Altherma EKHBH016AA User manual

1 2
1x 1x 1x1x2x2x2x 1x1x 1x 1x
12 1x
345 67 12354
3
45
≥350
300
35
48
35 668
895
922
39
361
48
142 101
235 235
502
500
23˚
30˚
47˚
400
90˚
200
1
2
3
4
5
3/4" FBSP
1/2" FBSP
0~40
0
H 300
630
220
110
1
2
3
4
5
6
Ø580
3/4" FBSP
3/4" FBSP
3/4" FBSP
≥1150
1-1/4" FBSP
1-1/4" MBSP
96
30°
90°
12
3 5
4

Daikin Europe N.V.
EN60335-2-40,
Low Voltage 2006/95/EC
Machinery Safety 98/37/EEC
Electromagnetic Compatibility 2004/108/EC *
Jiro Tomita
Director Quality Assurance
Ostend, 21st of July 2007
CE - DECLARATION-OF-CONFORMITY
CE - KONFORMITÄTSERKLÄRUNG
CE - DECLARATION-DE-CONFORMITE
CE - CONFORMITEITSVERKLARING
CE - DECLARACION-DE-CONFORMIDAD
CE - DICHIARAZIONE-DI-CONFORMITA
CE - ¢H§ø™H ™YMMOPºø™H™
CE - DECLARAÇÃO-DE-CONFORMIDADE
СЕ - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ
CE - OPFYLDELSESERKLÆRING
CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE
CE - ERKLÆRING OM-SAMSVAR
CE - ILMOITUS-YHDENMUKAISUUDESTA
CE -
PROHLÁŠENÍ-O-SHODĚ
CE -
IZJAVA-O-USKLAĐENOSTI
CE - MEGFELELŐSÉGI-NYILATKOZAT
CE -
DEKLARACJA-ZGODNOŚCI
CE -
DECLARAŢIE-DE-CONFORMITATE
CE - I
ZJAVA O SKLADNOSTI
CE -
VASTAVUSDEKLARATSIOON
CE -
ДЕКЛАРАЦИЯ-ЗА-СЪОТВЕТСТВИЕ
CE -
ATITIKTIES-DEKLARACIJA
CE -
ATBILSTĪBAS-DEKLARĀCIJA
CE -
VYHLÁSENIE-ZHODY
CE - UYUMLULUK-BİLDİRİSİ
01
are in conformity with the following standard(s) or other normative document(s), provided that these are used in accordance with our
instructions:
02
der/den folgenden Norm(en) oder einem anderen Normdokument oder -dokumenten entspricht/entsprechen, unter der Voraussetzung,
daß sie gemäß unseren Anweisungen eingesetzt werden:
03
sont conformes à la/aux norme(s) ou autre(s) document(s) normatif(s), pour autant qu'ils soient utilisés conformément à nos instructions:
04
conform de volgende norm(en) of één of meer andere bindende documenten zijn, op voorwaarde dat ze worden gebruikt overeenkomstig
onze instructies:
05
están en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) normativo(s), siempre que sean utilizados de acuerdo con
nuestras instrucciones:
06
sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a carattere normativo, a patto che vengano usati in conformità alle
nostre istruzioni:
07
Â›Ó·È Û‡Ìʈӷ Ì ÙÔ(·) ·ÎfiÏÔ˘ıÔ(·) ÚfiÙ˘Ô(·) ‹ ¿ÏÏÔ ¤ÁÁÚ·ÊÔ(·) ηÓÔÓÈÛÌÒÓ, ˘fi ÙËÓ ÚÔ¸fiıÂÛË fiÙÈ ¯ÚËÛÈÌÔÔÈÔ‡ÓÙ·È
Û‡Ìʈӷ Ì ÙȘ Ô‰ËÁ›Â˜ Ì·˜:
08
estão em conformidade com a(s) seguinte(s) norma(s) ou outro(s) documento(s) normativo(s), desde que estes sejam utilizados de
acordo com as nossas instruções:
09
соответствуют следующим стандартам или другим нормативным документам, при условии их использования согласно нашим
инструкциям:
10
overholder følgende standard(er) eller andet/andre retningsgivende dokument(er), forudsat at disse anvendes i henhold til vore
instrukser:
11
respektive utrustning är utförd i överensstämmelse med och följer följande standard(er) eller andra normgivande dokument, under
förutsättning att användning sker i överensstämmelse med våra instruktioner:
12
respektive utstyr er i overensstemmelse med følgende standard(er) eller andre normgivende dokument(er), under forutssetning av at
disse brukes i henhold til våre instrukser:
13
vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen, että niitä käytetään ohjeidemme
mukaisesti:
14
za předpokladu, že jsou využívány v souladu s našimi pokyny, odpovídají následujícím normám nebo normativním dokumentům:
15
u skladu sa slijedećim standardom(ima) ili drugim normativnim dokumentom(ima), uz uvjet da se oni koriste u skladu s našim uputama:
16
megfelelnek az alábbi szabvány(ok)nak vagy egyéb irányadó dokumentum(ok)nak, ha azokat előírás szerint használják:
17
spełniają wymogi następujących norm i innych dokumentów normalizacyjnych, pod warunkiem że używane są zgodnie z naszymi
instrukcjami:
18
sunt în conformitate cu următorul (următoarele) standard(e) sau alt(e) document(e) normativ(e), cu condiţia ca acestea să fie utilizate în
conformitate cu instrucţiunile noastre
19
skladni z naslednjimi standardi in drugimi normativi, pod pogojem, da se uporabljajo v skladu z našimi navodili:
20
on vastavuses järgmis(t)e standardi(te)ga või teiste normatiivsete dokumentidega, kui neid kasutatakse vastavalt meie juhenditele:
21
съответстват на следните стандарти или други нормативни документи, при условие, че се използват съгласно нашите
инструкции:
22
atitinka žemiau nurodytus standartus ir (arba) kitus norminius dokumentus su sąlyga, kad yra naudojami pagal mūsų nurodymus:
23
tad, ja lietoti atbilstoši ražotāja norādījumiem, atbilst sekojošiem standartiem un citiem normatīviem dokumentiem:
24
sú v zhode s nasledovnou(ými) normou(ami) alebo iným(i) normatívnym(i) dokumentom(ami), za predpokladu, že sa používajú v súlade
s našim návodom:
25
ürünün, talimatlarımıza göre kullanılması koşuluyla aşağıdaki standartlar ve norm belirten belgelerle uyumludur:
01
Directives, as amended.
02
Direktiven, gemäß Änderung.
03
Directives, telles que modifiées.
04
Richtlijnen, zoals geamendeerd.
05
Directivas, según lo enmendado.
06
Direttive, come da modifica.
07
√‰ËÁÈÒv, fiˆ˜ ¤¯Ô˘Ó ÙÚÔÔÔÈËı›.
08
Directivas, conforme alteração em.
09
Директив со всеми поправками.
10
Direktiver, med senere ændringer.
11
Direktiv, med företagna ändringar.
12
Direktiver, med foretatte endringer.
13
Direktiivejä, sellaisina kuin ne ovat muutettuina.
14
v platném znění.
15
Smjernice, kako je izmijenjeno.
16
irányelv(ek) és módosításaik rendelkezéseit.
17
z późniejszymi poprawkami.
18
Directivelor, cu amendamentele respective.
19
Direktive z vsemi spremembami.
20
Direktiivid koos muudatustega.
21
Директиви, с техните изменения.
22
Direktyvose su papildymais.
23
Direktīvās un to papildinājumos.
24
Smernice, v platnom znení.
25
Değiştirilmiş halleriyle Yönetmelikler.
01
following the provisions of:
02
gemäß den Vorschriften der:
03
conformément aux stipulations des:
04
overeenkomstig de bepalingen van:
05
siguiendo las disposiciones de:
06
secondo le prescrizioni per:
07
Ì ًÚËÛË Ùˆv ‰È·Ù¿Íˆv Ùˆv:
08
de acordo com o previsto em:
09
в соответствии с положениями:
10
under iagttagelse af bestemmelserne i:
11
enligt villkoren i:
12
gitt i henhold til bestemmelsene i:
13
noudattaen määräyksiä:
14
za dodržení ustanovení předpisu:
15
prema odredbama:
16
követi a(z):
17
zgodnie z postanowieniami Dyrektyw:
18
în urma prevederilor:
19
ob upoštevanju določb:
20
vastavalt nõuetele:
21
следвайки клаузите на:
22
laikantis nuostatų, pateikiamų:
23
ievērojot prasības, kas noteiktas:
24
održiavajúc ustanovenia:
25
bunun koşullarına uygun olarak:
01 Note *
as set out in
<A>
and judged positively by
<B>
according to the
Certificate
<C>
.
02 Hinweis *
wie in der
<A>
aufgeführt und von
<B>
positiv
beurteilt gemäß
Zertifikat
<C>
.
03 Remarque *
tel que défini dans
<A>
et évalué positivement par
<B>
conformément au
Certificat <C>
.
04 Bemerk *
zoals vermeld in
<A>
en positief beoordeeld door
<B>
overeenkomstig
Certificaat <C>
.
05 Nota
*
como se establece en
<A>
y es valorado
positivamente por
<B>
de acuerdo con el
Certificado <C>
.
06 Nota *
delineato nel
<A>
e giudicato positivamente
da
<B>
secondo il
Certificato <C>
.
07
™ËÌ›ˆÛË
* fiˆ˜ ηıÔÚ›˙ÂÙ·È ÛÙÔ
<A>
Î·È ÎÚ›ÓÂÙ·È ıÂÙÈο
·fi ÙÔ
<B>
Û‡Ìʈӷ Ì ÙÔ
¶ÈÛÙÔÔÈËÙÈÎfi <C>
.
08 Nota
*
tal como estabelecido em
<A>
e com o parecer
positivo de
<B>
de acordo com o
Certificado <C>
.
09 Примечание *
как указано в
<A>
и в соответствии с
положительным решением
<B>
согласно
Свидетельству <C>
.
10 Bemærk *
som anført i
<A>
og positivt vurderet af
<B>
i
henhold til
Certifikat <C>
.
11 Information *
enligt
<A>
och godkänts av
<B>
enligt
Certifikatet <C>
.
12 Merk *
som det fremkommer i
<A>
og gjennom positiv
bedømmelse av
<B>
ifølge
Sertifikat <C>
.
13 Huom *
jotka on esitetty asiakirjassa
<A>
ja jotka
<B>
on
hyväksynyt
Sertifikaatin <C>
mukaisesti.
14 Poznámka *
jak bylo uvedeno v
<A>
a pozitivně zjištěno
<B>
v
souladu s
osvědčením <C>
.
15 Napomena *
kako je izloženo u
<A>
i pozitivno ocijenjeno od
strane
<B>
prema
Certifikatu <C>
.
16 Megjegyzés *
a(z)
<A>
alapján, a(z)
<B>
igazolta a megfelelést,
a(z)
<C> tanúsítvány
szerint.
17 Uwaga *
zgodnie z dokumentacją
<A>
, pozytywną opinią
<B>
i
Świadectwem <C>
.
18
Notă *
aşa cum este stabilit în
<A>
şi apreciat pozitiv
de
<B>
în conformitate cu
Certificatul <C>
.
19 Opomba *
kot je določeno v
<A>
in odobreno s strani
<B>
v
skladu s
certifikatom <C>
.
20 Märkus
*
nagu on näidatud dokumendis
<A>
ja heaks
kiidetud
<B>
järgi vastavalt
sertifikaadile <C>
.
21 Забележка *
както е изложено в
<A>
и оценено
положително от
<B>
съгласно
Cертификата <C>
.
22 Pastaba *
kaip nustatyta
<A>
ir kaip teigiamai nuspręsta
<B>
pagal
Sertifikatą <C>
.
23 Piezīmes *
kā norādīts
<A>
un atbilstoši
<B>
pozitīvajam
vērtējumam saskaņā ar
sertifikātu <C>
.
24 Poznámka *
ako bolo uvedené v
<A>
a pozitívne zistené
<B>
v
súlade s
osvedčením <C>
.
25
Not
*
<A>
‘da belirtildiği gibi ve
<C> Sertifikasına
göre
<B>
tarafından olumlu olarak
değerlendirildiği gibi.
<A> DAIKIN.TCF.025C1/07-2007
<B> KEMA
<C> 2082543.0551-QUA/EMC
3PW33141-2B
01
a
declares under its sole responsibility that the equipment to which this declaration relates:
02
d
erklärt auf seine alleinige Verantwortung, dass die Ausrüstung für die diese Erklärung bestimmt ist:
03
f
déclare sous sa seule responsabilité que l’équipement visé par la présente déclaration:
04
l
verklaart hierbij op eigen exclusieve verantwoordelijkheid dat de apparatuur waarop deze verklaring betrekking heeft:
05
e
declara bajo su única responsabilidad que el equipo al que hace referencia la declaración:
06
i
dichiara sotto la propria responsabilità che gli apparecchi a cui è riferita questa dichiarazione:
07
g
‰ËÏÒÓÂÈ Ì ·ÔÎÏÂÈÛÙÈ΋ Ù˘ ¢ı‡ÓË fiÙÈ Ô ÂÍÔÏÈÛÌfi˜ ÛÙÔÓ ÔÔ›Ô ·Ó·Ê¤ÚÂÙ·È Ë ·ÚÔ‡Û· ‰‹ÏˆÛË:
08
p
declara sob sua exclusiva responsabilidade que os equipamentos a que esta declaração se refere:
09
u
заявляет, исключительно под свою ответственность, что оборудование, к которому относится настоящее заявление:
10
q
erklærer som eneansvarlig, at udstyret, som er omfattet af denne erklæring:
11
s
deklarerar i egenskap av huvudansvarig, att utrustningen som berörs av denna deklaration innebär att:
12
n
erklærer et fullstendig ansvar for at det utstyr som berøres av denne deklarasjon, innebærer at:
13
j
ilmoittaa yksinomaan omalla vastuullaan, että tämän ilmoituksen tarkoittamat laitteet:
14
c
prohlašuje ve své plné odpovědnosti, že zařízení, k němuž se toto prohlášení vztahuje:
15
y
izjavljuje pod isključivo vlastitom odgovornošću da oprema na koju se ova izjava odnosi:
16
h
teljes felelőssége tudatában kijelenti, hogy a berendezések, melyekre e nyilatkozat vonatkozik:
17
m
deklaruje na własną wyłączną odpowiedzialność, że urządzenia, których ta deklaracja dotyczy:
18
r
declară pe proprie răspundere că echipamentele la care se referă această declaraţie:
19
o
z vso odgovornostjo izjavlja, da je oprema naprav, na katero se izjava nanaša:
20
x
kinnitab oma täielikul vastutusel, et käesoleva deklaratsiooni alla kuuluv varustus:
21
b
декларира на своя отговорност, че оборудването, за което се отнася тази декларация:
22
t
visiška savo atsakomybe skelbia, kad įranga, kuriai taikoma ši deklaracija:
23
v
ar pilnu atbildību apliecina, ka tālāk aprakstītās iekārtas, uz kurām attiecas šī deklarācija:
24
k
vyhlasuje na vlastnú zodpovednosť, že zariadenie, na ktoré sa vzťahuje toto vyhlásenie:
25
w
tamamen kendi sorumluluğunda olmak üzere bu bildirinin ilgili olduğu donanımının aşağıdaki gibi olduğunu beyan eder:
EKHBH016AA***, EKHBX016AA***,
EKSWW150V3, EKSWW200V3, EKSWW300V3,
EKSWW200Z2, EKSWW300Z2,
EKSWWU150V3, EKSWWU200V3, EKSWWU300V3,
* = , , -, 1, 2, 3, ..., 9, A, B, C, ..., Z

