Airia LIFEBREATH RNC200 User manual

69-RNC 072717
RNC200
Setting a new standard for
energy efficient, clean air homes
511 McCormick Blvd
London, Ontario Canada N5W 4C8
519.457.1904
General Info / Tech Support:
1.855.247.4200
www.lifebreath.com

etting to Know your RNC Series HRV
Selecting the Ventilation Rate that is right for You
How the Dehumidistat Works
lossary and Additional Information
Warranty........................................................................................3
The Lifestyle RNC Digital Control...............................................4
The Lifestyle Dehumidistat
The Lifestyle RNC Ventilation Control........................................5
Optional Timers ............................................................................6
Maintenance Routine for your HRV .............................................7
Technical Data - Model RNC200 ...............................................11
Engineering Data - HRV.............................................................16
Installation Methods and Installation Diagrams ....................17-20
Installation
Suspending the Unit with the Adjustable Hanging Straps ..........21
Drain Connection and rilles .....................................................23
rille Fittings .............................................................................24
Weatherhood Installation ............................................................25
Installation of the Main Control..................................................26
Interlocking HRV to an Airhandler/Furnace Blower
Setting “Standby” when using a Main Control
Operating the HRV without a Main Control and
Adding Dry Contacts..................................................................28
Installer Selectable High Speed Settings.....................................29
Balancing Air Flows ...................................................................30
Balancing the Air Flows with a Pitot Tube.................................31
Air Flow Balancing using the Door Ports..............................32-33
Balancing Dampers
Balancing Instruments and Kits ..................................................34
Troubleshooting your HRV System............................................35
Wiring Diagram. .........................................................................36
2
Table of Contents
MPORTANT -
PLEASE READ TH S MANUAL
BEFORE NSTALL NG UN T.
CAUTION
Before installation, careful consideration must be
given to how this system will operate if connected
to any other piece of mechanical equipment, i.e. a
forced air furnace or air handler, operating at a
higher static. After installation, the compatibility of
the two pieces of equipment must be confirmed, by
measuring the air flows of the HRV, by using the
balancing procedure found in this manual.
NEVER install a ventilator in a situation where its
normal operation, lack of operation or partial
failure may result in the backdrafting or improper
functioning of vented combustion equipment.
WARNING
• Disconnect the power from the unit before
cleaning or servicing.
• To prevent electrical shock, it is extremely
important to confirm the polarity of the power line
that is switched by the safety (disconnect) switch.
The hot line (black) is the proper line for switching.
Use either a voltmeter or test lamp to confirm the
absence of a voltage between the disconnect
switch and ground (on the cabinet) while the door
is open. This procedure must be followed, as
dwellings are occasionally wired improperly.
Always enure the proper grounding of the unit.
• Do not apply electrical power to the unit until after
the completion of the installation (including the
installation of low voltage control wiring).
• Ensure the nstallation and wiring is in
accordance with CEC, NEC, and local electrical
codes.
• Due to ongoing research and product
development, specifications, ratings and
dimensions are subject to change without notice.
•Plug the unit into a standard designated (120 VAC)
electrical outlet with ground.
•The use of an extension cord with this unit is not
recommended. f the installation requires further
wiring, have a licensed electrician make all of the
electrical connections. The recommended circuit is a
separate 15 amp/120 volt circuit.
• Due to ongoing research and product
development, specifications, ratings and
dimensions are subject to change without notice.

Disconnect the power from the unit before cleaning or servicing.
To prevent electrical shock, it is extremely important to confirm the polarity of the power line that is switched by
the safety (disconnect) switch. The hot line (black) is the proper line for switching. Use either a voltmeter or test
lamp to confirm the absence of a voltage between the disconnect switch and ground (on the cabinet) while the
door is open. This procedure must be followed, as dwellings are occasionally wired improperly. Always ensure the
proper grounding of the unit.
Warning
Due to ongoing research and product development, specifications, ratings, and dimensions are subject to change
without notice. Refer to www.LIFEBREATH.com for the latest product information.
Note
Selecting the Ventilation Rate That is Right for You
The modes of operation and speeds are used to adjust your indoor ventilation rate. Experiment with the
ventilation levels in your home to evaluate the ideal amount of ventilation to suit your home and
personal preferences. Operational modes available to you will depend on the main control that is installed.
Some features and modes may be unavailable to you.
Recirculation
Recirculates existing household air without introducing fresh air. Recirculation modes (II and V) are not
applicable if your HRV is connected to a forced air system, since your forced air system already circulates the
household air. Recirculation modes are unavailable on some models.
I. Continuous Ventilation
This mode of operation provides continuous ventilation within the home. You may, for example, select
Continuous Ventilation at low speed for normal operation and increase to high speed during increased
activity levels, such as cooking and showering, etc.
II. 20 Minutes On, 40 Minutes Recirculation 20/hr 40/hr
This mode ventilates for 20 minutes and recirculates the household air every 40 minutes each hour. This
mode is not applicable if your HRV is connected to a forced air system.
III.20 Minutes On, 40 Minutes Standby 20/hr 40/hr
This mode of operation provides 20 minutes of ventilation each hour. You can use this ventilation mode at
low speed for low household activity levels or when the home is unoccupied.
IV. 10 Minutes On, 50 Minutes Standby 10/hr 50/hr
This mode of operation provides 10 minutes of ventilation each hour. You can use this ventilation mode at
low speed for low household activity levels or when the home is unoccupied. This mode is useful when
20/40 mode is providing too much ventilation.
V. Continuous Recirculation
or
This mode continuously recirculates your household air (no ventilation). This mode is not applicable if your
HRV is connected to a forced air system.
VI. Continuous Low Fan Speed LO
This mode will operate the fan in low speed continuously at the selected operating mode (Ventilation or
Recirculation).
VII. Continuous High Fan Speed HI
This mode will operate the fan in high speed continuously at the selected operating mode (Ventilation or
Recirculation). This mode is useful when occupancy in the home or activity is high for an extended period
of time.
3

