is at 105%~ 150% of rating and
in case of overloading at 150% of rating, it switches to bypass mode
immediately. It will automatically switch back to inverter mode once overload
condition ceases.
2.1.5Should the output becomes short-circuit, the UPS holds the system and
cuts the output automatically till the short circuit situation is removed
manually.
2.1.6Should the unit become overheated, the internal thermal Switch will detect
the heat and switch to bypass mode and vice versa.
2.1.7Fully digitalized control circuit built in the UPS may upgrade the
functionality Of the UPS as well as reach a high-level protection of the UPS.
Through powerful Communication capability built, it enhances its ability for
remote control and monitoring easily.
2.1.8Maintenance-free sealed-type battery minimizes after-sales service.
2.1.9Providing four different working modes, such as Normal, ECO, CF50 and
CF60, it may widely be used in a variety of applications.
2.1.10 DC-start function makes sure of the start-up of UPS during power
outages.
2.1.11 Revolutionary battery management circuit analyzes battery discharging
status to adjust battery cut-off point and extend the life of batteries.
2.1.12 Intelligent temperature-controlled fan may not only extend the life of the
fan, but also reduce annoying noise because of sudden fan spin. It remains
your office quiet and comfortable as usual.
2.1.13 When UPS is out of order, you may read out the possible fault reason
from the LCD screen directly, which may reduce down unnecessary repair
task a lot.
2.1.14 When UPS is out of order, you may read out the possible fault reason
from the LCD screen directly, which may reduce down unnecessary repair
task a lot.
5
2.1.15 In case the UPS is out of order, Fault status will be shown on the LCD
screen
2.1.16 When the UPS is operated under CF50 or CF60 mode, the
recommended load connected shall be 75% of rated capacity if the input
voltage is 176~280Vac and 50% of the rated capacity if the input voltage is
160~280Vac
2.2. Symbols on the LCD Display Panel
Item Symbol Description
1 LINE Utility or Bypass Source
2 Battery Low
3
Battery Abnormal
4 UPS Overloading
5 UPS Working in specified mode*
6 A Blackout Transfer occurred in UPS Output
7 Bypass Input Abnormal, UPS fails to transfer
to bypass, Bypass Abnormal at ECO mode
8 Utility Input Abnormal
9 OFF UPS Shutoff
10 LINE OFF UPS Abnormal Lock
11 UPS Flow Chart
12 4 Digits Measurement Display

6
13 Indicate the item desired to be measured
14 UPS ON Switch or Alarm Silence
15 UPS OFF Switch
16 Previous Page or Setting Change
17 Next Page
18 Special Function Log in /out
19 Enter or Reconfirmed
20 Utility Input Normal LED
21 Bypass Input Normal LED
22 UPS under Redundancy Mode
23 UPS under ECO Mode
24 UPS Fault or Abnormal Warning LED
25 EPO Emergency Power Off
26 Er05 Battery Weak or Dead
27 Er06 Output Short Circuit
28 Er10 Inverter Over-current
7
29 Er11 UPS Overheat
30 Er12 UPS Output Overloading
31 Er14 Fan Error
32 Er15 Wrong Procedure to Enter Maintenance Mode
33 Er16 Output Parameters Set Error in Parallel
System
34 Er17 ID Numbers are in conflict in Parallel System
or ID number Error in single unit
35 Er21 Parallel communication error ( communication
wire disconnected or failure to find ID1 UPS )
in parallel system
36 Er24 CVCF mode with Bypass input
37 Er27 The UPS must be operated in normal mode in
parallel system
38 Er28 Bypass Overload Time out and cut off output.
39 Er31 The settings of both control board and driver
board are not matched each other.
40 Er33 Isolated Transformer Overheat
41 Er** Other Error code
*The specified modes include Normal mode, ECO mode, CVCF mode, etc..