Installation manual
1EKHBH/X016AA + EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
CONTENTS Page
Introduction ....................................................................................... 1
General information....................................................................................1
Scope of this manual..................................................................................2
Model identification ....................................................................................2
Accessories....................................................................................... 2
Accessories supplied with the indoor unit ..................................................2
Accessories supplied with the sanitary water tank (optional).....................2
Typical application examples............................................................. 3
Application 1 ..............................................................................................3
Application 2 ..............................................................................................3
Application 3 ..............................................................................................4
Application 4 ..............................................................................................4
Overview of the indoor unit ............................................................... 5
Opening the indoor unit..............................................................................5
Main components.......................................................................................6
Switch box main components .................................................................... 7
Functional diagram.....................................................................................7
Installation of the indoor unit ............................................................. 8
Selecting an installation location................................................................8
Dimensions and service space .................................................................. 8
Inspecting, handling and unpacking the unit..............................................8
Mounting the indoor unit ............................................................................9
Installation of the EKHBDP drain pan kit (only for EKHBX models)...........9
Refrigerant pipework..................................................................................9
Water pipework ..........................................................................................9
Charging water.........................................................................................11
Piping insulation.......................................................................................11
Field wiring...............................................................................................11
Sanitary water tank (optional) ......................................................... 14
Main components.....................................................................................14
Outlook diagram.......................................................................................15
Installation guidelines...............................................................................15
Installing the sanitary water tank..............................................................15
Connecting the water circuits...................................................................15
Field wiring...............................................................................................15
Start-up and configuration............................................................... 17
DIP switch settings overview....................................................................17
Room thermostat installation configuration..............................................17
Pump operation configuration ..................................................................17
Sanitary water tank installation configuration...........................................18
Initial start-up at low outdoor ambient temperatures................................ 18
Pre-operation checks ...............................................................................18
Powering up the indoor unit...................................................................... 18
Setting the pump speed ...........................................................................19
Field settings............................................................................................19
Test run and final check .................................................................. 24
Automatic test run ....................................................................................24
Test run operation (manual) .....................................................................24
Final check...............................................................................................24
Maintenance ................................................................................... 25
Troubleshooting............................................................................... 25
General guidelines ................................................................................... 25
General symptoms...................................................................................25
Error codes ..............................................................................................26
Technical specifications .................................................................. 28
General ....................................................................................................28
Electrical specifications............................................................................28
Sanitary water tank specifications (optional)............................................28
INTRODUCTION
General information
Thank you for purchasing this indoor unit.
The indoor unit is the indoor part of the
reversible air to water Daikin ERHQ heat pumps. These units are
designed for wall mounted indoor installation and used for both
heating and cooling applications. The units can be combined with
Daikin fan coil units, floor heating applications, low temperature
radiators and sanitary water heating applications.
Heating/cooling units and heating only units
The indoor unit range consists of two main
versions: a heating/cooling (EKHBX) version and a heating only
(EKHBH) version.
Both versions can optionally be delivered with an integrated backup
heater for additional heating capacity during cold outdoor
temperatures. The backup heater also serves as a backup in case of
malfunctioning of the outdoor unit. The backup heater models are
available for a heating capacity of 3, 6 and 9 kW, and – depending on
the heating capacity – for three different power supply specifications.
EKHBH016AA*** EKSWW150V3
EKHBX016AA*** EKSWW200V3 EKSWW200Z2
EKSWW300V3 EKSWW300Z2
Indoor unit for air to water heat pump and sanitary
warm water tank for air to water heat pump system Installation manual
READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.
THE UNIT DESCRIBED IN THIS MANUAL IS DESIGNED
FOR INDOOR INSTALLATION ONLY AND FOR AMBIENT
TEMPERATURES RANGING 0°C~35°C.
Indoor unit model Backup heater capacity Backup heater
nominal voltage
EKHB*016AA3V3 3 kW 1 x 230 V
EKHB*016AA6V3 6 kW 1 x 230 V
EKHB*016AA6WN 6 kW 3 x 400 V
EKHB*016AA9WN 9 kW 3 x 400 V
EKHB*016AA6T1 6 kW 3 x 230 V
EKHB*016AA9T1 9 kW 3 x 230 V
NOTE An EKHBH/X016AA indoor unit can only be connected
to an outdoor ERHQ0*AA-series.