How the Dehumidistat Works
Only the DXPL02, BC02 and BC03 controls are equipped with an adjustable Dehumidistat.
High indoor humidity levels, during the heating season, have become a problem in many well
insulated, tight homes, excessive condensation on the window is a visual sign of high indoor
humidity levels. High indoor humidity levels can result in mold and mildew and the eventual
degradation of the building structure itself.
Your HRV reduces indoor humidity levels when the outdoor air is drier than the indoor air. These
conditions usually occur during the heating season when outdoor temperatures are less than 15oC
(59oF). During the heating season, the operation of the HRV may reduce indoor humidity levels
sufficiently to eliminate the need for further dehumidification. If your home requires further
dehumidification, use the Dehumidistat feature if available located on the main control. This
feature aggressively addresses high indoor humidity levels by initiating high speed ventilation when
the indoor humidity levels rise above the adjustable set point on the control. Refer to the "Setting
the Dehumidistat" section of either the DXPL02, BC02 or BC03 control instructions on how to set
the Dehumidistat, depending on which control you have installed. The Dehumidistat function
should be set to off for all seasons except the heating season because a dehumidifying effect
occurs only when the outdoor air is dryer than the indoor air.
The DXPL02, BC02 and BC03 controls have an adjustable Dehumidistat which can be set to achieve
a further dehumidification effect from your HRV. High speed ventilation will be initiated upon
exceeding the Dehumidistat set point regardless of the mode and speed of operation. Once the
humidity in the house is reduced, the HRV will revert back to its previous setting.
We suggest operating the HRV for the first few days without use of the Dehumidistat function to
observe if a further dehumidification effect will be required. The Dehumidistat operates in % of RH
(relative humidity) with 60 being high and 20 being low. If after a few days, further
dehumidification is required (the house is still too humid), set the humidity level to a lower
amount.
The average person is comfortable between 30% and 50% RH. The Dehumidistat should be set to
off for all seasons except the heating season.
Dehumidistat Disable automatically disables the dehumidistat function on the main control when outdoor
temperatures exceed 15oC (59oF) for a full 24 hour period. All other HRV features and functions operate normally
while the dehumidistat function is disabled.
Dehumidistat Re-Enable automatically re-enables the dehumidistat function if either the outdoor temperature
drops below 15oC (59oF) for a full 24 hour period or if the HRV is reset (unplugged for 30 seconds).
4
Dehumidistat Notes

The Lifebreath Ventilation Control 99-BC02
The Lifebreath Ventilation Control offers advanced features to control your home's ventilation.
Key Features:
2 speed fan setting (LOW / HIGH)
Standby setting (fan OFF)
Electronic Dehumidistat
Compatible with 99-DET02 Wireless
Timers
Slim-line design
Connect to 3 wire 20 gauge low voltage
wire
Only one main control can be installed on your system.
Timers will not function when mode of operation is set to “OFF”, unless specifically installed for that function.
Humidity
Setting
Fan Speed
Indicator
ON/OFF Light
Fan Speed
ON/OFF Button Button
Dehumidistat
Button
5
BC02 Operating Instructions:
Turning on the Control
Press and release the ON/OFF button . The
light above will illuminate.
Setting the Ventilation Speed
Press and release the Fan button to select LOW or HIGH fan speed. The corresponding “Indicator
Light" will illuminate. If both LO and HI indicator lights are off, the fan is OFF but will turn ON if
required by the Dehumidistat or remote Timer (if installed).
Humidity Control
Your unit will reduce indoor humidity when outdoor humidity levels are lower than indoor humidity
levels. This feature is only effective when the outdoor temperature is below 59˚F (15˚C).
Setting the Dehumidistat
Press and release the Dehumidistat button until the Dehumidistat Light is at the desired setting.
After a few seconds the Dehumidistat light will either flash or be on continuous.
A flashing light indicates the humidity level is higher than the setting and the unit is operating on
high speed ventilation. A continuous light indicates the humidity level is lower than the setting. Refer
to the unit's Home Owner’s manual for instructions on how the Dehumidistat works.
The Dehumidistat will override the current speed setting to HIGH speed.
The Dehumidistat function can be turned OFF by pressing the button until no Dehumidistat light
is on.
Note - Only 1 Dehumidistat should be installed in a system.
ATTENTION