8
2.3. Panel explanation
2.3.1Front Panel Function Explanations
LCD Display
Green LED steadily lights up to indicate that
the utility input voltage is within the window;
the LED flashes flickeringly to indicate that
the utility input voltage is within the
acceptable window
. Green LED lights up to indicate Bypass
Input is normal.
Green LED lights up to indicate the UPS
has the capability to run under redundancy
mode.
UPS is working under ECO ( Economic )
Mode
UPS fault or Abnormal
UPS ON/Alarm Silence
UPS OFF Switch
Special Functions log in/out
Go to next page
Go to Previous page or change the setting of the UPS
To reconfirm the change of UPS Setting
9
2.3.2Rear Panel Explanation
5/6k PM
10K PM
CB 1
Utilit y Input
Breaker
L12N1G1L21N22G2
OUTPUT INPUT
ON
OFF S1
Ext.Battery
ParallelWork Comm.
TNVCommunication Network
Bus Not I nten ded to
EPO
RS232
+
-
G
A
BNI
FDCG L E
P
RS232
Not I nten ded t o
TNV Communication
Networ k
EPO
-
G
+
SLOT
BATTERY
EXT.
INPUT
BREAKE R
INPUT
BREAKE R
UTILITY
BYPASS
TB1
TB2
ONOFF
S1
C
A
B
FL
GIJ
D
N
P
5K/6K with batt
Model
RS232
UtilityInput
Breake r
Slot
INPUT
L12-N1:UTILITYINPUT
G1 : INPUT EARTH
OUTPUT L1 2N1G1L21N22G2
GROUND
L21-N22:UPS OUTPUT
G2 :O UTPUT EARTH
GROUND
EPO
PAT. NO.:
US6906501,TW202668
ParallelWorkComm.
TNVCommunic ationN etwork
BusNot Int ended to
Ext.Battery
+
-
G
A
CD
G
N
F
L
P
I
B

10
A RS232 Port
B Terminal Resistor for Parallel function
C CAN Bus Connection Port for Parallel System
D Customer Options Slot 1
E Customer Options Slot 2
F Cooling Fan
G External Battery Connector
I Utility Input Breaker CB1
L Input/Output Terminal Block
N EPO(Emergency Power Off): Short to enable the function
P Air Ventilation Hole
11
2.4. Communication Port Explanation
The Communication port on the UPS provides true RS232 type to
communicate with UPS software to remote monitoring the power and UPS status.
With optional interfaces cards, which contains R2E(2nd RS232 plus EPO),
RSE(RS485 plus EPO), USE(USB plus EPO), DCE(Dry Contact plus EPO), as well
as SNMP/ card, you may combine them according to your demand. However, the
R2E card, RSE card and USE card are prohibited to be used simultaneously.
The bundled software of the UPS is compatible with many operating systems
such as Windows 98, & 2000, ME, NT and XP.
When the optional interface cards are used with onboard RS232 port in
communication, the shutdown command at the DCE card & also the EPO signals
will get the highest priority in control command, then the SNMP/WEB card, then
R2E, RSE and USE get the lowest priority.
2.4.1True RS232 type
2.4.1.1 The RS232 interface settings
The RS232 interface shall be set as follows:
Baud Rate 2400 bps
Data Length 8 bits
Stop Bit 1 bit
Parity None
2.4.1.2 The Pin Assignments of true RS232 type
The Pin Assignments of true RS232 type are illustrated as follows:
1
2
3
4
5
6
7
8
9
Pin 3: RS232 Rx
Pin 2: RS232 Tx
Pin 5: Ground

