manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Airxcel
  6. •
  7. Furnace
  8. •
  9. Airxcel SUBURBAN MANUFACTURING NT-12SE User manual

Airxcel SUBURBAN MANUFACTURING NT-12SE User manual

Suburban
Manufachmng
Company
a
subs~o~;~ry
of
AIRXCEL, Inc.
INSTALLATION MANUAL
For Furnace Models
NT-12SE NT-16SE NT-20SE
The design of these furnaces have been certified for installation in
recreational vehicles only. In order for these furnaces to operate in
conformitywith generally accepted safety regulations, the installation
instructions outlined inthis book mustbefollowed. Failuretocomply
with theinstallation instructions
willvoid any responsibility ofSuburban
ManufacturingCompany. Your furnacewas inspectedbefore it leftthe
factory. If any parts are found to be damaged, do not install the
furnace. Any damages should be reported to the transportation
company immediately and the appropriate claims filed.
WARNING! Improper installation,
adjustment, alteration, service or
maintenance cancause propertydamage,
personal injury or loss of life. Refer to the
installation instructions andlor owners
manual provided with this appliance.
SUBURBAN MANUFACTURINGCOMPANY
PostOffice Box
399
Dayton, Tennessee
37321
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Extinguish any open flame.
Evacuate all personsfrom the vehicle.
Shut off the gas supply at the gas
container or source.
Do not touch any electrical switch, or
use any phone'or radio in the vehicle.
Do not start the vehicle's engine or
electric generator.
Contact the nearest gas supplier or
qualified service technician for repairs.
If you cannot reach a gas supplier or
qualifiedservicetechnician, contactthe
nearestfire department.
Do notturn on the gas supply untilthe
gas leak(s) has been repaired.
Installation and service must be
performed by a qualified installer,
service agency or the gas supplier.
INSTALLATION INSTRUCTIONS
temperaturewhenever any door, panel, or cover is inthe open position.
CAUTION: Due tothe differences invinyl siding, this applianceshould not
beinstalledonvinylsiding withoutfirst consultingwith themanufacturerof
the siding or cutting the siding away from the area around the appliance
vent.
CAUTION: In any installation in which the vent of this appliance can be
covered duetothe constructionofthe RVor some specialfeature ofthe RV
such as slide out, pop-up, etc. always insurethat the appliance cannot be
operated by setting the thermostat to the positive "OFF" position and
shutting off all electrical and gas supply to the appliance. Never operate
furnacewith vent covered.
of
this
appliancemust
be
made
in
accordance
with
thewritten instructionsprovidedinthis manual. Noagent, representative
or employee of Suburban or other person has the authority to change,
modify or waive any provision of the instructions contained in this
manual.
Gas Minimum Maximum
PropaneILP 11" W.C.'
13"
W.C.
'Water Column
Inthe USA,the installationmustconformwith localbuildingcodes.Intheabsence
of local buildingcodes, referto the latestedition of:
1-Standardfor RecreationalVehiclesANSl A-119.2INFPA501C.
2-Natlonal FuelCodeANSl 2223.1.
3-The furnace must be electrically grounded in accordance with the latest
edltlon of the National Electr~calCodeANSIINFPA No. 70.
4-The installation of the furnace shall be in accordance with any applicable
localcodes and regulations.
NOTE: These furnaces shall be installed so the electrical components are
protected
fromwater.
These furnaces will accommodate an installation depth from 21" to 27 314".
depending on the intake vent tube length you select. (See Figure 1.)
Pleaseadherestrictlyto the followinginstructionsto insureproperinstallationand
-
NOTE:Thesefurnaces must beinstalledandvented as describedinthis manual
1,
canada,the
furnace
must be installed in accordancewith:
so thatthe negativepressurecreated by the air circulating (return air) fan cannot
affectthe combustionair intake or venting of any otherappliance. It is imperative 1-StandardCANICSA-Z240 RecreationalVehicles
thatthe oroductsof combustion be orooerlvvented to theatrnosohereand thatall 2-CSA Standard CANICSA-Z240.6.2-Ma6 Electrical Requirements for
CAUTION:
~fpossible, do not installthe furnace to where the vent can be safe
operation.
as well as adequateclearancesfor accessibility.
covered or obstructedwhen any door on the trailer isopened. If this isnot The efficiency rating of the appliance is a product thermal efficiency rating
possible, then the travel ofthe door must be restricted in order to provide determined under continuous operating conditions and was determined
a
6"
minimum clearance betweenthe furnace vent and any door whenever independentlyof any installed system.
the door is open. NOTE: The exhaust temperature of this furnace could
discolor orwarp some materials. You should verify that the material used These furnaces are certified for use with
prop an el^^
gas only.
p as
supply
onthecoach door.
t an el.
orcoverwillnotdiscolor
or war^
from theexhaust pressure
for
purposes
Of
input adjustment:
combusilon alr supplled to burner be dravin from the outs~deatmosphere (See Recreat~orialVehlcles