ATTENTION
Only one main control can be installed on your system.
Recirculation is not available on all models.
Timers will not function when mode of operation is set to “OFF”, unless specifically installed for that function. (See
Installation Guide for other options.)
The Lifebreath Ventilation Control 99-BC03
The Lifebreath Ventilation Control offers advanced features to control your home's ventilation.
Key Features:
Continuous LOW fan speed operation
Electronic Dehumidistat
3 modes of operation:
•Ventilation
•Recirculation
•20/40 mode
Compatible with 99-DET02 Wireless Timers
Slim-line design
Connect to 3 wire 20 gauge low voltage
wire
BC03 Operating Instructions:
Turning on the Control
Press and release the ON/OFF button . The light
above will illuminate and the fan will turn on to
LOW speed.
Humidity Control
Your unit will reduce indoor humidity when outdoor humidity levels are lower than indoor humidity levels.
This feature is only effective when the outdoor temperature is below 59˚F (15˚C).
Setting the Dehumidistat
Press and release the Dehumidistat button until the Dehumidistat Light is at the desired setting. After a few
seconds the Dehumidistat light will either flash or be on continuous.
A flashing light indicates the humidity level is higher than the setting and the unit is operating on high speed
ventilation. A continuous light indicates the humidity level is lower than the setting. Refer to the unit's Home
Owner’s manual for instructions on how the Dehumidistat works.
The Dehumidistat will override the current fan speed setting to high fan speed.
The Dehumidistat function can be turned OFF by pressing the button until no Dehumidistat light is on.
Note - Only 1 Dehumidistat should be installed in a system.
Setting 20/40 Mode
To activate 20/40 mode, press and release the Mode button until the "Indicator Light" below 20/40 is
illuminated.
20/40 mode is a repeating cycle. The fan will run at LOW speed for 20 minutes, then turn OFF for 40 minutes.
Some units are equipped to Recirculate air in your home during the 40 minute cycle with no Ventilation. The
control will automatically detect this feature and Recirculate air during the 40 minute cycle at LOW fan speed.
Recirculation Mode
Some units are equipped to Recirculate the air in your home without Ventilating.
"Indicator To activate Recirculation mode, press and release the Mode button until the Recirculation
Light" in ON. Recirculation is in LOW fan speed.
Humidity
Setting
20/40 Mode
Indicator
Recirculation
Mode Indicator
LOW Fan Speed
Indicator Light
ON/OFF Button Mode Button
Dehumidistat
Button
6

7
Attention
Only one main control can be installed on your system.
Recirculation is not available on all models.
Timers will not function when mode of operation is set to “OFF”, unless specifically installed for that function. (See
Installation Guide for other options.)
The Lifebreath Ventilation Control 99-BC04
The Lifebreath Ventilation Control offers advanced features to control your home's ventilation.
Key Features:
2 speed fan setting (LOW / HIGH)
Standby setting (fan OFF)
20/40 mode
Compatible with 99-DET02 Wireless
Timers
Slim-line design
Connect to 3 wire 20 gauge low voltage
wire
BC04 Operating Instructions:
Turning on the Control
Press and release the ON/OFF button . The
light above will illuminate.
Setting the Ventilation Speed
Press and release the Fan button to select LOW or HIGH fan speed. The corresponding “Indicator
Light" will illuminate. If both LO and HI indicator lights are off, the fan is OFF but will turn ON if
required by a remote Timer (if installed).
Setting 20/40 Mode
After a fan speed has been selected, press and release the 20/40 button. The “Indicator Light” will
turn ON and the control will be in 20/40 mode.
20/40 mode is a repeating cycle. The fan will run at the set speed, LO or HI, for 20 minutes then
turn OFF for 40 minutes.
Some units are equipped to Recirculate air in your home during the 40 minute cycle with no
Ventilation. The control will automatically detect this feature and Recirculate air during the 40 minute
cycle at the selected fan speed.
20/40 Mode
Indicator Light
Fan Speed
Indicator
ON/OFF Light
ON/OFF Button Fan Speed
Button
20/40 Mode
Button

8
Attention
Only one main control can be installed on your system.
Recirculation is not available on all models.
Timers will not function when mode of operation is set to “OFF”, unless specifically installed for that function. (See
Installation Guide for other options.)
Instruction Card
Mode
Button Dehumidistat
Button RESET Button
20/40/60 High
Speed Button
Digital Control Operating Instructions (DXPL02):
Turning on the Control
Press and release the ON/OFF button . The light above will illuminate.
Setting the Ventilation Speed
Press and release the Fan button to select one of the 5 fan speeds. The fan speed will be
displayed on the screen beside the Fan symbol . Standby mode (Fan OFF) is indicated as speed
0. The fan will turn ON if required by a remote Timer (if installed).
20/40/60 High Speed Button
Press and release the 20/40/60 High Speed button to temporarily initiate HIGH Fan speed for 20,
40 or 60 minutes. Press once for 20 minutes, twice for 40 minutes, 3 times for 60 minutes and 4
times to disable. The will appear on the screen and the corresponding section of the clock will
flash to indicate the time interval selected. When the timer runs out, the unit will return to it's
previous operating speed.
Setting the Mode of Operation
There are 5 modes of operation available with the DXPL02 control. Pressing the Mode button
will cycle through the different modes of operation and they will be displayed on the screen.
ON/OFF
Button
Fan Speed
Button
5 speed fan setting
Standby setting (fan speed 0)
Electronic Dehumidistat
20/40/60 HIGH speed override button
Compatible with 99-DET02 Wireless Timers
Easy to read backlit LCD screen
Slim-line design
Connect to 3 wire 20 gauge low voltage wire
Five selectable modes of operation
•Continuous Ventilation
•20 min. Ventilation / 40 min.
Recirculation 20/hr 40/hr
•20 min. Ventilation / 40 min. OFF
•10 min. Ventilation / 50 min. OFF
•Continuous Recirculation
Service indicator
20/hr 40/hr
10/hr 50/hr
The Lifebreath Digital Control 99-DXPL02
The Lifebreath Digital Control offers the most advanced features to control your home's ventilation.
Key Features :