12
3 Installation and Operation
The packing condition and the external outlook of the unit should be inspected
carefully before installation. Retain the packing material for future use.
3.1. Unpacking
3.1.1Unwrap the pack of UPS.
3.1.2Take the UPS out of the PE foam.
3.1.3Standard Package includes:
¾1 set of Quick Start Manual
¾1 set of User's Manual
¾1 set of UPS communication software with RS232 cable
¾1 set of accessories pack
3.1.4Package for the UPS with Isolation transformer & dual input:
¾Ditto, but with additional 3pcs wire No 7.
3.1.5Package for the UPS without isolation transformer but dual input:
¾Ditto, but with additional 1pcs wire No. 7.
(p.s. Wire No. 7 is to be used at the input/output terminal block of the UPS.
Please refer to Chapter 3.4 for installation.
A1 A2 A3
S1 S2 S3 S4
B1 B2 B3
x8 x6x4x2
x2 x2 x2
x1x4x4
for 2U
for 3U
PM10K only
X1A1
X1A2
X
1
A
3
Power Module
model
13
3.2. Selecting Installation Position
It is necessary to select a proper environment to install the unit, in order to
minimize the possibility of damage to the UPS and extend the life of the UPS.
Please follow the advice below:
1. Keep at least 30cm (12 inches) clearance from the rear panel of the UPS to
the wall.
2. Do not block the air-flow to the ventilation openings of the unit.
3. Please check the installation site to avoid overheat and excessive moisture.
4. Do not place the UPS in an environment near dust, corruptive or salty material
or flammable objects.
5. Do not expose the UPS to outdoors.
30%~90%
40

14
3.3. Installation of Accessories Kit
B1 B2 S4 B1 B3 S4
S3
S3S3
15
3.4. Terminal Block Explanation
L11L12N1G1L21L23N21L22N22G2
OUTPUT INPUT
BYPASS
INPUT
UTILITY
INPUT
L11-N1: BYPASS INPUT
L12-N1: UTILITY INPUT
G1 : INPUT EARTH GROUND
N22, L22, N21, L23, L21: UPS OUTPUT
G2 : OUTPUT EARTH GROUND
(DIM TYPE ONLY)
(DIM TYPE ONLY)
Rack 5/6K
TB1
TB2
Rack 10K
Tower model

16
●L12-N1: the terminal for Utility Input to provide the power source when theUPS is
working under Utility mode.
●G1: the terminal for UPS Input Ground.
●L21、L23、N21、L22、N22: the terminals for UPS Output.
●G2: the terminal for UPS Output Ground.
●Use Mounting Cable Tie to fix cables.
. Please refer to the specs of input current, output current and recommended
conductors listed as below :
a. AC input and output
b. Battery
input
Model Maximum Current Conductor Section
5/6KVA 33A
AWG #9
10KVA 54.3
AWG #7
ExternalBattery
ExternalCharger
T1
Tower model 6K Rack Model
10K rack model
5/6K model
17
Model Maximum Current Conductor Section
5/6KVA 25A
AWG #10
10KVA 41A
AWG #10

18
3.5. Operation Test and Installation Instruction
3.5.1Start Up in Normal Mode
3.5.1.1 Open the terminal block cover on the rear panel (refer to 2.3.2) Before
start the installation, please make sure the grounding is connected properly.
3.5.1.2 Make sure Utility breaker, UPS’ Utility breaker is On “Off” position.
3.5.1.3 Make sure the voltage of Utility matches with the input voltage window of
the UPS.
3.5.1.4 Connect the Utility separately to the terminal blocks of UPS’ Utility and
Bypass Inputs. Switch on the Power Breaker of the distribution panel and the
breakers of the UPS’ Utility and Bypass Inputs, and then the UPS starts up.
Green LEDs & light up to show the Utility and Bypass Inputs are
normal and the LCD display with parallel function will illustrate from drawing
A1, drawing A2 to drawing B. Otherwise the LCD display will illustrate from
drawing A2 to drawing B.
A1.
A2.
B.
19
3.5.1.5 Then, the UPS is on Bypass Mode now and it will proceed self-test
automatically. If there is no abnormal message occurred, it means the pre-
startup of the UPS is successful and the charger starts to charge the
batteries.
3.5.1.6 Press the UPS On Switch for approx. 3 seconds, then the Buzzer
sounds twice and the LCD display changes from drawing B to drawing C.
3.5.1.7
C
3.5.1.8 Then, the UPS is under self-test mode again, the LCD display will
illustrate from drawing C to drawing D and remain approx. 4 seconds under
battery mode, then illustrate from drawing E1 to drawing F if the self-test is
successful.
D
* It shows “test”.
E1
* It shows “OK” in self-test
E2
* It shows “Fail” in self-test