'
Installing
VentAssembly'
)
3-Standard CANICSA-Z2404 2-M86 lnstallatlon
Requirements
for propant
Appliances
and
Equipment
~nRecreat~onalVehlcles
4-CANICGA-6149 lnstallat~onCodes
5-Anyappl~cablelocal codes and
regulations
Form No. 2413-C
The furnace cabinet must extend through the coach cabinetry 1318" as shown
in Figure 1. The 1 318" extension must be held in order to assure that the front
grille will properly attach to the furnace cabinet. Adequate clearances must be
maintained around furnace cabinet so that the unit will be accessible for
servicing.
TO INSTALLTHE FURNACE
1. Locate the furnace near lengthwise center of the coach. Do not install the
furnace with the vent facing toward the forward end of the coach.
2. Select a location for installation out of the way of wires, pipes, etc. that might
interfere with installation. Adhere to the following minimum clearances from the
furnace cabinet to combustible construction.
Back
-
0" Top
-
518"
Floor
-
0" Sides
-
518"
NOTE:Sideandtop clearances of furnace cabinetmaybe
0"
forthroughthewall
installations up to a maximum of 2 112" wall thickness (See Figure 2.)
The following minimum clearances from the warm air discharge grille to
combustible materials must be maintained:
ModelsNT-12SE, NT-16SE, NT-POSE
Front
-
24 Top
-
1" Floor
-
114"
Left Side
-
1" Right Side
-
8" or Left Side
-
8"
Right Side
-
1"
(See Figure 8)
I
Models NT-12SE and NT-16SE only
I
Front
-
12" Top
-
1" Floor
-
114"
Side 0"'
'NOTE: Must provide an additional 12 sq, in, of return air
when side clearance is
On
-
8
(See Figure 9)
3.
When anappliance is installeddirectlyoncarpeting, tile,orother combustible
material other than wood flooring, the appliance shall be installed on a metalor
wood panel extending the full width and depth of the appliance. If preferred,the
carpeting, tile or combustible materials, otherthan wood maybecutawaythefull
length and depth of the appliance plus the appliance minimum clearances to
combustibles.
4.
Cut or frame an opening in the coach cabinetry 109/16x 103/16as shown
in Figure 2 or Figure 3.
5.
Slide the front of the furnace through the opening and extend it beyond the
coach cabinetry 1 318" as shown in Figure
2
or Figure 3.
6. Determine
"X"
dimension as shown in Figure 1.
7.
Determine "Y"dimension as shown in Figure 1.
8.
If
X
-
Y
is less than 21", then an opening
9
518" x 9
318"
must be cut through
the inner wall only. DO NOT CUT THROUGH COACH SKIN. (See Figure 2.)
Next, locate the center line of the exhaust and intake tube. Cut two 2 114"
diameter holes through the outer skin as shown in Figure 4.
NOTE: Whenever the furnace cabinet is installed through the outside wall, the
return air louvers on the furnace cabinet must not be blocked. The maximum
projection of the furnace cabinet into the wall is 2 112". (See Figure 2.)
NOTE:Furnacecabinet approved for
0"
clearanceto combustible materialsrear
2 112" of furnace cabinet.
9.
If
X
-
Y
is 21" or greater, two melhods may be used to install the furnace.
a. Cut a
4"
x
7
112" opening through combustible wall as shown in Figure
3.
DO NOT CUT THROUGH TRAILER SKIN. Next, locate the center line of the
exhaustand intake tube. Cuttwo 2 114" diameter holes throughlrailer skin. (See
Figure4.)
b.
If
you do not wish to cut the 4"
x
7
112opening, locate the center line of
the exhaust and intake tube as shown in Figure
4.
Next,cut two 2 314" diameter
holesthrough trailer skin and alsothecombustiblewall of thetrailerasillustrated
in Figure
6.
Care must betaken when locating the center lineof the exhaust and
intake tube as well as when cuttingthe holes in orderto assurea318" clearance
around the exhaust and intake tube to combustible materials.
10. Refer to the chart in Figure 1 and select the range for which the
'X'
dimension falls. The intake tube length directly to the left of the selected range
is the length required. NOTE: The
7
314" length exhaust tube assembly will
accommodate all approved installation depths
-
only the intake tube must be
ordered when needed. Under no circumstances should the standard
5"
intake
tube be cut or altered to adapt to the 21"
-
23 114range.
11. Secure furnace to the floor using the two holes provided in the front area of
the furnace cabinet. (See Figure 2 or Figure 3.)
12. NOTE: OPTIONAL DISCHARGE DUCT ADAPTER -The cabinet has a 4"
diameter knockout on the left side of cabinet. (See F~gure6A.) A
4"
diameter
connector can be attached to this location to providea warmair discharge duct.
(Notto exceed 10in length.)
CONNECTINGGAS SUPPLY
A 318" flare connection is provided on the right side of the furnace for the gas
supply connection to the furnace.
NOTE: Be sure all male joints have been treated with a sealing compound
resistant to the action of liquefied petroleum (LP)gas.
In order to maintain a check on gas supply pressure to the furnace. Suburban
advises the installer to provide a 118" NPT plug tap for test gauge connection
immediately upstream of the gas supply connection to the furnace.
NOTE:The appliance must bedisconnected from the gas supply piping system
