Aisin GHP Series User manual


2

3
Indice
1
Outdoor Unit (mod. 8 – 10 – 13 HP) ..............................................................................................................5
1.1
Technical specifications......................................................................................................................6
1.2
External dimensions...........................................................................................................................7
1.3
Allowed temperature range................................................................................................................8
1.4
Noise level charateristics....................................................................................................................9
1.5
Space required for installation..........................................................................................................12
1.6
Outline diagram of refrigerant piping................................................................................................14
1.7
Refrigerant piping installation specifications ....................................................................................14
1.8
Refrigerant piping – Selecting branches and permissible lengths...................................................15
1.9
Refrigerant charging.........................................................................................................................20
1.10
Note for branch piping......................................................................................................................21
1.11
How to extend exhaust pipe.............................................................................................................22
1.12
Summary of electric wiring installation.............................................................................................24
1.12.1
Opening for power supply wires / signal wires........................................................................24
1.12.2
Wiring example (AC 230 V single phase)................................................................................25
1.13
Power supply wiring procedure........................................................................................................26
1.13.1
Wiring instruction.....................................................................................................................26
1.13.2
Wiring lenght............................................................................................................................27
1.13.3
Branch wiring...........................................................................................................................28
1.14
Various function settings ..................................................................................................................29
2
Outdoor unit (mod. 16 – 20 – 25 HP)...........................................................................................................30
2.1
Specifiche tecniche...........................................................................................................................31
2.2
External dimensions.........................................................................................................................32
2.3
Allowed temperature range..............................................................................................................33
2.4
Noise level charateristics..................................................................................................................34
2.5
Space required for installation..........................................................................................................37
2.6
Combinations and capacities of the outdoor units and indoor units.................................................39
2.6.1
Stand-alone installation ...........................................................................................................39
2.6.2
Combined installation ..............................................................................................................39
2.7
Outline diagram of refrigerant piping................................................................................................40
2.7.1
Combined installation ..............................................................................................................40
2.7.2
Stand-alone installation ...........................................................................................................41
2.8
Refrigerant piping installation specifications ....................................................................................42
2.8.1
Combined installation ..............................................................................................................42
2.8.2
Stand-alone installation ...........................................................................................................42
2.8.3
Reducer selection for combined installation............................................................................43
2.9
Refrigerant piping – Selecting branch pipes and permissible lengths .............................................46
2.9.1
Combined installation ..............................................................................................................46
2.9.2
Stand alone installation............................................................................................................50
2.10
Refrigerant charging.........................................................................................................................55
2.10.1
Refrigerant charging amount...................................................................................................55
2.10.2
Refrigerant charging method...................................................................................................55
2.11
Notes for branching piping ...............................................................................................................56
2.12
How to extend exhaust pipe.............................................................................................................57
2.13
Power supply wiring procedure........................................................................................................59
2.13.1
Wiring instruction combined installation ..................................................................................59
2.13.2
Wiring instruction stand-alone installation ...............................................................................60
2.14
Summary of electric wiring installation.............................................................................................61
2.14.1
Opening for power supply wires / signal wires........................................................................61
2.14.2
Wiring example (AC 230V single phase).................................................................................62
2.14.3
Direct expansion indoor unit system wiring (AC 230V single phase)......................................63
2.14.4
Air water system wiring (AC 230V single phase) ...................................................................63
2.15
Wiring length ....................................................................................................................................64
2.16
Branch wiring....................................................................................................................................65
2.17
Various function setting ....................................................................................................................66
Specifications, drawings and general information within this manual are subject to change without notice.