EKHBH/X016AA + EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
Installation manual
2
Sanitary water tank option
An optional EKSWW sanitary water tank with integrated 3 kW
electrical booster heater can be connected to the indoor unit. The
sanitary water tank is available in three sizes: 150, 200 and 300 litre.
All models can be floor mounted, while the 150 litre model can be
wall mounted as well via option kit EKWBSWW150. The 200 and
300 litre models are also available as 400 V versions.
Drain pan kit
For heating/cooling versions (EKHBX), it is necessary to install the
EKHBDP drain pan kit (see "Accessories" on page 2).
For more information concerning the drain pan kit, refer to
"Installation of the EKHBDP drain pan kit (only for EKHBX models)"
on page 9.
Scope of this manual
This installation manual describes the procedures for unpacking,
installing and connecting all EKHBH/X indoor unit models and the
optional EKSWW sanitary water tanks.
Model identification
Indoor unit
Sanitary warm water tank (optional)
Drain pan kit (optional)
ACCESSORIES
Accessories supplied with the indoor unit
See figure 1
Accessories supplied with the sanitary water tank
(optional)
See figure 2
Optional equipment
■EKUSWW: installation kit, required for installation of EKSWWU*
sanitary tanks.
■EKWBSWW150: kit, including a wall bracket for a sanitary tank
of 150 litres.
■EKHBDP: drain pan kit, required for EKHBX models.
1Heat pump capacity
2Required heating capacity (site dependent)
3Additional heating capacity provided by the backup heater
4Equilibriumtemperature (can be set through the user interface,
refer to "Field settings" on page 19)
TAAmbient (outdoor) temperature
PHHeating capacity
NOTE Especially for the United Kingdom
For installation of an EKSWWU sanitary water tank,
refer to the installation manual supplied with the
EKUSWW installation kit.
NOTE Installation of the ERHQ heat pump outdoor is
described in the outdoor unit installation manual.
Operation of the indoor unit is described in the indoor
unit operation manual.
EK HB X016 AA 3V3
Backup heater nominal
voltage: (Optional)
V3 = 1P, 230 V
WN = 3P, 400 V
T1 = 3P, 230 V
Backup heater capacity (kW)
(Optional)
Series
Indication of heating/cooling capacity (kW)(a)
(a) For exact values, refer to "Technical specifications" on page 28.
X = heating and cooling,
H = heating only
Hydro Box
European Kit
TA
4
3
1
2
PHEK SWW U150 V3
Booster heater voltage
V3 = 1P, 230 V
Z2 = 2P, 400 V (only for 200 l and 300 l
models)
Indication of storage capacity in litres
Special version for United Kingdom only
Standard version when no letter is mentioned
Sanitary Warm Water
European Kit
EK HB DP 150
Drain Pan
Hydro Box
European Kit
1Installation manual
2Operation manual
3Unpacking instruction sheet
4Shut-off valve
5Wall mounting bracket
6Wiring diagram sticker (inside indoor unit cover)
7Indoor unit cover fixing screw
1Thermistor + connection wire (12 m)
2Prewired contactor and circuit breaker assembly
3Contactor fixing screw
4PG nipple
5PG nut
NOTE For accessories supplied with the EKSWWU sanitary
water tank, refer to the manual supplied with the
EKUSWW installation kit.

Installation manual
3EKHBH/X016AA + EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
TYPICAL APPLICATION EXAMPLES
The application examples given below are for illustration purposes
only.
Application 1
Space heating only application with a room thermostat connected to
the indoor unit.
Pump operation and space heating
When a room thermostat (T) is connected to the indoor unit, the
pump (4) will operate when there is a heating request from the room
thermostat, and the outdoor unit will start operating to achieve the
target leaving water temperature as set on the user interface.
When the room temperature is above the thermostat set point, the
outdoor unit and pump will stop operating.
Application 2
Space heating only application without room thermostat connected to
the indoor unit. The temperature in each room is controlled by a valve
on each water circuit. Sanitary warm water is provided through the
sanitary water tank which is connected to the indoor unit.
Pump operation
With no thermostat connected to the indoor unit (2), the pump (4) can
be configured to operate either as long as the indoor unit is on, or
until the required water temperature is reached.
Space heating
The outdoor unit (1) will operate to achieve the target leaving water
temperature as set on the user interface.
When the system is used in series
with another heat source (e.g. gas boiler), it shall be made
sure that the return water temperature to the heat
exchanger does not exceed 55°C. Daikin shall not be held
liable for any damage resulting from not observing this
rule.
1Outdoor unit 6Collector (field supply)
2Indoor unit 7Shut-off valve
3Heat exchanger FHL1..3 Floor heating loop
(field supply)
4Pump
5Shut-off valve TRoom thermostat
(field supply)
Make sure to connect the thermostat wires to the correct
terminals (see "Connection of the thermostat cable" on
page 13) and to configure the DIP switch toggle switches
correctly (see "Room thermostat installation configuration"
on page 17).
FHL1
FHL2
FHL3
T
5 64321
7
1Outdoor unit 10 Booster heater
2Indoor unit 11 Heat exchanger coil
3Heat exchanger 12 Sanitary water tank
4Pump FHL1..3 Floor heating loop
(field supply)
5Shut-off valve
6Collector (field supply) T1..3 Individual room
thermostat (field supply)
7Shut-off valve
8Motorised 3-way valve
(field supply) M1..3 Individual motorised
valve to control loop
FHL1 (field supply)
9By-pass valve
(field supply)
NOTE Details on pump configuration can be found under
"Pump operation configuration" on page 17.
When circulation in each space heating loop (FHL1..3) is
controlled by remotely controlled valves (M1..3), it is
important to provide a by-pass valve (9) to avoid the flow
switch safety device from being activated.
The by-pass valve should be selected as such that at all
time the minimum water flow as mentioned under "Water
pipework" on page 9 is guaranteed.
M
FHL1
FHL2
FHL3
M1
T1
M2
T2
M3
T3
54321
11
12
10
7
8 6 9