during any pressure testing of that system at test pressure in excess of 112
PSIG.
The appliance must be isolated from the gas supply piping during any pressure
testing of thegas supplypiping system at test pressure equal to or lessthan 112
PSIG.
WARNING! All joints must becheckedfor leaks. Do not useopen flame
to check for leaks! Usea soap and water solution.
CONNECTING ELECTRICAL SUPPLY
CAUTION: These furnaces aredesignedfor a negativeground 12volt D.C.
system only. Do not attempt to alter the furnace for a positive ground
systemor connect thefurnacedirectly to 115voltsA.C. Damagetofurnace
component parts will occur.
Be sure all wiring to the furnace is of heavy enough gauge to keep the voltage
drop through it to a minimum. No. 12gauge wire is recommended. If any of the
original wire that is supplied with the appliance must be replaced, it must be
replacedwith Type 105" Cor its equivalent.
Connect the power supply to the red and yellow wlres onthe right side of the
furnace. The wires are color coded, red for positive
(+)
and yellow for negative
(-).
This polarity must beobserved so the furnace motor will run with the proper
direction of rotation to insure correct air delivery. (Seewiring diagram.)
If the furnace power supply is to be from a convertor, we recommend that the
convertorsystem usedto power thefurnace bewired in parallel with the battery.
This will serve two purposes:
1. Providea constant voltage supply to the furnace.
2. Filter any A.C. spikes or volt surges.
NOTE: Furnace models NT-12SE, NT-l6SEAND NT-POSEare equipped with
an electric ignitor device that has an energy consumption of.1 amps at 12volts
D.C.
CONNECTING THERMOSTAT
Locatethe roomthermostat approximately4 112 feet above!he flooronaninside
bulkhead where it is not affected by heat from any source except room air.
Connect the thermostatwires to the blue wires on the right side of the furnace.
(See wiring diagram.)
INSTALLING VENT ASSEMBLY
The vent outlet must be installed so it is inthe same atmospheric pressure zone
as the combustion air intake. The exhaust and intake tubes must be ~nstalled
from the outside, pass through the RV skin and slide onto the furnace exhaust
and intake.
WARNING! Do not alter the vent assembly supplied with this furnace.
Any modificationswill result inimproperinstallationwhich couldcause
unsafe furnace operation.
CAUTION! Combustionair must not bedrawnfrom the living area. All air
for combustion must bedrawn from the outside atmosphere. All exhaust
gases must be vented to the outside atmosphere
-
never inside the RV.
Therefore, it isessential to insure that the vent cap and tube assemblies
are properly installed.
1. Apply caulking to RV skin behind vent cap as shown in Figure 6. Apply
caulking generously around perimeter of vent cap and across center as shown.
2. Insert intake tube through RV skin and slide it onto the furnace intake (See
Figure 1.) Minimum tube overlap of 112" is required.
3.
Insert vent cap exhaust tube through RV skin and slide it onto the furnace
exhaust (See Figure 1.) Minimum tube overlap of 1 114" is required.
4.
Attachvent cap assembly to outer skin of RV withthe six (6)screws provided.
Do not install vent assembly upsidedown. The words "Suburban" and "Dayton,
Tenn."must be riaht side UD.
--
-
-
Due to high temperatures, the unit should belocated out of traffic and
away from furniture and draperies.
Children and adults should be alerted to the hazards of high surface
temperatures andshould stay away to avoid burns or clothing ignition.
Youngchildrenshouldbecarefullysupervisedwhentheyareinthesame
roomasthe unit.
Clothing orotherflammablematerialshould not beplacedonornearthe
unit.
Any safety screen or guard removed for servicing the unit must be
replaced prior to operating the unit.
Theareaaroundthe unit mustbekeptclearfromcombustible materials,
gasolineand other flammable vapors and liquids.
Installation and repairs should bedone bya qualified service person.
The unit should be ins~ectedbefore use and at least annuallv bv a
qualified service person: Morefrequent cleaningmayberequireddueto
excessive lint from carpeting, beddingmaterial, etc. It isimperative that
control compartments, burners, and circulating air passageways of the
~ ~
I
unit
be
kept clean.
I
I
VENT
TUBE
INSTALLATION
HOCfLS
NT-I?.
HT-I6
L
NT-FOSC
I
VEHT
TUBr
<EXHAUSTI
8'
K
2'
D.0.
VENT
TUBE
IIHTAKE>
SEE
CHART
(U
-
HIIUEIT
IHG
SURFACE
-I
C1/2.
"I*
(IVLRLIP
*
IOFIHTAKETUBE
I
PPXI
MI.
INllKt
TUBE
LENGTH
ONLY
1
-X-
DIKMIO.
I
I
$r
NEVER
INSTALL
VFNT
TUBES
*
STANDARD
TUBE
FWmISMD
WITH
FWWC
WITH
LESS
TW
1/2'
OVERLbP
THE
SPECIAL
TUBES.
IF
NEEDED.
WST
OM
INTAKE
L
1
I/4'
IR1
EXWCST
BC
OR3CRED
Flgure
i
BACK
Of
FURNACE
CABlNEl
fRAltER
SKIM
\POWER
SUPPLY
b
THERMOSTAT
W~RES
INLET
FOR
ELECTRIC
IGNTTION
WDELS
SECURE
UNIT
IN
PLACE
VlTH
(2)
SLREVS
ngum
2
2
1/4' DIA. TVD HOLES
THROWGH
TPAILER
SKIN
U[lLIHTlFIG SURF
hCE
PIIVER
SUPPLY
b
THERHDSTAT
WlRES
5
INLET
FOR
ELECTRIC
IGNITIUH
MUDELS
2
1/4' DIA TVD HOLES
THROWGH
TPAILER
SKIN
U[lLIHTlFIG SURF
hCE
rVCN:
CAP
OUTLiPiF
THSU
TRAICOR
SKIN
BACK
VIEW
OF
FURNACE
Rgum
4