4

5
1
Outdoor Unit (mod. 8 – 10 – 13 HP)
8 HP – AXGP224E1 [N – P] [NATURAL GAS – LPG]
10 HP – AXGP280E1 [N – P] [NATURAL GAS – LPG]
13 HP – AXGP335E1 [N – P] [NATURAL GAS – LPG]

6
1.1 Technical specifications
Model AXGP224E1 AXGP280E1 AXGP355E1
8 HP 10 HP 13 HP
Performace
Rated cooling capacity* 100%
kW
22,4 28,0 35,5
50% 11,2 14,0 17,8
Rated heating capacity** 100% 25,0 31,5 40,0
50% 12,4 15,5 20,2
Maximum heating capacity*** 26,5 33,5 42,5
Fuel gas
Type Natural gas G20
Natural gas G25
LPG
Rated cooling consumption* 100%
kW
15,0 19,2 26,4
50% 7,4 8,0 9,9
Rated heating consumption** 100% 15,9 20,3 27,0
50% 8,3 9,6 11,7
Maximum heating consumption*** 21.7 27.5 36,6
Electricity
Power supply V AC 230 single phase
Starting current A 20
Rated consumption / Current Cooling kW/[A] 0,34 / [1,4]
0,42 / [1,8] 0,44 / [1,9]
0,58 / [2,5] 0,57 / [2,4]
0,74 / [3,2]
Heating
Engine
Type Water cooled vertical type, 3 cylinders, 4 strokes
Displacement cm3952
Rated mechanical output kW 5,0 6,2 7,9
Revolution range Cooling rpm 800~1.250
800~2.450 800~1.550
800~2.900 800~2.000
800~2.900
Heating
Compressor Type x numbers of units Variable capacity scroll x 2
Transmission Poli V belt
Refrigerant Type R410A
Factory charge Kg 11,0
Fans
Type x numbers of units Variable speed propeller type x 2
Rated total flow rate m3/ h 10.020 11.640 12.780
Static pressure: standard – [silent mode] Pa 5 – [30]
Noise level Sound pressure : standard – [silent mode] dB(A) 54 – [52] 56 – [52] 59 – [57]
Piping
Refrigerant Gas line mm Ø 19,1
Ø 9.5 Ø 22,2
Ø 9.5 Ø 25,4
Ø 12.7
Liquid line
Fuel gas inch R 3 / 4
Exhaust gas mm Ø 80
Exhaust drain: standard – [cold district] Ø 15 – [Ø 30]
Piping permissible length: actual / equivalent – [AWS]
m
165 / 190 – [70 / 60]
Max. distance after the first branch 60
Max. height difference between indoor units 15
Max. height difference between indoor and outdoor units – [AWS] + 50 / - 40 – [+25 / - 20]
External dimensions
Height
mm
2.077
Width 1.400
Depth 880
Weight: standard – [cold district] Kg 565 – [570]
Connectable indoor units Number: standard – [cold district] 20 – [13] 25 – [16] 32 – [20]
Capacity: standard – [cold district] % 50 – 200 / [50 – 130]
Maintenance Scheduled maintenance interval h 10.000
Engine oil replacement 30.000
Special models: Cold district (F): outdoor temp lower than – 10°C /AWS (A): outdoor unit connectable with AWS / W kit (K): built in domestic hot water version
*Outdoor temp. 35°C (DB) – indoor temp. 27°C (DB) / ** Outdoor temp 7°C (DB) – indoor temp. 20°C (DB) / ***Outdoor temp. 2°C (DB) – indoor temp. 20°C (DB)

7
1.2 External dimensions

8
1.3 Allowed temperature range
Cooling
Heating
30
16 -20 21
Temperatura aria esterna [°C]
Temperatura aria interna [°C]
Campo di applicazione
in riscaldamento
Kit zone
fredde
-20 -10 0 10 20
10
20
30 30
16 -20 21
Temperatura aria esterna [°C]
Temperatura aria interna [°C]
Campo di applicazione
in riscaldamento
Kit zone
fredde
-20 -10 0 10 20
10
20
30
All measurements are expressed as dry bulb
Note Scale temperature setting on the remote control
Limite
superiore Limite
inferiore
Cooling. 35°C 20°C
Heating 30°C 15°C
Indoor temperature (°C)
Indoor temperature (°C)
Outdoor t
emperature (°C)
Outdoor temperature (°C)
Allowed cooling mode
temperature range
Allowed
heating mod
e
temperature range
Cold
district