EKHBH/X016AA + EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
Installation manual
4
Sanitary heating
When sanitary heating mode is enabled (either manually by the user,
or automatically through a schedule timer) the target sanitary water
temperature will be achieved by a combination of the heat exchanger
coil and the electrical booster heater.
When the sanitary water temperature is below the user configured
set point, the 3-way valve will be activated to heat the sanitary water
by means of the heat pump. In case of large sanitary water demand
or a high sanitary water temperature setting, the booster heater (10)
can provide auxiliary heating.
Application 3
Space cooling and heating application with a room thermostat
suitable for cooling/heating changeover connected to the indoor
unit. Heating is provided through floor heating loops and fan coil
units. Cooling is provided through the fan coil units only.
Sanitary warm water is provided through the sanitary water tank
which is connected to the indoor unit.
Pump operation and space heating and cooling
According to the season, the customer will select cooling or heating
on the room thermostat (T). This selection is not possible by
operating the user interface.
When space cooling/heating is requested by the room thermostat
(T), the pump will start operating and the indoor unit (2) will switch to
"cooling mode"/"heating mode". The outdoor unit (1) will start
operating to achieve the target leaving cold/hot water temperature.
In case of cooling mode, the motorised 2-way valve (13) will close as
to prevent cold water running through the floor heating loops (FHL).
The ON/OFF setting of the heating/cooling operation is done by the
room thermostat and cannot be done by the user interface on the
indoor unit.
Sanitary heating
Sanitary water heating is as described under "Application 2" on
page 3.
Application 4
Space cooling and heating application without a room thermostat
connected to the indoor unit, but with a heating only room
thermostat controlling the floor heating and a cooling/heating
thermostat controlling the fan coil units. Heating is provided through
floor heating loops and fan coil units. Cooling is provided through the
fan coil units only.
It is possible to connect either a 2-wire or a 3-wire 3-way
valve (8). Make sure to fit the 3-way valve correctly. For
more details, refer to "Wiring the 3-way valve" on page 13.
NOTE The indoor unit can be configured so that at low
outdoor temperatures the sanitary water is exclusively
heated by the booster heater. This assures that the full
capacity of the heat pump is available for space
heating.
Details on sanitary water tank configuration for low
outdoor temperatures can be found under "Field
settings" on page 19, field settings [5-02] to [5-04].
1Outdoor unit 10 Booster heater
2Indoor unit 11 Heat exchanger coil
3Heat exchanger 12 Sanitary water tank
4Pump 13 Motorised 2-way valve
(field supply)
5Shut-off valve
6Collector (field supply) FCU1..3 Fan coil unit (field supply)
7Shut-off valve FHL1..3 Floor heating loop
(field supply)
8Motorised 3-way valve
(field supply) TRoom thermostat with
cooling/heating switch
(field supply)
M M
FHL1
T
FHL2
FHL3
FCU1
FCU2 FCU3
54321
6
12
7
8 13
11
12
10
Make sure to connect the thermostat wires to the correct
terminals (see "Connection of the thermostat cable" on
page 13) and to configure the DIP switch toggle switches
correctly (see "Room thermostat installation configuration"
on page 17).
Wiring of the 2-way valve (13) is different for a NC (normal
closed) valve and a NO (normal open) valve! Make sure to
connect to the correct terminal numbers as detailed on the
wiring diagram.
M
FCU1
FCU2 FCU3
T4 T5
T6
FHL1
FHL2
FHL3
T
54321
6
7
13
M
14 6
9

Installation manual
5EKHBH/X016AA + EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
Pump operation
With no thermostat connected to the indoor unit (2), the pump (4) can
be configured to operate either as long as the indoor unit is on, or
until the required water temperature is reached.
Space heating and cooling
According to the season, the customer will select cooling or heating
through the user interface on the indoor unit.
The outdoor unit (1) will operate in cooling mode or heating mode to
achieve the target leaving water temperature.
With the unit in heating mode, the 2-way valve (13) is open. Hot water
is provided to both the fan coil units and the floor heating loops.
With the unit in cooling mode, the motorised 2-way valve (13) is
closed to prevent cold water running through the floor heating loops
(FHL).
The ON/OFF setting of the heating/cooling operation is done by the
user interface on the indoor unit.
OVERVIEW OF THE INDOOR UNIT
Opening the indoor unit
■The front flap on the indoor unit cover gives access to the
manometer and user interface, and is equipped with a push lock
system. Push to open the front flap.
■The indoor unit cover can be removed by removing the 2 side
screws and unhitching the cover.
■To gain access to the switch box' internals – e.g. to connect the
field wiring – the switch box service panel can be removed.
Thereto, loosen the front screws and unhitch the switch box
service panel.
1Outdoor unit 14 Motorised 2-way valve for
activation of the room
thermostat (field supply)
2Indoor unit
3Heat exchanger
4Pump FCU1..3 Fan coil unit with
thermostat (field supply)
5Shut-off valve
6Collector (field supply) FHL1..3 Floor heating loop (field
supply)
7Shut-off valve
9By-pass valve (field
supply) THeating only room
thermostat (field supply)
13 Motorised 2-way valve
to shut off the floor
heating loops during
cooling operation (field
supply)
T4..6 Individual room
thermostat for fan coil
heated/cooled room (field
supply)
NOTE Details on pump configuration can be found under
"Pump operation configuration" on page 17.
When closing several loops in the system by remotely
controlled valves, it might be required to install a by-pass
valve (9) to avoid the flow switch safety device from being
activated. See also "Application 2" on page 3.
Wiring of the 2-way valve (13) is different for a NC (normal
closed) valve and a NO (normal open) valve! Make sure to
connect to the correct terminal numbers as detailed on the
wiring diagram.
Make sure to fix the cover with the screws and nylon
washers when installing the cover (screws and nylon
washers are delivered as accessory).
Parts inside the unit can be hot.
Switch off all power supply — i.e. outdoor unit power
supply and backup heater and sanitary water tank power
supply (if applicable) — before removing the switch box
service panel.

EKHBH/X016AA + EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
Installation manual
6
Main components 1Air purge valve
Remaining air in the water circuit will be automatically removed
via the air purge valve.
2Backup heater
The backup heater consists of an electrical heating element that
will provide additional heating capacity to the water circuit if the
heating capacity of the outdoor unit is insufficient due to low
outdoor temperatures.
3Temperature sensors
Four temperature sensors determine the water and refrigerant
temperature at various points in the water circuit.
4Switch box
The switch box contains the main electronic and electrical parts
of the indoor unit.
5Heat exchanger
6Expansion vessel (10 l)
7User interface
The user interface allows the installer and user to set up, use
and maintain the unit.
8Refrigerant liquid connection
9Refrigerant gas connection
10 Shut-off valves (accessory)
The shut-off valves on the water inlet connection and water
outlet connection allow isolation of the indoor unit water circuit
side from the residential water circuit side. This facilitates
draining and filter replacement of the indoor unit.
11 Water inlet connection
12 Water outlet connection
13 Drain and fill valves
14 Water filter
The water filter removes dirt from the water to prevent damage
to the pump or blockage of the evaporator. The water filter
should be cleaned on a regular base. See "Maintenance" on
page 25.
15 Expansion vessel drain valve
The drain valve of the expansion vessel allows draining the
remaining water in the expansion vessel after draining with the
drain and fill valves.
16 Manometer
The manometer allows readout of the water pressure in the
water circuit.
17 Flow switch
The flow switch checks the flow in the water circuit and protects
the heat exchanger against freezing and the pump against
damage.
18 Pump
The pump circulates the water in the water circuit.
19 Backup heater vessel
The backup heater heats the water in the backup heater vessel.
20 Backup heater thermal protector
The backup heater is equipped with a thermal protector. The
thermal protector is activated when the temperature becomes
too high.
21 Backup heater thermal fuse
The backup heater is equipped with a thermal fuse. The thermal
fuse is blown when the temperature becomes too high (higher
than the backup heater thermal protector temperature).
22 Pressure relief valve
The pressure relief valve prevents excessive water pressure in
the water circuit by opening at 3 bar and discharging some
water.
1
3
8
9
1
0
11
12
10
2
3
4
5
3
7
6
13
14
15
16
18
19
2
2
2
1
17
2
0
3