9
Digital Control
(continued)
Setting the Dehumidistat
For a full description of the Dehumidistat function, refer to page 4 "How the Dehumidistat Works".
The DXPL02 control displays the current indoor humidity in LARGE numbers and the Dehumidistat
setting in SMALL numbers on the screen. If the indoor humidity is above the set point, the
DXPL02 control will initiate HIGH Fan speed operation in Ventilation mode until the indoor
humidity has been reduced below the set point.
Press and release the Dehumidistat button to adjust the Dehumidistat setting. The numbers on
the screen will cycle. The Dehumidistat can be set between 25% RH and 60% RH. To disable
the Dehumidistat function on the control, cycle through the setting until OFF is displayed.
Reset Button
The RESET button will clear the current Fan, Timer, Mode and Dehumidistat settings and set the
unit into LOW fan speed, Ventilation mode and a Dehumidistat setting of 40%.
Service Indicator
A service indicator appears when the unit requires routine maintenance. Refer to
"Maintenance Routine" in this guide.
To reset the service indicator once routine maintenance has been performed, press and hold the
ON/OFF button for 5 seconds.
Timers
Depending on the type of HRV installation, you may have timers in areas such as restrooms. The
Timer will override the operational mode (regardless of the setting) and initiate HIGH fan speed
Ventilation. Upon completion of the timer cycle, the HRV will return to your selected operational
mode and fan speed setting.
Lifebreath 20/40/60 Minute Timer
99-DET01
Initiates high speed ventilation for 20, 40 or 60 minutes.
The 20/40/60 minute status lights indicate high speed
operation. Lockout mode is useful if you wish to disable
the timer. Set lockout by holding the select button for 5
seconds. Unlock by holding for 5 seconds.
20/40/60 Minute
Status Lights
Select Button

10
Timers
(continued)
Lifebreath Wireless 20/40/60 Minute Timer
99-DET02
Initiates high speed ventilation for 20, 40 or 60 minutes.
The 20/40/60 minute status lights indicate high speed
operation.
Wireless Timers have an estimated range of 40' with no
obstructions. To increase the range of a Wireless Timer
a 99-RX02 Repeater may be used.
Using the Wireless 99-DET02 Timer
When paired to the main wall control, the Wireless Timer
may be moved to a remote location in the home such as
a bathroom.
Pressing the Select Button on the Timer will initiate high
speed fan operation. The corresponding Status Light will
illuminate under the number on the Timer to indicate
either 20, 40 or 60 minutes of high speed fan operation.
To cancel the call for high speed fan operation, press the
Select Button until the Status Lights are no longer
illuminated.
Replacing the Battery
When the battery on the timer needs to be replaced in
the Wireless Timer, the red LED Battery Indicator will
illuminate.
To replace the battery, first remove the Face Plate by
pulling it off the wall. On the back of the Timer Face
Plate the battery will be exposed. Replace the battery
and re-attach the Face Pate to the Back Plate. Be
careful not to damage the tabs on the Back Plate when
re-attaching the Face Plate.
Back of
99-99-DET02
Face Plate
Removable
Backplate
20/40/60 Minute
Status Lights
Select Button initiates
high speed ventilation
for 20, 40 or 60 min.
Battery Indicator
Back Plate
Face Plate
Battery

11
Power Plug
Timers
(
continued)
Lifebreath Wireless Repeater
99-RX02
The Wireless Repeater is used to extend range of the 99-
DET02 Wireless Timers. The Repeater plugs directly into
a 120V power outlet. The 99-RX02 wirelessly connects to
the main control as well as the 99-DET02 Timers.
The 99-RX02 Repeater should be installed at the halfway
point between the 99-DET02 Wireless Timer and the
main wall control if timer is out of range.
Indicator LED's
When the Repeater is positioned correctly, a solid green
LED will illuminate indicating the Repeater has a strong
connection to the main wall control and may be moved
farther away if necessary.
Dehumidistat LEDs
Set to the desired
humidity level. High
speed ventilation will
initiate when the indoor
moisture level exceeds
the set
Dehumidistat Adjust
Button
A flashing green LED means that the Repeater has a moderate connection to the main wall
control. The Repeater will function properly at this position but should not be moved farther from
the main wall control to ensure the connection is maintained.
A red LED indicates the Repeater is not connected to the main wall control and should be
repositioned closer to the main wall control to re-establish the connection and function.
Dehumidistat
Lifebreath Dehumidistat 99-DH01
Initiates high speed ventilation when the moisture
level in the home exceeds the set point on the
control. Once the humidity in the house is
reduced, the HRV will revert back to its previous
setting.
The Dehumidistat should be set to OFF for all
seasons except the heating season. Refer to "How
the Dehumidistat Works" in this manual before
setting the Dehumidistat.