9
1.4 Noise level charateristics
Global values (dB(A)/m)
Model Front Rear Right Left
AXGP224E1
N-P 54 53 49 50
Detection status:
Semi-anechoic room
Distance 1 m
Height 1 m
Front

10
Noise level charateristics
Global values (dB(A)/m)
Model Front Rear Right Left
AXGP280E1
N-P 56 56 52 53
Detection status:
Semi-anechoic room
Distance 1 m
Height 1 m
Front

11
Noise level charateristics
Global values (dB(A)/m)
Model Front Rear Right Left
AXGP355E1
N-P 59 59 54 55
Detection status:
Semi-anechoic room
Distance 1 m
Height 1 m
Front

12
1.5 Space required for installation
1) Provide sufficient distance from flammable materials
Install the outdoor unit in the proper distance from flammable items as required by the rel-
evant local and national regulations, and technical standards. (See the reference below.) If
the distance does not meet the requirements, it could result in a fire.
WARNING
DISTANCE FROM FLAMMABLE MATERIALS (MM)
FRONT
FRONT

13
2) Installation space
Provide ample space for inspection and maintenance taking into account the refrigerant and fuel gas piping.
The following drawings show the minimum installation space for providing room for
intake air and inspection and maintenance operations.
Insufficient space could result in injury to the maintenance personnel or damage to the
equipment
CAUTION
FRONT
* FRONT
MULTIPLE UNIT INSTALLATION
* FRONT
*
THIS SPACE MUST BE 800 MM OR MORE WHEN THE SNOW HOOD IS MOUNTED
MINIMUM DISTANCE FROM SORROUNDING OBJECTS (MM)

14
1.6 Outline diagram of refrigerant piping
1.7 Refrigerant piping installation specifications
Outdoor Unit
Item
Refrigerant main piping diameter
(mm) Permissible piping
length (m)
Equivalent length/
Actual length
Permissible height
difference (m)
Refrigerant
oil
Vapor line
Liquid line Outdoor unit is
higher
Outdoor
unit is lower
P224 ø19.1
*1(ø22.2) ø9.5
*1(ø12.7) 190
/165
*2 50 40 NL10
P280 ø22.2
*1(ø25.4) ø9.5
*1(ø12.7)
P355 ø25.4
*1(ø28.6) ø12.7
*1(ø15.9)
ATTENTION
∗If the piping length exceeds 100 m, install pipes larger by one rank specified in ( ).
∗∗ When total capacity of connected indoor unit exceeds 130 % of rated capacity, restrict the
permissible piping length(actual length) to 100 m or less.
Refrigerant liquid pipe (brazing)
Brazing connections
Indoor unitIndoor unit
Branch pipes or helders
(sold separatly)
Outdoor unit
Fuel gas pipe R ¾’’
Refrigerant capor line (brazing)
Condensation water drain port
Exhaust gas
water drain port
Flare connections