Installation manual
7EKHBH/X016AA + EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
Switch box main components
1Backup heater contactors K1M, K2M and K5M (optional)
2Main PCB
The main PCB (Printed Circuit Board) controls the functioning of
the unit.
3Booster heater contactor K3M (only for installations with sanitary
water tank)
4Booster heater circuit breaker F2B (only for installations with sanitary
water tank)
The circuit breaker protects the booster heater in the sanitary
water tank against overload or short circuit.
5Backup heater circuit breaker F1B (optional)
The circuit breaker protects the backup heater electrical circuit
against overload or short circuit.
6Ter minal blocks
The terminal blocks allow easy connection of field wiring.
7Cable tie mountings
The cable tie mountings allow to fix the field wiring with cable
ties to the switch box to ensure strain relief.
8Ter minal blocks X3M, X4M (only for installations with sanitary water
tank)
9PCB fuse FU1
10 DIP switch SS2
The DIP switch SS2 provides 4 toggle switches to configure
certain installation parameters. See "DIP switch settings
overview" on page 17.
11 X13A socket
The X13A socket receives the K3M connector (only for
installations with sanitary water tank).
12 X9A socket
The X9A socket receives the thermistor connector (only for
installations with sanitary water tank).
13 Pump fuse FU2 (in line fuse)
14 Pump relay K4M
15 Transformer T1R
Functional diagram
OPTION EKSWW
OPTION EKSWW
OPTION EKSWW
NL
L2L1
X3M (230V)
21
X4M
OPTIONAL
X2M
18171615
Q2L
3-way valve2-way valve
12114
thermostat
213 5678910 1314
thermal
fuse
F2B F1B
F2B F1B
K3M
K3M
K5M
K2M
K1M
T1R
TR1
K1M
K2M
K5M
OPTION EKSWW
A1P
A1P
K4M
X4M
X2M
X3M
X1M
X9A
X13A
SS2
FU1
1
4
2
10
11
12
9
8
6
6
7
3
5
X1M
L1L2 L3 N
FU2
13
14
15
1Outdoor unit 10 Flow switch
2Indoor unit 11 Shut-off valve water outlet
with drain valve (field
installation)
3Expansion vessel drain
valve
4Expansion vessel 12 Shut-off valve water inlet with
drain valve (field installation)
5Manometer
6Air purge valve 13 Filter
7Pressure relief valve 14 Heat exchanger
8Backup heater vessel
with backup heater R1T
R2T
R3T
R4T
Temperature sensors
9Pump
R4T
H2O
t >
R3T
t >
R2T
t >
R1T
t >
10
11
12
432 5 9
13141
6 7 8

EKHBH/X016AA + EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
Installation manual
8
INSTALLATION OF THE INDOOR UNIT
Selecting an installation location
The unit is to be wall mounted in an indoor location that meets the
following requirements:
■The installation location is frost-free.
■The space around the unit is adequate for servicing. (See
figure 3).
■The space around the unit allows for sufficient air circulation.
■There is a provision for condensate drain (only for EKHBX
models with drain pan kit EKHBDP) and pressure relief valve
blow-off.
■The installation surface is a flat and vertical non-combustible
wall, capable of supporting the operation weight of the unit (see
"Technical specifications" on page 28).
■There is no danger of fire due to leakage of inflammable gas.
■All piping lengths and distances have been taken into
consideration.
Dimensions and service space
Wall bracket dimensions
Required service space, see figure 3
Dimensions, see figure 4
Inspecting, handling and unpacking the unit
■The indoor unit is packed in a cardboard box, fixed by straps on
a wooden pallet.
■At delivery, the unit should be checked and any damage should
be reported immediately to the carrier claims agent.
■Check if all indoor unit accessories (see "Accessories" on
page 2) are enclosed.
■Bring the unit as close as possible to its final installation position
in its original package in order to prevent damage during
transport.
■The indoor unit weighs approximately 55 kg and should be lifted
by two persons using the two lifting bars provided.
Requirement Value
Maximum allowable refrigerant piping length between
outdoor unit and indoor unit 75 m
Minimum required refrigerant piping length between
outdoor unit and indoor unit 3 m(a)
(a) When <5 m, recharging of the outdoor unit is required. Refer to the
installation manual of the outdoor unit.
Maximum allowable height difference between
outdoor unit and indoor unit 30 m
Maximum allowable distance between the 3-way
valve and the indoor unit (only for installations with
sanitary water tank). 3 m
Maximum allowable distance between the sanitary
water tank and the indoor unit (only for installations
with sanitary water tank). The thermistor cable
supplied with the sanitary water tank is 12 m in
length.
10 m
NOTE If the installation is equipped with a sanitary water tank
(optional), please refer to "Sanitary water tank
(optional)" on page 14 for additional guidelines and
requirements.
1Flexible drain hose 5Refrigerant gas
connection
2Water outlet connection
3Water inlet connection FBSP Female British Standard
Pipe
4Refrigerant liquid
connection MBSP Male British Standard
Pipe
1010 163163 10
Do not grasp the switch box or piping to lift the unit! Two
lifting bars are provided to lift the unit.

Installation manual
9EKHBH/X016AA + EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
Mounting the indoor unit
1Fix the wall mounting bracket to the wall using appropriate plugs
and screws.
Make sure the wall mounting bracket is completely level. When
the unit is not installed level, air might get trapped in the water
circuit resulting in malfunctioning of the unit.
Pay special attention to this when installing an EKHBX model to
prevent overflow of the drain pan.
2Hang the indoor unit on the wall mounting bracket.
3Fix the indoor unit at the bottom side using appropriate plugs
and screws. To do so, the unit is equipped with 2 holes at the
bottom outer edges of the frame.
Installation of the EKHBDP drain pan kit (only for
EKHBX models)
For heating/cooling models, it is necessary to install the drain pan kit
(see "Accessories" on page 2).
During cooling operation, water vapour (humidity) in the air might
condense to liquid and collect on the cold refrigerant and water pipes.
This water is collected in the drain pan, which should be connected to
a drain.
For installation instructions, refer to the instruction sheet delivered
with the drain pan kit.
Refrigerant pipework
For all guidelines, instructions and specifications regarding
refrigerant pipework between the indoor unit and the outdoor unit,
please refer to the outdoor unit installation manual.
The location of the gas pipe and liquid pipe on the indoor unit is
shown under "Main components" on page 6.
Water pipework
Checking the water circuit
The units are equipped with a water inlet and water outlet for
connection to a water circuit. This circuit must be provided by a
licensed technician and must comply with all relevant European and
national regulations.
Before continuing the installation of the unit, check the following
points:
■The maximum water pressure is 3 bar.
■Two shut-off valves are delivered with the unit. To facilitate
service and maintenance, install one at the water inlet and one
at the water outlet of the indoor unit. Mind position of the shut-off
valves. Orientation of the integrated drain valves is important for
servicing. See figure 4.
■Drain taps must be provided at all low points of the system to
permit complete drainage of the circuit during maintenance.
Two drain valves integrated in the shut-off valves, and a drain
valve on the expansion vessel are provided to drain the water
from the indoor unit water system.
■Make sure to provide a proper drain for the pressure relief valve
to avoid any water coming into contact with electrical parts.
■Air vents must be provided at all high points of the system. The
vents should be located at points which are easily accessible for
servicing. An automatic air purge is provided inside the indoor
unit. Check that this air purge valve is not tightened too much so
that automatic release of air in the water circuit remains possible.
■Take care that the components installed in the field piping can
withstand the water pressure.
The weight of the indoor unit is approximately 55 kg. Two
persons are required to mount the unit.
3
2
1
Make sure to position the pressure relief valve hose end in
the drain pan. Failure to do so might lead to water coming
into contact with electrical parts, resulting in electrical
shocks or short-circuit of the electrical system.
Refrigerant piping
specifications Indoor unit Outdoor unit
Gas pipe outer diameter 15.9 mm (5/8 inch) 15.9 mm (5/8 inch)
Liquid pipe outer diameter 9.5 mm (3/8 inch) 9,5 mm (3/8 inch)
When connecting the refrigerant pipes, always use two
wrenches/spanners for tightening or loosening nuts!
Failure to do so can result in damaged piping connections
and leaks.
The unit is only to be used in a closed water system.
Application in an open water circuit can lead to excessive
corrosion of the water piping.