This manual suits for next models

2

Other Airxcel Furnace manuals

Airxcel Suburban SF-20F User manual

Airxcel

Airxcel Suburban SF-20F User manual

Airxcel Suburban SF-20Q Guide

Airxcel

Airxcel Suburban SF-20Q Guide

Airxcel Suburban SF Series User manual

Airxcel

Airxcel Suburban SF Series User manual

Airxcel Suburban Dynatrail P-30S User manual

Airxcel

Airxcel Suburban Dynatrail P-30S User manual

Airxcel Suburban SF-25Q Guide

Airxcel

Airxcel Suburban SF-25Q Guide

Popular Furnace manuals by other brands

Suburban NT-16SQ User's information manual

Suburban

Suburban NT-16SQ User's information manual

Goodman GME8 Technical manual

Goodman

Goodman GME8 Technical manual

Thermo Pride OMC-70 specification

Thermo Pride

Thermo Pride OMC-70 specification

Bryant 987MB Installation, start-up, operating and service and maintenance instructions

Bryant

Bryant 987MB Installation, start-up, operating and service and maintenance instructions

VERDER HZS 12/900 Installation, operation and maintenance instructions

VERDER

VERDER HZS 12/900 Installation, operation and maintenance instructions

Coleman DGAA User's information manual

Coleman

Coleman DGAA User's information manual

Carrier 170 Series Service and maintenance instructions

Carrier

Carrier 170 Series Service and maintenance instructions

Central Boiler CLASSIC EDGE 350 owner's manual

Central Boiler

Central Boiler CLASSIC EDGE 350 owner's manual

Bryant 30AAV A Series Installation, start-up, and operating instructions

Bryant

Bryant 30AAV A Series Installation, start-up, and operating instructions

VERDER CARBOLITE GERO CFM 14/2 Installation, operation and maintenance instructions

VERDER

VERDER CARBOLITE GERO CFM 14/2 Installation, operation and maintenance instructions

hecht international SALINO manual

hecht international

hecht international SALINO manual

Napoleon HYBRID 150 operating instructions

Napoleon

Napoleon HYBRID 150 operating instructions

HP 422690 I Installer's information manual

HP

HP 422690 I Installer's information manual

Payne Gas Furnace User's information manual

Payne

Payne Gas Furnace User's information manual

VERDER Carbolite Gero CTF 12/75/700 Installation, operation and maintenance instructions

VERDER

VERDER Carbolite Gero CTF 12/75/700 Installation, operation and maintenance instructions

Carrier UPFLOW INDUCED-COMBUSTION FURNACES 58PAV Installation, start-up, and operating instructions

Carrier

Carrier UPFLOW INDUCED-COMBUSTION FURNACES 58PAV Installation, start-up, and operating instructions

Bryant 355BAV Service and maintenance instructions

Bryant

Bryant 355BAV Service and maintenance instructions

Continental Refrigerator C97 Series Installation and operating manual

Continental Refrigerator

Continental Refrigerator C97 Series Installation and operating manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.