15
1.8 Refrigerant piping – Selecting branches and permissible
lengths
Piping specifications (Use the following pipes)
•Piping material: Phosphate deoxidized copper seamless air-conditioning pipe JIS H3300, C1220T
(Japanese technical standard) or equivalent.
•Refrigerant pipe specifications: Outer diameter ×thickness (mm)
ø 6.4 × 0.8 ø 9.5 × 0.8
ø 12.7 × 0.8 ø 15.9 × 1.0
ø 19.1 × 1.0 ø 22.2 × 1.0
ø 25.4 × 1.0 ø 28.6 × 1.0
ø 31.8 × 1.1 ø 38.1 × 1.35
(1) 【Main piping】Between outdoor unit and first branch (A on the figure)
Outdoor unit
P224
P280
P355
Vapor line (mm)
Ø 19.1
Ø 22.2
Ø 25.4
Liquid line (mm)
Ø 9.5
Ø 12.7
(2) Main piping】Between outdoor unit and first branch (A on the figure)
Total capacity of downstream
indoor units (kW) fino a
22.4kW da 22.4kW
a 33.0kW
da 33.0kW
a 47.0kW da 47.0kW
a 71.0kW da 71.0kW
o più
Vapor line (mm)
Ø 15.9
Ø 22.2
Ø 28.6
Ø 31.8
Liquid line (mm)
Ø 9.5
Ø 12.7
Ø 15.9
Ø 19.1
(3) Piping between branch and indoor unit (a, b, c, d, e and f on the figure)
Indoor unit
P22, 28, 36, 45, 56
P71, 80, 90, 112, 140
P224 P280
Vapor line (mm)
Ø 12.7
Ø 15.9
Ø 19.1
Ø 22.2
Liquid line (mm)
Ø 6.4 Ø 9.5
•Make sure that total extension refrigerant piping lenght is 520 m. or less.
•If the refrigerant piping equivalent length exceeds 100 m, use pipes with diameters larger by
one rank indicated in “4-3. Refrigerant piping installation specifications“ on the previous page
for the main liquid and vapor piping. Example: ø 12.7 →ø 15.9.
•This unit uses R410A. Limit pressure of O material pipe with ø 19.1 diameter or larger is
insufficient. Be sure to use 1/2H or H material pipes with minimum thickness or thicker. For
ø 19.1 pipe only, however, as long as the thickness is 1.05 mm or greater, O materials can
be used.
•Method of refrigerant piping can be selected from line branching, header branching, and
line-header combined branching. Select the proper method according to the layout of indoor
units.
•Refrigerant piping length and the height difference between indoor units should be arranged
as short as possible.
•Re-branching after the header branching is not allowed.
CAUTION
Outdoor unit
First branch
Indoor
Unit 1 Indoor
Unit 2 Indoor
Unit 3 Indoor
Unit 4 Indoor
Unit
5
Indoor
Unit 6

16
Selecting branch piping and permissible piping length
Line branching
Layout example
(When 6 indoor units are connected)
Note: If there is a height differen-
ce between the locations of
indoor and outdoor units, apply
a small “trap pipes” only on the
vapor line at least every 10 m as
illustrated.
10 m10 m
Permissible
piping length
Maximum piping length (L)*
(
Equivalent length / Actual length)
A + B + C + D + E + f
190/165m or less
Maximum piping length after the first branch
B + C + D + E + f
60 m or less
Piping length difference after the first branch
(whenA is shortest length after the first branch)
l
– a
40 m or less
Permissible
height
difference
Height difference between indoor and
outdoor unit (H)
When outdoor unit is higher than
indoor unit
50 m or less
When outdoor unit is lower than
indoor unit
40 m or less
Height difference between indoor units (h)
15 m or less
Branch piping
How to select the branch piping kit
* When total capacity of connected indoor unit exceeds 130% of rated capacity, restrict the permissible piping
length (actual length) to 100 m.
CAUTION
In the c
a
se of h
e
ader b
r
an
c
h
ing
or lin
e
-
h
e
a
d
e
r combined b
r
an
c
h
ing, ind
o
or
u
n
i
t
s
with c
a
p
a
c
i
ty of
P280 or larger cannot be connected after the header branching (c, d, e or f in the right figure).
Connect the indoor units with capacity of P280 or larger to line branching (a or b in the right figure).
Important remider
Be sure to use the indoorunit pipingand indoorbranch piping that correspond to the indoorunit connecting piping
size.
Always install the branch piping joint (both for vapor and liquid) so that the joint branches either horizontally or
vertically.
Refer to the following table to select the branch piping kit because the size of branching pipe varies
depending on the total capacity of connected indoor units (total capacity of the downstream indoor
u
n
i
t
s).