EKHBH/X016AA + EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
Installation manual
10
Checking the water volume and expansion vessel pre-
pressure
The unit is equipped with an expansion vessel of 10 litre which has a
default pre-pressure of 1 bar.
To assure proper operation of the unit, the pre-pressure of the
expansion vessel might need to be adjusted and the minimum and
maximum water volume must be checked.
1Check that the total water volume in the installation is 20 l
minimum.
2Using the table below, determine if the expansion vessel pre-
pressure requires adjustment.
3Using the table and instructions below, determine if the total
water volume in the installation is below the maximum allowed
water volume.
Calculating the pre-pressure of the expansion vessel
The pre-pressure (Pg) to be set depends on the maximum
installation height difference (H) and is calculated as below:
Pg=(H/10+0.3) bar
Checking the maximum allowed water volume
To determine the maximum allowed water volume in the entire circuit,
proceed as follows:
1Determine for the calculated pre-pressure (Pg) the
corresponding maximum water volume using the graph below.
2Check that the total water volume in the entire water circuit is
lower than this value.
If this is not the case, the expansion vessel inside the indoor unit is
too small for the installation.
Example 1
The indoor unit is installed 5 m below the highest point in the water
circuit. The total water volume in the water circuit is 100 l.
In this example, no action or adjustment is required.
Example 2
The indoor unit is installed at the highest point in the water circuit.
The total water volume in the water circuit is 350 l.
Result:
■Since 350 l is higher than 280 l, the pre-pressure must be
decreased (see table above).
■The required pre-pressure is:
Pg = (H/10 + 0.3) bar = (0/10 + 0.3) bar = 0.3 bar
■The corresponding maximum water volume can be read from
the graph: approximately 410 l.
■Since the total water volume (350 l) is below the maximum water
volume (410 l), the expansion vessel suffices for the installation.
Setting the pre-pressure of the expansion vessel
When it is required to change the default pre-pressure of the
expansion vessel (1 bar), keep in mind the following guidelines:
■Use only dry nitrogen to set the expansion vessel pre-pressure.
■Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system. Therefore, the pre-pressure
should only be adjusted by a licensed installer.
Connecting the water circuit
Water connections must be made in accordance with the outlook
diagram delivered with the unit, respecting the water in- and outlet.
If air, moisture or dust gets in the water circuit, problems may occur.
Therefore, always take into account the following when connecting
the water circuit:
■Use clean pipes only.
■Hold the pipe end downwards when removing burrs.
■Cover the pipe end when inserting it through a wall so that no
dust and dirt enter.
■Use a good thread sealant for the sealing of the connections.
The sealing must be able to withstand the pressures and
temperatures of the system.
■When using non-brass metallic piping, make sure to insulate
both materials from each other to prevent galvanic corrosion.
■Because brass is a soft material, use appropriate tooling for
connecting the water circuit. Inappropriate tooling will cause
damage to the pipes.
In most air conditioning applications this minimum water
volume will have a satisfying result.
In critical processes or in rooms with a high heat load
though, extra water volume might be required.
Installation
height
difference(a)
(a) Installation height difference: height difference (m) between the highest point of
the water circuit and the indoor unit. If the indoor unit is located at the highest
point of the installation, the installation height is considered 0 m.
Water volume
≤280 l >280 l
≤7 m No pre-pressure adjustment
required.
Actions required:
• pre-pressure must be decreased,
calculate according to "Calculating
the pre-pressure of the expansion
vessel"
• check if the water volume is lower
than maximum allowed water volume
(use graph below)
>7 m
Actions required:
• pre-pressure must be increased,
calculate according to "Calculating
the pre-pressure of the expansion
vessel"
• check if the water volume is lower
than maximum allowed water volume
(use graph below)
Expansion vessel of the unit
too small for the installation.
= pre-pressure
= maximum water volume
0.3
0.5
1
1.5
2
2.5
10050
0
20
150 200 250 300 350 400 450
maximum water volume [l]
pre-pressure [bar]
Be careful not to deform the unit piping by using excessive
force when connecting the piping. Deformation of the
piping can cause the unit to malfunction.
■The unit is only to be used in a closed water system.
Application in an open water circuit can lead to
excessive corrosion of the water piping.
■Never use Zn-coated parts in the water circuit.
Excessive corrosion of these parts may occur as
copper piping is used in the unit's internal water
circuit.
NOTE ■When using a 3-way valve in the water circuit.
Preferably choose a ball type 3-way valve to
guarantee full separation between sanitary warm
water and floor heating water circuit.
■When using a 3-way valve or a 2-way valve in the
water circuit.
The recommended maximum changeover time of
the valve should be less than 60 seconds.

Installation manual
11 EKHBH/X016AA + EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
Charging water
1Connect the water supply to a drain and fill valve (see "Main
components" on page 6).
2Make sure the automatic air purge valve is open (at least 2
turns).
3Fill with water until the manometer indicates a pressure of
approximately 2.0 bar. Remove air in the circuit as much as
possible using the air purge valves. Air present in the water
circuit might cause malfunctioning of the optional backup heater.
4For units with optional backup heater:
Check that the backup heater vessel is filled with water by
opening the pressure relief valve. Water must flow out of the
valve.
Piping insulation
The complete water circuit, inclusive all piping, must be insulated to
prevent condensation during cooling operation and reduction of the
cooling and heating capacity.
If the temperature is higher than 30°C and the humidity is higher than
RH 80%, then the thickness of the sealing materials should be at
least 20 mm in order to avoid condensation on the surface of the
sealing.
Field wiring
Overview
The illustration below gives an overview of the required field wiring
between several parts of the installation. Refer also to "Typical
application examples" on page 3.
NOTE ■During filling, it might not be possible to remove all
air in the system. Remaining air will be removed
through the automatic air purge valves during first
operating hours of the system. Additional filling
with water afterwards might be required.
■The water pressure indicated on the manometer
will vary depending on the water temperature.
(higher pressure at higher water temperature).
However, at all times water pressure should
remain above 0.3 bar to avoid air entering the
circuit.
■The unit might dispose some excessive water
through the pressure relief valve.
■Water quality must be according to EN directive
98/83 EC.
WARNING
■A main switch or other means for disconnection,
having a contact separation in all poles, must be
incorporated in the fixed wiring in accordance with
relevant local and national legislation.
■Switch off the power supply before making any
connections.
■All field wiring and components must be installed by a
licensed electrician and must comply with relevant
European and national regulations.
■The field wiring must be carried out in accordance
with the wiring diagram supplied with the unit and the
instructions given below.
■Be sure to use a dedicated power supply. Never use a
power supply shared by another appliance.
■Be sure to establish an earth. Do not earth the unit to
a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.
■Be sure to install an earth leakage protector (30 mA).
Failure to do so may cause electrical shock.
ASingle power supply for
outdoor unit, backup
heater and booster
heater (optional)
F3-way valve for sanitary
water tank (field supply,
optional)
G2-way valve for cooling
mode (field supply,
optional)
BOutdoor unit
CBackup heater HSanitary water tank
(optional)
DIndoor unit
ERoom thermostat (field
supply, optional) IBooster heater
(optional)
Item Description
Required
number of
conductors Maximum
running current
1Power supply cable for outdoor
unit 2+GND (a)
(a) Refer to nameplate on outdoor unit
2Indoor unit power supply and
communication cable 3+GND (b)
(b) Cable section 2.5 mm2
3Power supply cable for backup
heater 2+GND or
3+GND
(c)
(c) See table under "Connection of the backup heater power supply" on page 12.
4Room thermostat cable 3 or 4 100 mA(d)
(d) Minimum cable section 0.75 mm2
53-way valve control cable 2+GND 100 mA(d)
62-way valve control cable 2+GND 100 mA(d)
7Booster heater power supply
and thermal protection cable 4+GND (b)
8Thermistor cable 2 (e)
(e) The thermistor and connection wire (12 m) are delivered with the sanitary water
tank.
9Booster heater power supply
cable 2+GND 13 A
T
M
M
2
B
1 3
4
C5
6
7
8
D
A 9
E
H
I
G
F