20
F
* It shows “220Vac” in Utility Input.
3.5.1.9 In case of failure in self-test, the LCD display will illustrate from Drawing
D to drawing E2, then an error code or error status will be shown on the
screen.
3.5.1.10 Your start-up operation of the UPS is completely now. Make sure the
UPS is plugged onto the wall receptacle for charging at least 8 hours and the
batteries of the UPS are fully charged.
3.5.2Start-up in Battery Mode (Cold Start)
3.5.2.1 Make sure the UPS you have has already been installed at least 1
set(20pcs) of 12V/7AH or 12V/5AH batteries.
3.5.2.2 Push the UPS On Switch once for approx. 5 seconds to awake the
ups, and then the buzzer sounds twice. The LCD display will illustrate from
drawing A to drawing G, and keep awake for approx. 15 seconds.
3.5.2.3 Press the UPS On Switch of the UPS again for about 3 seconds till
the LCD display illustrates from drawing G to drawing H, then the UPS will
be in self-test Mode. The UPS may offer energy to the output in a minute,
and the LCD display illustrates as drawing I. In case of failure in pushing the
UPS On Switch in 15 seconds, the UPS will automatically turn off. You then
have to go through step 3.5.2.1 to 3H3.5.2.3 once again.
G
* It shows “Off”, which means the UPS pre-start is successful.
21
H
* It shows Utility input is “0” and Utility Abnormal.
I
3.5.3
80BCheck Measured Values & Figures detected by UPS
3.5.3.1 If you would like to check the measured values & figures detected by the
UPS, please use scroll up and scroll down key pads. When you
use scroll down key pad, the LCD display will illustrate as Drawing C(Voltage
from Utility Input) ÆDrawing I1(Voltage from Bypass Input) ÆDrawing
J(Frequency from Utility Input) ÆDrawing K(Frequency from Bypass Input)
ÆDrawing L(UPS Output Voltage) ÆDrawing M(UPS Output Frequency)
ÆDrawing N(UPS Output Load %)ÆDrawing O(UPS Battery Voltage)
ÆDrawing P(UPS Inner Temperature).
I1
* It shows voltage comes from Bypass Input
J
* It shows frequency from Utility Input.

22
K
* It shows frequency from Bypass Input.
L
* It shows UPS output Voltage.
M
* It shows UPS output frequency.
N
* It shows UPS output load level(%)
O
* It shows Battery Voltage.
23
P
* It shows UPS Inner Temperature
3.5.4UPS Default Data and Special Function Execution
3.5.4.1 After UPS completely starts up, press key pad to change the LCD
display screen to drawing Q1.
Q1
* It shows buzzer “On”.
Q2
* It shows buzzer “Off”.
3.5.4.2 Press key pad to scroll down the screen and check the UPS
settings. The LCD display will show in consequence between Drawing
Q1(buzzer) ÆDrawing R1(Self-test) ÆDrawing S1(Bypass Voltage
Windows) ÆDrawing T(Output Frequency Synchronization Window)
ÆDrawing U(Inverter Output Voltage) ÆDrawing V1(UPS Operation Mode)
ÆDrawing W(Output Voltage Micro Tune Value) ÆDrawing X(UPS Id)
ÆDrawing Y(Parallel function status).

24
R1
* It shows self-test is NOT “on”.
R2
* It shows self-test is “On”.
S1
* It shows Bypass Voltage is adjusted to narrow one.
S2
* It shows bypass voltage is adjusted to wider one.
T
* It shows Frequency Window is +/-3Hz.
25
U
* It shows inverter output voltage.
V1
* It shows the UPS is operated in “normal mode”.
V2
* It shows the UPS is operated in “Eco mode”.
V3
* It shows the UPS is operated in “CVCF 50Hz mode”.
V4
* It shows the UPS is operated in “CVCF 60Hz mode”.