12
Main Control Installation
The Lifebreath Digital Control 99-DXPL02 is to be surface mounted onto a wall and the Lifebreath
Ventilation Controls 99-BC02, 99-BC03 and 99-BC04 may either be installed onto a flush mounted
electrical switch box or surface mounted onto a wall. Only one master control should be installed to a
ventilation system (the face plate on this illustration may not be exactly the same as yours).
1. For DXPL02 control, remove the operating
instructions card from the top of the control
(Figure A).
2. Separate the face plate from the back plate by
firmly pulling apart (Figures B or C). Be careful
not to damage face plate contact pins.
3. For DXPL02 control, place the back plate of
the control in the desired location on the wall
and pencil mark the wall with the right and left
screw holes (Figure D).
4.
5.
6.
7.
8.
9.
Operating
Instruction
Card
Figure
A
Keep top / bottom
vent openings clear
Figure
D
(Two) 1/8 in hole for
screws and anchors.
1.5" 1.5"
1 in hole for Wiring
wire opening. Terminals
10.
11.
12.
For BC02, BC03 or BC04 controls, place the
back plate of the control in the desired location
on the wall and pencil mark the top and bottom
screw holes
(Figure E or F). For mounting the control
without a Decora plate, break off top and
bottom tabs and refer to Figure F for mounting.
Remove the back plate from the wall and mark
the center hole for the wires in the middle of
the screw holes. Refer to Figure D, E or F for
dimensions.
Drill (two) 1/8 in holes for the screws and wall
anchors (Figure D, E or F). For DX control, drill
a 1 in hole in the center (Figure D). For BC
controls, cut in a 3/4 in by 1 in oval hole in the
wall (Figure E or F).
Pull 3 wire 20 gauge (min.) 100 ft length
(max.), through the opening in the wall.
Connect red, green, and yellow to the wiring
terminals located on the back plate (Figure D, E
or F).
Attach the back plate to the wall using two
supplied screws and anchors.
Attach the face plate to the back plate (Figure B
or C). Note: Be careful to correctly align the
face plate to avoid damaging the face plate
contact pins.
For DXPL02 control, insert the operating
instructions card into the control (Figure A).
Connect the 3 wire 20 gauge (min.) 100 ft length (max.) to the terminal block located on ventilator (Red #3, Yellow #4
and Green #5).
Face
Plate
Figure B
Back
Plate
Pay special attention not to damage the contact pins when removing and detaching the face plate (Figures B and C).
Attention
Figure C
Keep top / bottom
vent openings clear
Back Plate
Face Plate
Figure
E
1.625"
0.75"
1"
1.625"
1/8 in hole for
screw and
anchor
1 in x 3/4 in
for wire
opening
Wiring
Terminals
1/8 in hole
for screw and
anchor
oval hole
Break off tab
Alternate Wall Mount
1/8 in hole for
screw and
anchor
1 in x 3/4 in 0.75"
oval hole
1/8 in
for wire
hole for
opening
screw and
anchor
Wiring
Terminals
Break off tab
Figure
F
1"
Wire hole
centered
between
screw
holes

13
Mechanical Timers Installation 99-101
The Mechanical Timer is a 2 wire “dry
contact” timer. A jumper wire must be
connected between 2 (ON) and 3 (RED).
Connect the 2 timer wires to ON and HI.
2 wire timers require a
jumper wire between
ON and RED on the
terminal block Connect the 2
wires from the
timer to ON and HI on the terminal block.
HRV Terminal Block
Wire
Connector
Furnace
Terminal Strip
Furnace
Thermostat
Interlocking the HRV to an Air Handler or Furnace
Blower
Connecting the HRV as illustrated will ensure the air handler/
furnace blower motor is operating whenever
the HRV is venting.
The HRV must be interlocked to the furnace/air handler with a
simplified installation (return/return installation) and should be
interlocked with a partially dedicated installation.
Setting “Standby” When Using a Main Control
The HRV will be “fully-off” when the off position is selected on the
Timers mount in standard electrical boxes
Use 3 wire 20 gauge (min.) 100 ft length (max.) low voltage wire and multiple timers individually wired back to the unit.
Caution:
Consideration should be given to competing airflows when connecting the HRV in conjunction with an air handler/furnace
blower system.
Building codes in some areas require “fully-off” functionality. Check with your local building authority before modifying the
unit to
“standby-off”. Unintentional operation of the HRV by the end user may occur if the unit is modified from “fully-off” to
“standby-off”.
Attention/Caution
Main Control. Timers and/or other controls will not function when the HRV is in the off position.
The “fully-off” feature can be modified to “standby-off” by adding a jumper on the terminal block between 2
(ON) and 3 (RED). “Standby” can also be achieved by setting the main control to the ON position and selecting
speed 0*. Timers and/or additional controls will initiate high speed ventilation when activated.
*Speed 0 is not available on all controls.
Operating the HRV With Dry Contact Controls
A jumper must be in place between 2 (ON) and 3 (RED) on the terminal block to activate the HRV for timers and/
or dry contact controls.
Adding Dry Contact Controls
Low Speed: A jumper between 2 (ON) and 1 (LOW) initiates low speed ventilation.
High Speed: A jumper between 2 (ON) and 6 (HI) initiates high speed ventilation.
Dehumidistat: A dry contact for a Dehumidistat is connected between 2 (ON) and 10 (BLK)