17
Header branching
Layout example
(When 6 indoor units are connected)
Note: If there is a height differen- ce
between the locations of indoor
and outdoor units, apply a small
“trap pipes” only on the vapor line at
least every 10 m as illustrated.
10 m10 m
Permissible
piping
length
Maximum piping length (L)*
(
Equivalent length / Actual length)
A + f
190/165m or less
Maximum piping length after the first branch
f
60 m or less
Piping length difference after the first branch
(whenA is shortest length after the first branch)
l
– a
40 m or less
Permissible
height
difference
Height difference between indoor and
outdoor unit (H)
When outdoor unit is higher than indoor unit
50 m or less
When outdoor unit is lower than indoor unit
40 m or less
Height difference between indoor units (h)
15 m or less
Branch piping
How to select the branch piping kit
* When total capacity of connected indoor unit exceeds 130% of rated capacity, restrict the permissible piping
length (actual length) to 100 m.
Important remider
Be sure to use the indoorunit pipingand indoorbranch piping that correspond to the indoorunit
connecting piping size.
Always install the branch piping joint (both for vapor and liquid) so that the joint branches either
horizontally or vertically.
Re-branching after the header branching is not allowed. Besides, the indoor unit with
capacity of P280 or larger can not be connected after the header branching
Connect crimp piping (locally procured) to the branching points (on the indoor unit connection side)
in accordance with the number of connection indoor units.
Refer to the header branching kit (sold separately) for the crimp piping size.

18
Line – Header combined branching
Layout example
(When 6 indoor units are connected)
Note: If there is a height differen- ce
between the locations of indoor
and outdoor units, apply a small
“trap pipes” only on the vapor line at
least every 10 m as illustrated.
10 m10 m
Permissible
piping
length
Maximum piping length (L)*
(
Equivalent length / Actual length)
A + B + C + f
190/165m or less
Maximum piping length after the first branch
f
60 m or less
Piping length difference after the first branch
(whenA is shortest length after the first branch)
l
– a
40 m or less
Permissible
height
difference
Height difference between indoor and
outdoor unit (H)
When outdoor unit is higher than indoor unit
50 m or less
When outdoor unit is lower than indoor unit
40 m or less
Height difference between indoor units (h)
15 m or less
Branch piping
How to select the branch piping kit
* When total capacity of connected indoor unit exceeds 130% of rated capacity, restrict the permissible piping length (actual length) to 100 m.
Important remider
Be sure to use the indoorunit pipingand indoorbranch piping that correspond to the indoorunit
connecting piping size.
Always install the branch piping joint (both for vapor and liquid) so that the joint branches either
horizontally or vertically.
Refer to the following table to select the branch piping kit because the size of branching pipe varies
depending on the total capacity of connected indoor units (total capacity of the downstream indoor units).
How to select the header piping kit
Connect crimp piping (locally procured) to the branching points (on the indoor unit connection side)
in accordance with the number of connecting indoor units.
Refer to the header branching kit (sold separately) for the crimp piping size.
Important remider
Be sure to use the indoorunit pipingand indoorbranch piping that correspond to the indoorunit
connecting piping size.
Always install the branch piping joint (both for vapor and liquid) so that the joint branches either
horizontally or vertically.
Re-branching after the header branching is not allowed. Besides, the indoor unit with
capacity of P280 or larger can not be connected after the header branching

19
AWS line connection
Layout example
(When AWS is connected)
Note: If there is a height differen- ce
between the locations of indoor and
outdoor units, apply a small “trap
pipes” only on the vapor line at least
every 10 m as illustrated.
10 m
Permissible
piping
length
Maximum piping length (L)
(Equivalent length / Actual length) L = A
70/60m or less
Permissible
height
difference
Height difference between AWS unit and
outdoor unit (H)
When outdoor unit is higher than
indoor unit
50 m or less
When outdoor unit is lower than
indoor unit
40 m or less
ATTENTION
Never exceed the maximum allowed distance between AWS and GHP. Failure in doing so can
result in malfunctioning of the units and invalidates the warranty.
WARNING
•
Always refer to AWS installation manual for maintenance clearence and position of the unit.
•
Always connect the AWS to the designed outdoor unit for AWS.