26
W
* It shows Output Voltage Adjustment % from 0% to 3% or -0% to -3%.
X
* It shows UPS Identification Number.
Y
* It shows the UPS is in the No. 1st of parallel systems.
3.5.4.3 Press scroll up key pad, you may execute special functions. The
Functions includes buzzer ON (as drawing Q1), or buzzer OFF (as drawing
Q2, Alarm silence for UPS Warning) and self-test OFF (As drawing R1) or
self-test ON. (as drawing R2. UPS will execute battery test for 10 seconds. If
the self-test is successful, it will show as Drawing E1; otherwise, it will show
as drawing E2 & error message in the same time.)
3.5.5UPS Default Settings and their alternatives
3.5.5.1 Make sure the UPS is not “On” yet. Press On Switch and scroll
down key pads simultaneously for approx. 3 seconds, the buzzer will
sound twice, the LCD display screen shows as drawing Q1, then the UPS is
under setting mode now.
3.5.5.2 To scroll down the LCD screen, you may refer to Chapter 3.5.4.2
3.5.5.3 Except Buzzer(as drawing Q1 & Q2) and Self-test(as drawings R1 & R2),
all the rest default settings may be changed by pressing scroll up key
pad.
27
3.5.5.4 Drawings S1 and S2 mean the bypass input acceptable window, it can
be 184Vac~260Vac or 195Vac~260Vac.
3.5.5.5 Drawing T means the bypass frequency window of the Inverter Output,
the acceptable setting values are ±3Hz and ±1Hz.
3.5.5.6 Drawing U means the acceptable Inverter Output Voltage, of which
voltage is 200Vac, 208Vac, 220Vac, 230Vac, or 240Vac.
3.5.5.7 Drawing V1, V2, V3 and V4 mean the operation modes of the UPS, of
which alternative is Online, Eco(Economic) mode, fixed 50Hz Output or fixed
60Hz Output.
3.5.5.8 Drawing W means the adjustments of the Inverter Output, which may be
calibrated as 0%, +1%, -1%, +2%, -2%, +3%, or -3%.
3.5.5.9 Drawing X means a specified address & position of the UPS when the
UPS is in Parallel mode. The settable numbers are from 1st to 4th. The
number must be 1st if the UPS is not in parallel.
3.5.5.10 Drawing Y means the parallel function status. The “P 01” means parallel
function disabled and the “P02” means parallel function enabled.
3.5.5.11 When all the setting changes are done, you have to press enter key
Pad to save all the changes when the LCD screen shows as drawing Z, then,
the LCD screen will show as drawing AA to complete the setting changes. If
you don’t want to change those settings, you may press “OFF” key pads
for 5 seconds, then the LCD screen turns to Drawing AA directly, which
means your setting changes are invalid.
Z
* Please press Enter key to save data.
AA
* It shows the UPS is locked.
3.5.5.12 Turn Off the breaker of Utility Input.
3.5.5.13 Your Setting changes are complete.