14
BC Series
Control
NOTE: Your BC
control may look
different than the
one shown.
Press Simultaneously
to Initiate Pairing Mode
Figure A
Figure
D
NOTE
The wireless Timers and Repeaters must be matched to
the main wall control of the HRV / ERV. This process is
called "Pairing". Multiple Timers and Repeaters can be
paired to a single wall control.
Figure
B
1/8 in hole for
screw and
anchor
1/8 in hole
for screw and
anchor
Break off tab
Alternate Wall Mount
1/8 in hole for
screw and anchor
Figure
C
Back Plate
Face Plate
1/8 in
hole for
screw and
anchor
Break off tab
Figure
F
Figure
E
Press Simultaneously
to Initiate Pairing
Mode
DXPL Series
Control
DET02 Timer
20/40/60 Minute
Status Lights
Select Button initiates
high speed ventilation
for 20, 40 or 60 min.
Battery Indicator
Removable
Backplate
The Timers may be installed onto a flush mounted electrical
switch box or it may be surface mounted onto a wall. Multiple
Timers may be installed in a ventilation system. To increase
the range of a wireless Timer, a RX02 Repeater should be used.
Pairing:
To pair additional DET02 Timers with the same wall control, or
if pairing was not successful, repeat steps 1-6.
When paired, the DET02 Timers can be moved and installed
elsewhere. Estimated range of the Timer is 40’ with no
obstructions. A RX02 Repeater may be installed to increase the
range of the Timers.
Test if pairing was successful by pressing the Select Button and
listen for the HRV / ERV to initiate HIGH fan speed Ventilation.
Un-pairing:
Installation:
1. Turn on the main wall control by pressing the ON/OFF
button and remove the battery from Timer.
2.
DET02 with DXPL Series Controls:
Press the left and
right buttons simultaneously on the main wall control
( and RESET buttons). The screen will go blank and the
wireless symbol will appear flashing on the bottom right
of the display. This indicates that the main control is now
in pairing mode. (Figure D)
3.
DET02 with BC Series Controls:
Press the left and
right buttons simultaneously on the main wall control
( and either or buttons, depending on the main
control). The bottom row of 3 LED's will begin flashing.
This indicates that the main control is now in pairing mode.
(Figure E)
4. Keep the Timer within 16” of the main wall control when
pairing.
5. Install the battery in the DET02 Timer. All four lights on
the Timer will immediately flash 5 times, then only the red
battery light will remain on for approximately 12 seconds
after which the "40" light flashes the rev code. 20, 40, 60
lights will flash until paired or will stop if not paired within
12 seconds. If pairing was not successful you now must
return to step 1 to restart the pairing process.
6. Press the button on the main wall control to exit pairing
mode when Timers have been successfully paired.
1. Remove the battery from the back of the DET02 Timer
2. Press and hold the Select Button on the front of the Timer
3. While holding the Select Button, reinsert the battery in the
Timer. Continue holding the select button until the LED
under "40" begins flashing. The DET02 Timer will now be
unpaired with the main wall control.
1. Separate the face plate from the back plate by firmly
pulling apart (Figure A).
2. For mounting the control without a Decora plate, break off top and bottom tabs and refer to Figure C for mounting.
3.Place the back plate of the control in the desired location on the wall and pencil mark the top and bottom screw holes
(Figure B or C). Drill two 1/8" holes.
4. Attach the back plate to the wall using the 2 supplied screws and anchors.
5. Attach the face plate to the back plate (Figure A).
Installation and Operation of Wireless 20/40/60 Minute Timer: 99-DET02

15
1. Turn on the main wall control by pressing the ON/OFF button .
2.
RX02 with DXPL Series Controls:
Press the left and right buttons simultaneously on the main
wall control ( and RESET buttons). The screen will go blank and the wireless symbol will appear
flashing on the bottom right of the display. This indicates that the main control is now in pairing
mode.
RX02 with BC Series Controls:
Press the left and right buttons simultaneously on the
main wall control ( and either or buttons, depending on the main control). The bottom row
of 3 LED's will begin flashing. This indicates that the main control is now in pairing mode.
3. The RX02 Repeater must be powered within 16” of the main wall control for pairing. If an outlet is
not available an extension cord should be used to power the repeater initially for pairing.
4. Plug the RX02 Repeater into the power outlet. The green light will flash after approximately 12
seconds indicating that the repeater is paired with the main wall control.
5. Press the ON/OFF button on the main wall control to exit pairing mode and the Repeater may
RX02
Repeater
Power
Plug
Installation and Pairing of Repeaters: 99-RX02
The RX02 Repeaters are to be plugged directly into a 120V power outlet
The circuit board on this unit has adjustable DIP switches for the selection of speeds
Hi1, Hi2 or Hi3. The factory setting is Hi3. Refer to the specification page found online at;
www.lifebreath.com for the airflow rates on Hi1, Hi2 and Hi3. Note: Low speed is not adjustable.
DIP 1 ON R2000 defrost cycle disabled (factory setting)
DIP 1 OFF R2000 defrost cycle enabled
DIP 2 ON recirculate defrost models
DIP 2 OFF damper defrost and fan defrost models
Illustration of DIP switches 3
and 4 in the ON position
(factory setting).
Functionality of DIP
Switches 1 and 2
Description Switch 1 Switch 2 Switch 3 Switch 4
Hi 3 (factory default) Factory Setting “ON” Leave on factory setting ON ON
Hi 2 Factory Setting “ON” Leave on factory setting OFF ON
Hi1 Factory Setting “ON” Leave on factory setting ON OFF
now be unplugged and moved to its permanent location.
To pair additional RX02 Repeaters with the same wall control, repeat steps 1-5 until
all Repeaters have been paired.
When installed in its permanent location, the green LED will remain solid to indicate
the best location and the Repeater can be moved farther if required. The green LED
will flash to indicate it is in a good location. A red light indicates the Repeater is out
of range and needs to be moved closer to the main wall control.
Installer Selectable High Speed Settings