EKHBH/X016AA + EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
Installation manual
12
Internal wiring - Parts table
Refer to the internal wiring diagram supplied with the unit (on the
inside of the indoor unit switch box cover). The abbreviations used
are listed below.
A1P..................Main PCB
A2P..................Remote controller PCB (user interface)
A3P..................Thermostat (field supply, PC= internal Power Circuit)
E1H..........*......Backup heater element 1
E2H..........*......Backup heater element 2
E3H..........*......Backup heater element 3
E4H......... #......Booster heater
F1B ..........*......Fuse backup heater
F2B ......... #......Fuse booster heater
F1T ..................Thermal fuse (250 V, 94°C)
FU1..................Fuse 3.15 A T 250 V
FU2..................Fuse 5 A T 250 V
K1M .........*......Contactor backup heater step 1
K2M .........*......Contactor backup heater step 2
K3M ........ #......Contactor booster heater
K4M .................Pump relay
K5M .................Contactor for thermal fuse
M1P .................Pump
M2S ...... ##......2-way valve for cooling mode
M3S ........ #......3-way valve: floor heating/sanitary warm water
Q1DI ................Earth leakage protector
Q1L..........*......Thermal protector backup heater
Q2L......... #......Thermal protector booster heater
R1T (A1P)........Outlet water heat exchanger thermistor
R2T..........*......Outlet water backup heater thermistor
R3T..................Refrigerant liquid side thermistor
R4T..................Inlet water thermistor
R5T......... #......SWW (sanitary warm water) thermistor
S1L ..................Flow switch
TR1..................Transformer 24 V for PCB
V1S..................Spark suppression 1
V2S..................Spark suppression 2
X1M-X4M.........Terminal blocks
Field wiring guidelines
■Most field wiring on the indoor unit side is to be made on the
terminal block inside the switch box. To gain access to the
terminal block, remove the indoor unit cover and switch box
service panel, see "Opening the indoor unit" on page 5.
■Cable tie mountings are provided at the bottom of the switch
box. Fix all cables using cable ties.
■A dedicated power circuit is required for the backup heater
(optional).
■Installations equipped with a sanitary water tank (optional),
require a dedicated power circuit for the booster heater.
Please refer to "Sanitary water tank (optional)" on page 14 for all
wiring specifications.
Connection of the indoor unit power supply and
communication cable
Power circuit and cable requirements
Power supply for the indoor unit is to be provided through the outdoor
unit. Data communication with the outdoor unit is provided through
the same cable.
For all guidelines and specifications regarding field wiring between
the indoor unit and the outdoor unit, please refer to the outdoor unit
installation manual.
Procedure
1Using the appropriate cable, connect the power circuit to the
appropriate terminals as shown on the wiring diagram and the
illustration below.
2Connect the earth conductor (yellow/green) to the earthing
screw on the switch box mounting plate.
3Fix the cable with cable ties to the cable tie mountings to ensure
strain relief.
4When routing out cables, make sure that these do not obstruct
mounting of the indoor unit cover, see figure 4.
Note: only relevant field wiring is shown.
Connection of the backup heater power supply
Power circuit and cable requirements
This power circuit must be protected with the required safety devices
according to local and national regulations.
Select the power cable in accordance with relevant local and national
regulations. For the maximum running current of the backup heater,
refer to the table below.
* Optional
# Applications with sanitary water tank only
## Heating/cooling applications only
■Be sure to use a dedicated power circuit for the
backup heater. Never use a power circuit shared by
another appliance.
■Use one and same dedicated power supply for the
outdoor unit, indoor unit, backup heater and booster
heater (sanitary water tank).
Indoor unit model Backupheater
capacity Backup heater
nominal voltage Maximum
running current
EKHB*016AA3V3 3 kW 1 x 230 V 13 A
EKHB*016AA6V3 6 kW 1 x 230 V 26 A
EKHB*016AA6WN 6 kW 3 x 400 V 8.6 A
EKHB*016AA9WN 9 kW 3 x 400 V 13 A
EKHB*016AA6T1 6 kW 3 x 230 V 15 A
EKHB*016AA9T1 9 kW 3 x 230 V 23 A
OPTION EKSWW
OPTION EKSWW
NL
L2L1
X3M (230V)
21
X4M
OPTIONAL
X2M
18171615
Q2L
3-way valve2-way valve
12114
thermostat
213 5678910 13 14
thermal
fuse
F2B F1B
A1P
K4M
X4M
X2M
X3M
X1M
123
1 3
2
X1M
123

Installation manual
13 EKHBH/X016AA + EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
Procedure
1Using the appropriate cable, connect the power circuit to the
main circuit breaker as shown on the wiring diagram and the
illustration below.
2Connect the earth conductor (yellow/green) to the earthing
screw on the X1M terminal.
3Fix the cable with cable ties to the cable tie mountings to ensure
strain relief.
Note: only relevant field wiring is shown.
Connection of the sanitary water tank field wiring
(optional)
Refer to "Sanitary water tank (optional)" on page 14 for wiring details.
Connection of the thermostat cable
Connection of the thermostat cable depends on the application.
See also "Typical application examples" on page 3 and "Room
thermostat installation configuration" on page 17 for more information
and configuration options on pump operation in combination with a
room thermostat.
Thermostat requirements
■Power supply: 230 V AC or battery operated
■Contact voltage: 230 V.
Procedure
1Connect the thermostat cable to the appropriate terminals as
shown on the wiring diagram.
2Fix the cable with cable ties to the cable tie mountings to ensure
strain relief.
3Set DIP switch SS2-3 on the PCB to ON. See "Room thermostat
installation configuration" on page 17 for more information.
Connection of the valve control cables
Valve requirements
■Power supply: 230 V AC
■Maximum running current: 100 mA
Wiring the 2-way valve
1Using the appropriate cable, connect the valve control cable to
the X2M terminal as shown on the wiring diagram.
2Fix the cable(s) with cable ties to the cable tie mountings to
ensure strain relief.
Wiring the 3-way valve
1Using the appropriate cable, connect the valve control cable to
the appropriate terminals as shown on the wiring diagram.
2Fix the cable(s) with cable ties to the cable tie mountings to
ensure strain relief.
Heating only thermostat Heating/cooling thermostat
OPTION EKSWW
OPTION EKSWW
NL
L2L1
X3M (230V)
21
X4M
OPTIONAL
X2M
18171615
Q2L
3-way valve2-way valve
12114
thermostat
213 567 8910 13 14
thermal
fuse
F2B F1B
A1P
K4M
X4M
X2M
X3M X1M
X1M
L1L2 L3 N
L1 L2 L3
3x 230 V
3x 400 V
X1M
X1M
L1 N
L1 N
1x 230 V
X2M
HC
th
LN
1234
X2M
HC
H
th
C
LN
1234
NOTE Wiring is different for a NC (normal closed) valve
and a NO (normal open) valve. Make sure to
connect to the correct terminal numbers as
detailed on the wiring diagram and illustrations
below.
Normal closed (NC) 2-way valve Normal open (NO) 2-way valve
Two types of 3-way valves can be connected. Wiring
is different for each type:
■"Spring return 2-wire" type 3-way valve
The 3-way valve should be fitted as such that
when the 3-way valve is idle (not activated), the
space heating circuit is selected.
■"SPST 3-wire" type 3-way valve
The 3-way valve should be fitted as such that
when terminal ports 9 and 10 are electrified, the
sanitary heating circuit is selected.
"Spring return 2-wire" valve "SPST 3-wire" valve
NC
5X2M 67
M
NO
56X2M 7
M
9X2M 810
M
9X2M 8 10
M

EKHBH/X016AA + EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
Installation manual
14
SANITARY WATER TANK (OPTIONAL)Following descriptions are only for EKSWW*V3
models, not for EKSWWU*V3 models.
Main components
■The total system (indoor unit and
outdoor unit) is designed for combination with an
sanitary water tank. In case
another tank is being used in combination with the
indoor unit, Daikin cannot
guarantee neither good operation nor reliability of the
system. For those reasons Daikin cannot give
warranty of the system in such case.
■Sanitary water quality must be according to EN
directive 98/83 EC.
■For safety reasons, it is not allowed to add ethylene
glycol to the water circuit. Adding ethylene glycol
might lead to contamination of the sanitary water if a
leakage would occur in the heat exchanger coil.
■It is important that the storage capacity of the sanitary
water tank meets normal daily fluctuations in
consumption of hot water without any fall of the water
outlet temperature during use.
■Immediately after installation, the sanitary water tank
must be flushed with fresh water. This procedure must
be repeated at least once a day the first 5 consecutive
days after installation.
■In case of limited consumption of hot water, e.g. at
holiday residences or at houses that are occasionally
not occupied, the sanitary water tank installation must
be fitted with a shunt pump.
- The shunt pump can be time-controlled,
- the shunt pump must operate to circulate the
complete volume of the sanitary water tank 1.5
times per hour,
- and the shunt pump must operate, or be
programmed for operation, during 2 uninterrupted
hours per day at least.
NOTE For installation of an EKSWWU sanitary water tank,
refer to the installation manual supplied with the
EKUSWW installation kit.
1
2 3
4
1Cold water
connection
2Hot water
connection
3Shunt pump
(field supply)
4Non-return valve
(field supply)
1Field supply
2Hot water connection
3Pressure relief valve connection
4Pressure relief valve (field supply)
5Electrical box
6Electrical box lid
7Booster heater
8Threaded thermistor hole
9Flow inlet connection
10 Heat exchanger coil
11 Return outlet connection
12 Cold water connection
5
6
9
11
12
10
7
8
C
R
F
14
23
H