28
3.5.6UPS Is Off Due to Unknown Reason and Its Trouble Shooting
3.5.7
3.5.7.1 If there is a serious abnormal condition occurred, the UPS will lock it
itself in “OFF” position as shown in drawing AA and a abnormal message will
show on the LCD screen.
3.5.7.2 After 3 seconds, all messages will be locked except Bypass
messages(LED & LCD ). In case the Utility is abnormal after
the UPS is locked, the LED will be extinguished and the LCD will
be shown on the LCD screen.
3.5.7.3 To release the UPS lock, please proceed the followings:
3.4.6.3.1. Check those error messages recorded.
3.4.6.3.2. Check to see Chapter 2.2 to trouble shoot the problem of the UPS.
Otherwise, consult your local distributor for service.
3.4.6.3.3. Press Off key pad for 5 seconds and buzzer will sound twice.
3.4.6.3.4. Turn Off the Breaker of Utility Input.
3.4.6.3.5. The UPS lock problem is solved now, but you shall contact with your
Local distributor to make sure the error message shown is solved.
3.5.8Shut Off
3.5.8.1 Press
Off key pad for about 5 seconds, the Inverter output will be
turned off, then the output load is supplied by Bypass loop and the LCD
screen shows as drawing B.
3.5.8.2 Turn Off the breaker of Utility Input.
3.5.8.3 The UPS is turned off completely.
29
4 Troubleshooting Guide
4.1. Trouble Shooting
When the UPS malfunctions during operation, you may check the followings:
a. Are the wirings of input and output correct?
b. If the input voltage of the Utility is within the input window of the UPS?
In case problems or symptoms still exist, please proceed the followings for
proper adjustment. Should the problem persists, please contact your local
distributor for help.
Situation Check Items Solution
UPS Red Fault LED
lights up Check the error code
shown on the LCD
screen
1.Er05, &
2.Er06, Er10, Er12,
Er28 &
3.EPO
4.Er11, Er33
5.Er14
6.Er15
7.Er16, Er27
8. Er21
9.Er24
10.other error code
1.Check to see if the battery connection
is properly done, then re-charge the
batteries for 8 hours to see whether
the UPS may backup normally;
otherwise, consult your local
distributor right away.
2. If the CB3 is tripped, please turn off
the UPS completely and keep the
CAM switch at position INV before
pressing CB3. Then remove some
uncritical load at the UPS output end. If
any damage of the coating of AC
power cord, please replace a new one.
3. Remove the short circuit occurred at
the EPO terminal.
4. Remove the objects blocked onto the
ventilation holes.
5. Check the cooling FANs on rear panel
are working normally.
5. Make sure the UPS is operated
normally. If it is on CVCF mode, you
have to turn off and turn on the UPS
again.
6. All of parameters except ID Number in
the parallel UPS must be same. Please
refer chapter3.5.5 to set them again
7. Reconnect the RJ-45 wire or set a
UPS with ID=1.
8. When the UPS is on CVCF mode, it is
prohibited to have bypass input. You
have to turn off the UPS and bypass
input and re-start the UPS.
9. Consult your local distributor for help.

30
UPS fails to offer
battery backup or its
back up time is shorter
than its calculation.
If the backup time is still too
short after 8 hours of charge,
please contact your local
distributor for battery
replacement.
UPS locks itself and it
can not be turned off. Please refer to chapter 3.5.6 to
trouble shoot the problem;
otherwise, consult your local
distributor for help.
31
5 Bundled Software Installation Guide
5.1. Hardware Installation
1. Connect the male connector of RS232 cable to the UPS communication port.
2. Connect the female connector of the RS232 cable to a dedicated RS232
port of the computer.
3. For optional interface cards, you may refer to Chapter 6 for installation.
5.2. Software Installation
Please refer to the user’s manual of the software for installation.