Maintenance Routine
1. Inspect Exterior Hoods at Least Once a Month
Make sure exhaust and fresh air supply hoods are not blocked or restricted by leaves, grass,
or snow. In winter, it is especially important to make sure snow is not blocking the hoods or
that frost has not built up on the wire mesh (bird screen).
2. Clean Air Filters (Clean Four times a Year)
The standard filters equipped with your HRV are removable and washable.
a) Open access door and slide core out.
b) Remove filter clips if present.
c) Once clips are removed, filters can be taken off the core to be rinsed with water or a
combination of mild soap and water. Do not clean in the dishwasher.
d) To re-assemble, place clean filter(s) (wet or dry) back into their positions against the core
and return clips to their original positions.
e) Slide core back into its original position.
3. Clean Core Twice a Year
a) Open access door.
b) Carefully grip ends of core and pull evenly outward. Core may be snug, but will slide out
of the cabinet.
c) Once removed from the cabinet remove filters.
d) Install the clean filters.
e) Install clean core in the cabinet.
Note: Core installation label on the outer end of the core.
To Install the Clean Core:
a) To reinstall the core first position the bottom of the core on the bottom support in the
cabinet.
b) Carefully align the core with the other 3 supports and fully insert the core.
c) Push on sides of core, do not push on the center.
Note: Core may appear to stick out from the cabinet approximately 1/8 in (3 mm). This is
designed this way so that the access door will fit tight against the core.
Do not use cleaning solutions for the HRV core
Soak and rinse the HRV core in warm soapy water
Do not use bleach or chlorine
Do not use a pressure washer on the HRV core
Do not place the HRV core in a dishwasher
Warning:
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn
the electrical power unit off at disconnect switch(es). Unit may have multiple power supplies.
Blockage of hoods may cause an imbalance
Attention/Warning
16

Maintenance Routine Continued
4. Motors — Maintenance Free
5. Drain (condensate) Line - Clean Once a Year
Inspect drain line, drain spout and “P” trap for blockage, mold or kinks. Flush with warm
soapy water and replace if worn, bent or unable to clean.
6. Clean Duct Work if Required
The duct work running to and from the HRV may accumulate dirt. Wipe and vacuum the duct
once every year. You may wish to contact a heating/ventilation company to do this.
7. General Maintenance - Twice a Year
Wipe down the inside of the cabinet with a damp cloth to remove dirt, bugs and debris that
may be present.
17

18
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily
removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan
operation.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of the cabinet designed to accept the “S” hooks and
hanging straps supplied with the unit.
DEFROST
Recirculating damper defrost system.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance.
Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.
Balancing ports are located in the door.
ELECTRONICS
The optional controls can be wall mounted in a central location of the home. 3 wire
20 gauge (min.) 100 ft length (max.).
CONTROL OPTIONS
*Sensible Efficiency – ther al **Latent Efficiency – oisture
Note: Effectiveness - b sed on temp. differenti l between the 2 irstre ms
Efficiency – t kes into ccount ll power inputs
Performance ( VI certified)
Net supply air flow in cf (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 207 (97)
@ 0.2" (50 Pa) 200 (94)
@ 0.3" (75 Pa) 184 (87)
@ 0.4" (100 Pa) 171 (80)
@ 0.5" (125 Pa) 152 (71)
@ 0.6" (150 Pa) 130 (61)
@ 0.7" (175 Pa) 116 (55)
@ 0.8" (200 Pa) 86 (40)
Max. Temperature Recovery 74%
Sensible Effectiveness
@ 66 cfm (31 L/s) 32°F (0°C) 74%
32°F (0°C) 64%
*Sensible Efficiency
@ 66 cfm (31 L/s)
*Sensible Efficiency
@ 109 cfm (51 L/s) -13°F (-25°C) 62%
VAC @ 60 Z 120
WATTS / Low speed. 87
WATTS / igh speed 164
Amp rating 1.4
BALANCING DAMPER
33 5/8"
(850 mm)
STALE AIR
FROM INSIDE
FRESH AIR
FROM OUTSIDE
STALE AIR
TO OUTSIDE
FRESH AIR
TO INSIDE
14 3/4"
(375 mm)
19"
(483 mm)
*All Duct Connections 6" (152 mm)
CONDENSATE DRAINS
FILTERS
BLOWERS
*NOT E: Front
clearance
of 25 inc hes
(635 mm)
is recommended
for s erv icing unit.
RECIRCULATING
DEFROST
DAMPER
MOTOR
CORE
BALANCING DAMPER
HI 3
HI 2
HI 1
LOW
RNC 200
HEAT RECOVERY VENTILATOR
_
_
Qty:
_
_
_
_
_
_
_
Date:
Tag:
Project:
Engineer:
Contractor:
Supplier:
Quote #:
Submied By:
Units carry a lifeme warranty on the HRV core and
a 5 year replacement parts warranty.
NOTE: All specifications are subject to change without notice.
All units conform to CSA and UL standards
WEIGHT 71 lbs (32.5 kg) SHIPPING WEIGHT 73 lbs (33.2 kg)
DIMENSIONS RNC200
between timer and main wall control if timer is out of range.
ACCESSORY OPTIONS
99-163 Duct Heater w/Electronic SCR Thermostat - 1 kW, 6 in (152 mm)
99-186 Weatherhoods - Two 6 in (152 mm)
TIMER OPTIONS
99-DET01 Lifebreath 20/40/60 Minute Timer - Initiates High speed Ventilation for 20, 40 or 60 minutes.
99-BC03 Lifebreath Ventilation Control
•
•
•
Continuous Low fan speed
Humidity control through adjustable
Dehumidistat
3 modes of operation: Ventilation,
Recirculation, 20/40
•Compatible with 99-DET02 Wireless Timers
•3 wire connection
99-DXPL02 Lifebreath Digital Control
•
•
5 speed operation on each mode
Humidity control through adjustable
Dehumidistat
•5 user selectable operational modes: Continuous
Ventilation, Continuous Recirculation, 20 ON/40
OFF, 10 ON/50 OFF, 20 ON/40 Recirculation
•20/40/60 min. High speed override button
•Compatible with 99-DET02 Wireless Timers
•3 wire connection
99-BC02 Lifebreath Ventilation Control
•2 speed fan setting (Low/High)
•Humidity control through adjustable
Dehumidistat
•Compatible with 99-DET02 Wireless Timers
•3 wire connection
99-BC04 Lifebreath Ventilation Control
•2 speed fan setting (Low/High)
•2 modes of operation: Ventilation, 20/40
•Compatible with 99-DET02 Wireless
Timers
•3 wire connection
99-DH01 Lifebreath Dehumidistat
•Humidity control through adjustable
Dehumidistat
•3 wire connection
3 wire connecon.
99-DET02 Lifebreath WIRELESS 20/40/60 Minute Timer - Initiates High speed Ventilation for 20, 40 or 60
minutes. Wirelessly connects to main control for ease of install ation. 40' approximate range.
99-RX02 Lifebreath WIRELESS Repeater - Used to extend range of 99-DET02 Wireless Timers. Plugs into
120V power outlet. Wirelessly connects to main control and 99-DET02. Install at halfway point