20
1.9 Refrigerant charging
ATTENTION
•When charging the refrigerant, accurately measure the length of the piping and charge
the proper amount of refrigerant. If the amount of refrigerant is not proper, performance
will decline or a breakdown could occur.
•
After completion of refrigerant charging, write down the installation record on the plate
“POINTS FOR INSTALLATION” inside the outdoor unit control box panel. Besides,
calculate the refrigerant amount for the whole system and write down the amount on the
plate. Calculation formula is shown on the plate. (Write with a permanent marker so that
the record does not disappear easily.)
1) Refrigerant charging amount.
Always check the refrigerant gas factory charge on the unit label before calculating the amount to be added.
Calculate the amount of refrigerant to be charged according to the following formula and liquid piping length
for each size of the piping.
When the GHP is connected to YOSHI AWS E1:
Charge amount (kg) = (L1 × 0.353) + (L2 × 0.250) + (L3 × 0.170) + (L4 × 0.110) + (L5 × 0.054)
+ (L6 x 0.022) + Q
AWS
When the GHP is connected to direct expansion indoor units:
Charge amount (kg) = (L1 × 0.353) + (L2 × 0.250) + ( L3 × 0.170) + (L4 × 0.110) + ( L5 × 0.054)
+ (L6 x 0.022) + Q
de
Type or indoor system Q
de
[kg] Q
aws
[kg]
Direct expansion single unit 0,0 -
Direct expansion multiple indoor unit 1,0 -
Direct expansion air handling unit AHU
Refer to manufacturer
specification
-
Air water system YOSHIAWS E1 - 0,0
2) Refrigerant charging method
•
Always charge the refrigerant as a liquid in the tank. Charging as
a vapor may cause a compositional change of the refrigerant, and
could result in a performance decline or a breakdown
.
•Always use a refrigerant scale when charging the refrigerant.
using a charging cylinder may cause a compositional change of
the refrigerant, and could result in a performance decline or a
breakdown.
•To avoid cross-contamination with other oils types, make sure to
separate maintenance tools according to the type of refrigerant
used. In particular, never use the gauge manifold and charging
hose with other refrigerants (R22, R407C etc.)
CAUTION
When charging the refrigerant, be sure to wear a pair of leather gloves.
If the refrigerant touches your skin directly, it may cause a frostbite.
L1: Liquid pipe Ø 22.2 total length (m)
L2: Liquid pipe Ø 19.1 total length (m)
L3: Liquid pipe Ø 15.9 total length (m)
L4: Liquid pipe Ø 12.7 total length (m)
L5: Liquid pipe Ø 9.5 total length (m)
L6: Liquid pipe Ø 6.4 total length (m)
This manual suits for next models
3
Table of contents
Other Aisin Air Conditioner manuals

Aisin
Aisin AXLP22P2D User manual

Aisin
Aisin AXJP22A2D User manual

Aisin
Aisin AXGP096E1NHS User manual

Aisin
Aisin GHP AXAP22PAD User manual

Aisin
Aisin AXJP28A2D User manual

Aisin
Aisin AXMP90P7D User manual

Aisin
Aisin AXMP224P7D User manual

Aisin
Aisin AXFP22AVD User manual

Aisin
Aisin AWGP180E1NHS User manual

Aisin
Aisin AXDP22P7D User manual
Popular Air Conditioner manuals by other brands

LG
LG LS-J0761CL Service manual

Bryant
Bryant Evolution Extreme 186CNV installation instructions

Mitsubishi Electric
Mitsubishi Electric PUZ-ZM200YKA2-ET Service manual

Whynter
Whynter ARC-12SDH instruction manual

Friedrich
Friedrich Chill CP18 Installation and operation manual

Hitachi
Hitachi RAS-10NHZ4(H) instruction manual