Allen-Bradley Series B User manual

Fault Codes
Setting the Operating Speed Before
Starting the Unit
Standard units:Use the speed potentiometer or
other user-supplied external speed reference
device.
Units with local operator controls: As shipped
from the factory, the unit receives its speed
reference from the keypad.Use the
key to
increase the speed reference and the
key
to decrease the speed reference.
To use the analog input terminals for the speed
reference, setup switch 2 (Speed Reference
Select) must be in the ON position.In this case,
the
keys are not used.
At subsequent power ups, the unit will use the
last speed reference setting selected before
power was removed.
Using the Local Operator Controls
1329I
Integrated Drive/Motor
(Series B)
Quick Reference
Fault Code Fault Description
Communication Loss
Keyboard Disconnected
Parameter Checksum
Keypad connected while under power
DeviceNet Communication Fault
(
X
= E, F, L, P, or U)
Keypad connected while under power
Keypad Redundant Start
Function Loss
Overvoltage
EEPROM Drive ID
Undervoltage
Overcurrent
Overtemperature
Overload
TB Redundant Start
Internal Fault
(
NNN
= a number between 0 and 999)
X
Desired Action User Steps
Start the unit. Press the green
key.
Stop the unit. Press the red
key.
Change motor
rotation direction. Press the
key.
Clear faults or abort
Auto Restart
sequence. Press the
key.
Decrease the speed
reference.
Press the
key until the
speed reference displayed
is the desired value.The
longer the
key is held
down, the faster the value
will change.
Display the current
speed or load.
Press the
or
key once.
The display will return to indicating
speed in RPM or %load after three to
five seconds.
Display the speed in
RPM.
No action required; speed in RPM is
the default display based on terminal
12.
Display %load. Close switch on terminal 12.
Increase the speed
reference.
Press the
key until the
speed reference displayed is the
desired value.The longer the
key is held down, the faster the value
will change.
RESET
IMPORTANT:
This publication is designed as a reference
tool.The Bulletin 1329I
User Manual
and 1329I
DeviceNet
Option User Manual
must be consulted for more detailed
information about operation and hazards of personal
injury.
Publication 1329I-5.6 – January, 2000 P/N 194445 (01)
PE
DC Bus (Do Not Wire)
DBR (Do Not Wire)
AC Inputs
AC Input Power Connections
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
10Volt Reference ➊
0 – 10V DC Speed Reference Input
4 – 20 mA Speed Reference Input
Common
0 – 10Volt Output
Common
Speed Preset 2
Speed Preset 1
Speed Preset 0
Forward/Reverse
24Volt DC ➌
RPM/Percent Load Display
Reset
Start
Stop ➌
24Volt DC Common
N.O.Relay
Relay Common
24Volt DC ➋
Function Loss ➋
-+
RPM
% Load
OFF ON
Enabled
Terminal Block
Faulted
Enabled
Constant
Ramp-to-Rest
Disabled
FromTerminal Block
FromTerminal Block
From EEPROM Memory
Run On Power Up
Speed Reference ➊
Relay Control Output
Auto Restart
Torque Curve
Stop
Reverse
Minimum Speed
Start Mode ➊
Parameter Mode ➋
Disabled
Operator Controls
Running
Disabled
Variable
Coast-to-Rest
Enabled
0 Hz
From Operator Controls
From Setup Switches
Setup DIP Switch (SW3)
➊ Switches 2 and 9 apply to local operator control units only.
➋ Switch 10 applies to the DeviceNet Communication option only.
1 2 3 4 5 6 7 8 9 1011121314151617181920
10Volt Reference ➊
0 – 10V DC Speed Reference Input
4 – 20 mA Speed Reference Input
Common
0 – 10Volt Output
Common
Speed Preset 2
Speed Preset 1
Speed Preset 0
Forward/Reverse
24Volt DC ➌
RPM/Percent Load Display
Reset
Start
Stop ➌
24Volt DC Common
N.O.Relay
Relay Common
24Volt DC ➋
Function Loss ➋
-+
+10V DC
5K Ω
RPM Fwd
Rev
% Load
13 16 17
Maintained 2-Wire Start.
Momentary 3-Wire Start.
0 = 1 Second Accel/5 Sec Decel
1 = 5 Seconds (Default)
2 = 10 Seconds
3 = 15 Seconds
4 = 20 Seconds
5 = 30 Seconds
6 = 60 Seconds
7 = 90 Seconds
0 = 1500 RPM (50 Hz)
1 = 1800 RPM (60 Hz) Default
2 = 2100 RPM (70 Hz)
3 = 2400 RPM (80 Hz)
4 = 2700 RPM (90 Hz)
5 = 3000 RPM (100 Hz)
6 = 3300 RPM (110 Hz)
7 = 3600 RPM (120 Hz)
Max Speed Switch (SW2) Accel/Decel Switch (SW1)
ATTENTION: All adjustments to these components
should be made with the power removed.Failure to
observe this precaution could result in severe bodily
injury or loss of life.
ATTENTION: After disconnecting input power, wait
five minutes and check with voltmeter to assure that
DC bus capacitors are discharged (DC+, DC-).
The voltmeter should read zero volts.
Control SignalTerminal Block
ATTENTION: The cover screws must be securely
tightened in order to properly ground the cover.
Verify that all four cover screws are tight before
applying power to the unit.Failure to observe this
precaution may result in severe bodily injury or loss
of life.
Standard Unit Local Operator Control Unit
Connect to external device.
➋The jumper between terminals 7 and 11 must be removed when wiring
the Function Loss input. See Section 7.1 of the User Manual for more information. ➌The jumper between terminals 13 and 17 must be removed when wiring
the Stop input. See Section 7.6 of the User Manual for more information.
➊An external 0 to 10 volt or 4 to 20 mA speed reference source can
be connected. See Section 7.5.3 of the User Manual for more information.
= N.O.Momentary Contact
= N.C.Momentary Contact
= Maintained Contact - Closed
= Maintained Contact - Open
Ground
= Default Setting (OFF Position)
Connect to external device.
DC+
DC-
DBR
T/L3
S/L2
R/L1