19
Simplified Installation (Return/Return Method)
Installation Notes
The HRV must be balanced.
Unit should be balanced on high speed with the furnace
blower on.
It is mandatory that the furnace blower run continuously
or HRV operation be interlocked with the furnace blower.
The duct configuration may change depending on the
HRV model.
A backdraft damper is recommended in the exhaust air
duct to prevent outdoor air from entering the unit.
The airflow must be confirmed on site using the
balancing procedures found in this guide.
Spring-Loaded Backdraft Damper (Recommended)
Install the backdraft damper with the leaf hinge vertical. The damper is installed on the “Stale Air to
Outside Collar”
3’ min.
recommended
Forced Air
Furnace
Cool Air
Return
40 in (1 m) Minimum
Dampers for
balancing
airflows
Outdoors
Return Air 3 ft min.
recommended
Backdraft Damper
Leaf Hinge
Installed Vertically
(Recommended)
Applications such as greenhouses, atriums, swimming pools, saunas, etc. have unique ventilation requirements
which should be addressed with an isolated ventilation system.
Weatherhood arrangement is for drawing purposes only. 6 ft (2 m) minimum separation is recommended with 18
in (460 mm) above ground.
Check local codes/authority having jurisdiction for acceptance.
Backdraft dampers are recommended for the stale air to outside air duct. This damper prevents outdoor air from
entering the HRV during the operation of the furnace/air handler while the HRV is in standby, off, or recirculating.
Attention/Warning

20
Partially Dedicated System
Installation Notes
The HRV must be balanced.
Unit should be balanced on high speed with the furnace
blower on.
It is recommended that the furnace blower run
continuously or HRV operation be interlocked with the
furnace blower. Refer to building code.
The duct configuration may change depending on the
HRV model.
A backdraft damper is recommended in the exhaust air
duct to prevent outdoor air from entering the unit.
The airflow must be confirmed on site using the
balancing procedures found in this guide.
Spring-Loaded Backdraft Damper (Recommended)
Install the Backdraft Damper with the leaf hinge vertical. The damper is installed on the “Stale Air to
Outside Collar”
Forced Air
Furnace
Cool Air
Return
Dampers for
balancing
airflows
Outdoors
3 ft min.
recommended
Backdraft Damper
Leaf Hinge
Installed Vertically
(Recommended)
Applications such as greenhouses, atriums, swimming pools, saunas, etc. have unique ventilation requirements
which should be addressed with an isolated ventilation system.
Weatherhood arrangement is for drawing purposes only. 6 ft (2 m) minimum separation is recommended with 18
in (460 mm) above ground.
Check local codes/authority having jurisdiction for acceptance.
Backdraft dampers are recommended for the stale air to outside air duct. This damper prevents outdoor air from
entering the HRV during the operation of the furnace/air handler while the HRV is in standby, off, or recirculating.
Attention/Warning
EXHAUST AIR from various parts of home. i.e.
bathrooms (if required), kitchens (if required)
RETURN AIR
Other Airia Fan manuals