32
6 Customer Options Slots
6.1. R2E(2nd RS-232 ) card
6.1.1CN1 is for RS232 DB9
6.1.2For communication protocol, please
refer to Chapter 2.4.1
6.1.3Installation Position: slot1(CHA-CN4)
or slot 2(CHB-CN5).
6.2. RSE(RS-485) card
6.2.1CN1 is for the function of the terminal resistor. Short pin1-2 to enable the
function and short pin2-3 to disable it.
6.2.2 CN2 for RS485 and CN3 for remote power.
6.2.3Definition
6.2.4Installation Position: slot1.
6.3. USE(USB) card
6.3.1CN1 for USB.
6.3.2Definition
6.3.3Comply with USB version 1.0,1.5Mbps
6.3.4Comply with USB HID Version 1.0.
6.3.5The Pin Assignments of the USE card:
6.3.6Installation Position: slot1(CHA-CN3)or slot 2(CHB-CN4)
1 ÆVCC (+5V)
2 ÆD−
3 ÆD+
4 ÆGround
1 2
CN3
1 2 3
CN2 1 ÆGround
2 ÆA/Data+
3 ÆB/Data-
1 ÆAC+
2 ÆAC-
33
6.4. DCE(Dry Contact)-B card
6.4.1The pin assignments of 10-Pin Terminal:
12345678910
Pin 1: UPS on Bypass mode.
Pin 2: Utility Normal (Normal close contact)
Pin 3: Utility Normal (Normal open contact)
Pin 4: Inverter On
Pin 5: Battery Low
Pin 6: Battery Bad or Abnormal
Pin 7: UPS Alarm
Pin 8: Common
Pin 9: Shutdown UPS positive(+ ) signal
Pin 10: Shutdown UPS positive(- ) signal
6.4.2The shutdown function will be activated, after a +6~+25Vdc is put
between pin9 and pin10 for 5 seconds.
6.4.3The capacity of each relay contact is 40Vdc/25mA.
6.4.4Installation Position: slot1(CHA-CN7) or slot 2(CHB-CN8).
6.4.5Flexible signal output for N.C.(Normal close) or N.O.(Normal open)
contact by shorting pin1-2 or pin2-3 from JP1-5.
6.4.6The shutdown function will be enabled in 1 minute after blackout occurs if
the pin1-2 of both CN1 and CN6 be shorted by cap. Or, the shutdown
function can only be enabled by pin9-10 of CN3 if the pin2-3 of both CN1and
CN6 be shorted by cap. (Refer to 6.4.2)
6.5. 25BSNMP Cards
6.5.1
104BSNMP/WEB card
6.5.1.1 For installation, please
refer to the user’s manual
attached with the card. .
6.5.1.2 Installation
6.5.1.3 Position: slot 2(CHB).
6.5.2
105BNet Agent II Internal Card
6.5.2.1 For installation, please
refer to the user’s manual
attached with the card.
6.5.2.2 Installation
6.5.2.3 Position: slot 2(CHB).

34
7 Specifications
Model 5000VA/6000VA 10000VA
INPUT
Voltage Window 160~280Vac*
Frequency 45 ~ 65 Hz
Phase/Wire Single, Line + Neutral + Ground
Power Factor Up to 0.99 at 100% Linear Load
Current THD <5% at 100% Linear Load
OUTPUT
Voltage Window 220/230/240Vac Selectable(208/120Vac
optional)
Voltage Adjustment ±0%; ±1%; ±2%; ±3%
Voltage Regulation ±2%
Capacity 3500W/4200W 7000W
Rated Power Factor 0.7 Lagging
Wave Form Sine Wave, THD<3%(no load to full load)
Frequency Stability ±0.2%(Free Running)
Frequency Regulation ±1%; ±3%
Transfer Time 0ms
Crest Factor 3:1
Efficiency(AC to AC, Normal) Up to 91%
Efficiency(AC to AC, ECO) Up to 97% Up to 93%
DC Start Yes
BATTERY
Quantity 20pcs
Voltage 240Vdc
Recharge Time 4 hours to 90% 5 hours to 80%
DISPLAY
Status On LED + LCD Line Mode, Backup Mode, ECO Mode, Bypass
Supply, Battery Low, Battery Bad/Disconnect,
Overload, Transferring with interruption & UPS
Fault.
Readings on LCD Input Voltage, Input Frequency, Output
Voltage, Output Frequency, Load Percentage,
Battery Voltage & Inner Temperature.
Self-Diagnostics Upon Power-on, Front Panel Setting &
Software Control, 24-hour routine checking
35
ALARMS
Audible and Visual Line Failure, Battery Low, Transfer to Bypass,
System Fault Conditions
PHYSICAL power module 440x88x680 440x176x680
Dimensions
(HxWxD)mm With batteries 440x176x680 x
Input/Output Connection Hardwire
External Battery Connection Plug-in & Play
Power module 33 35Net Weight
(Kgs), With battery 55 x
Leakage Current < 3mA at Full Load
Marks CE, cUL, UL
***These cards are not suitable to use simultaneously.

36
192321132015003
Table of contents
Other Adams UPS manuals