Other manuals for Series B

11

This manual suits for next models

1

Popular Drill manuals by other brands

Wesco WS3173 manual

Wesco

Wesco WS3173 manual

Powerplus POWDP1510 manual

Powerplus

Powerplus POWDP1510 manual

Go-On BM 650E operating instructions

Go-On

Go-On BM 650E operating instructions

Delta DP300L instruction manual

Delta

Delta DP300L instruction manual

BLACK DECKER BEHD201 instruction manual

BLACK DECKER

BLACK DECKER BEHD201 instruction manual

BLACK DECKER KR5010 Original instructions

BLACK DECKER

BLACK DECKER KR5010 Original instructions

Tack life PID03B user manual

Tack life

Tack life PID03B user manual

MasterForce 241-0401 Operator's manual

MasterForce

MasterForce 241-0401 Operator's manual

Bauer HYPERMAX 1992C-B user manual

Bauer

Bauer HYPERMAX 1992C-B user manual

Taurox 120 user manual

Taurox

Taurox 120 user manual

Bosch 26618 Specifications

Bosch

Bosch 26618 Specifications

Hilti UD30 operating instructions

Hilti

Hilti UD30 operating instructions

BTI A18 SBS BL Original instructions

BTI

BTI A18 SBS BL Original instructions

DeWalt XR Li-Ion DCD771 instruction manual

DeWalt

DeWalt XR Li-Ion DCD771 instruction manual

Bosch GSR18V-755C Operating/safety instructions

Bosch

Bosch GSR18V-755C Operating/safety instructions

Kernlochbohrer MKB-60RL operating instructions

Kernlochbohrer

Kernlochbohrer MKB-60RL operating instructions

Makita HP2050 instruction manual

Makita

Makita HP2050 instruction manual

Milwaukee MX FUEL MXF302 Operator's manual

Milwaukee

Milwaukee MX FUEL MXF302 Operator's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.