Installation manual
15 EKHBH/X016AA + EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
Safety devices
■Thermal protector — The booster heater in the sanitary water
tank is equipped with a thermal protector. The thermal protector
is activated when the temperature becomes too high. When
activated, the protector has to be reset on the sanitary water
tank by pressing the red button (for access, remove the electrical
box lid).
■Pressure relief valve — A pressure relief valve (field supply) in
accordance with relevant local and national regulations, and with
an opening pressure of maximum 10 bar must be connected to
the pressure relief valve connection.
Outlook diagram
Outlook diagram, see figure 5
Installation guidelines
Keep in mind the following guidelines when installing the sanitary
water tank:
■The installation location is frost-free.
■Make sure to make the piping in size 1" or more (and reduce to
3/4" at the inlet of the tank) as to have sufficient water volume in
the piping between indoor unit and sanitary water tank.
■Locate the sanitary water tank in a suitable position to facilitate
ease of maintenance; remember access is required to the
electrical box. Refer to the grey-coloured zones indicated in
figure 5.
■Provide a connection for the pressure relief valve blow-off and
drain.
■To avoid back siphonage it is advised to install a non-return
valve on the water inlet of the sanitary water tank in accordance
with local and national regulations.
■The sanitary water tank model
EKSWW(U)150V3 can be floor or wall
mounted. In case of wall mounting, wall
mounting kit EKWBSWW150 is required
(separate ordering).
Installing the sanitary water tank
1Check if all sanitary water tank accessories (see "Accessories"
on page 2) are enclosed.
2When floor mounting, place the sanitary water tank on a level
surface. When wall mounting (only for EKSWW(U)150V3
model), make sure the wall is sturdy. In both cases, make sure
the tank is mounted level.
3Apply thermal paste to the thermistor and insert the thermistor
as deep as possible in the thermistor socket. Fix using the nut
provided.
Connecting the water circuits
1Connect the water inlet and water outlet.
2Connect the hot and cold water supply tubes.
3Connect the pressure relief valve (field supply, opening pressure
maximum 10 bar) and drain.
Field wiring
Power circuit and cable requirements
For cable requirements and specifications, refer to "Field wiring" on
page 11.
Thermistor cable
The distance between the thermistor cable and power supply cable
must always be at least 5 cm to prevent electromagnetic interference
on the thermistor cable.
The electrical box lid must only be opened by a
licensed electrician.
Switch off the power supply before opening the
electrical box lid.
1Hot water and pressure relief valve connection
2Threaded thermistor hole
3Flow inlet connection from the main indoor unit
4Return outlet connection to the main indoor unit
5Cold water connection
6Sanitary water tank electrical box cable entry
Sanitary water tank model H
EKSWW150V3 900
EKSWW200V3/Z2 1150
EKSWW300V3/Z2 1600
NOTE It is important that the 3-way valve is fitted correctly!
Refer to "Wiring the 3-way valve" on page 13.
■A main switch or other means for disconnection,
having a contact separation in all poles, must be
incorporated in the fixed wiring in accordance with
relevant local and national legislation.
■All field wiring and components must be installed by a
licensed electrician and must comply with relevant
European and national regulations.
■The field wiring must be carried out in accordance
with the wiring diagram supplied with the unit and the
instructions given below.
■The sanitary water tank must be earthed via the
indoor unit.
■Be sure to use a dedicated power circuit. Never use a
power circuit shared by another appliance.
■Use one and same dedicated power supply for the
outdoor unit, indoor unit, backup heater and sanitary
water tank.
NOTE Select the power cable in accordance with relevant
local and national regulations.

EKHBH/X016AA + EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
Installation manual
16
Procedure
Connections to be made in the sanitary water tank electrical box
1Connect the booster heater power supply and thermal protection
cable as show in the wiring diagram below.
2Make sure to ensure strain relief of the cable by correctly
mounting the PG nipple and PG nut (delivered with the tank)
Connections to be made in the indoor unit switch box
3Mount the prewired contactor (K3M), circuit breaker (F2B) and
terminal blocks (X3M, X4M). The contactor and terminal blocks
should be fixed with the 3 x 2 screws supplied.
4Plug the connector connected to the contactor K3M in the
socket X13A on the PCB.
5Plug the thermistor cable connector in the socket X9A on the
PCB.
6Connect the prewired earth wires of the terminal block X3M and
X4M to the earthing screw.
7Connect the booster heater power supply and thermal protection
cable (field supply) to terminal X4M earth, 1, 2, and X2M 13, 14.
8Connect the booster heater power supply cable to the terminal
block X3M.
9Fix the cables to the cable tie mountings with cable ties to
ensure strain relief.
10 Set DIP switch SS2-2 on the PCB to ON. See "DIP switch
settings overview" on page 17 for more information.
11 When routing out cables, make sure that these do not obstruct
mounting of the indoor unit cover, see figure 4.
Note: only relevant field wiring is shown.
Switch off the power supply before making any
connections.
BLK Black BRN Brown
1
2
2
3
4
2X4M X2M1 1413
BLK
BRN
NL L2L1
X3M (230V)
21
X4
OPTIONAL
X2M
18171615
Q2L
3-way valve2-way valve
12114
thermostat
213 5678910 1314
thermal
fuse
F2B F1B
F2B F1B
K3M
K5M
K2M
K1M
T1
TR1
K1M
K2M
K5M
A1P
A1P
K4M
X4M
X2M
X1M
K3M
X3M X1M
1
230 V AC
3 kW 24
113
2
3
14
LNX4M X2M
>50 mm
X9A
X13A

Installation manual
17 EKHBH/X016AA + EKSWW150-300V3/Z2
Indoor unit for air to water heat pump and sanitary warm water tank for air to water heat pump system
4PW36978-1C
START-UP AND CONFIGURATION
The indoor unit should be configured by the installer to match the
installation environment (outdoor climate, installed options, etc.) and
user expertise.
DIP switch settings overview
DIP switch SS2 is located on the switch box' PCB (see "Switch box
main components" on page 7) and allows configuration of sanitary
water tank installation, room thermostat connection and pump
operation.
Room thermostat installation configuration
The following table summarizes the required configuration and
thermostat wiring at the terminal block in the switch box. Pump
operation is listed in the third column. The three last columns indicate
whether the following functionality is available on the user interface
(UI) or handled by the thermostat (T):
• space heating or cooling on/off (y)
• heating/cooling changeover (=)
• heating and cooling schedule timers (pr)
Pump operation configuration
Without room thermostat
When no thermostat is connected to the indoor unit, pump operation
will be determined by the leaving water temperature.
To force continuous pump operation when no room thermostat is
connected do the following:
- set toggle switch SS2-3 to ON,
- short-circuit the terminal numbers 23-17-13 on the terminal
block in the switch box.
With room thermostat
When a thermostat is connected to the indoor unit, the pump will
operate continuously whenever there is heating or cooling demand
requested by the thermostat.
It is important that all information in this chapter is read
sequentially by the installer and that the system is
configured as applicable.
Switch off the power supply before opening the switch box
service panel and making any changes to the DIP switch
settings.
DIP
switch
SS2 Description ON OFF
1Not applicable for installer — (Default)
2Sanitary water tank
installation
(see "Sanitary water tank
installation configuration"
on page 18)
Installed Not installed
(Default)
3Room thermostat
connection
(see "Room thermostat
installation configuration"
on page 17)
Room thermostat
connected No room
thermostat
connected
(Default)
4This setting(a) decides the
operation mode when
there is a simultaneous
demand for more space
heating/cooling and
sanitary water heating.
(a) only applicable in case DIP switch 2 = ON
Heating/cooling Sanitary (Default)
■When no room thermostat is connected to
the indoor unit, toggle switch SS2-3 should be
set to OFF.
■When a room thermostat is connected to the
indoor unit, toggle switch SS2-3 should be set
to ON.
■On the room thermostat, set the hysteresis appropriately to
prevent the pump from repeatedly turning on and off (i.e.
chattering), and thereby impacting the lifetime of the pump.
NOTE ■When a room thermostat is connected to the
indoor unit, the heating and cooling schedule
timers are never available. Other schedule timers
are not affected. For more information on the
schedule timers, refer to the operation manual.
■When a room thermostat is connected to the
indoor unit, and the =button or ybutton is
pressed, the centralised control indicator ewill
flash to indicate that the room thermostat has
priority and controls on/off operation and change
over operation.
4321
ONOFF
4321
ONOFF
4321
ONOFF
Thermostat Configuration Pump
operation yy
yy ==
== pp
pprr
rr
No thermostat •SS2-3 = OFF
•wiring: (non) determined by
leaving water
temperature (a)
(a) The pump will stop when space heating/cooling is turned off or when the water
reaches the desired water temperature as set on the user interface. With space
heating/cooling turned on, the pump will then run every 5 minutes during 3
minutes to check the water temperature.
UI UI UI
•SS2-3 = ON
•wiring: on when space
heating or
cooling is on
(y)
UI UI UI
Heating only
thermostat
•SS2-3 = ON
•wiring: on when
heating
request by
room
thermostat
T——
Thermostat with
heating/cooling
switch
•SS2-3 = ON
•wiring: on when
heating
request or
coolingrequest
by room
thermostat
TT—
th = Thermostat contact
C = Cooling contact
H = Heating contact
L, N = 230 V AC
NOTE To set the pump speed, refer to "Setting the pump
speed" on page 19.
X2M
HCLN
1234
X2M
HCLN
1234
X2M
HC
th
LN
1234
X2M
HC
H
th
C
LN
1234
This manual suits for next models
7
Table of contents
Other Altherma Air Conditioner manuals
Popular Air Conditioner manuals by other brands

Samsung
Samsung AJ NBNDEH Series user manual

EcoNet
EcoNet A2024AJVCA installation instructions

Carrier
Carrier 38BA Installation, Start-Up and Service Instructions

Frigidaire
Frigidaire LRA257ST216 installation instructions

Shinco
Shinco SPF1-10C owner's manual

Hitachi
Hitachi RAS-10NHZ4(H) instruction manual