Altherma ERYQ005-007A User manual

technical data
ERYQ005-007A
EKHBH007A / EKHBX007A
EKSWW150-300
EEDE06-9
Altherma

Zandvoordestraat 300
B - 8400 Ostend Belgium
www.daikineurope.com
ISO14001 assures an effective environmental
management system in order to help protect
human health and the environment from
potential impact of our activities, products and
services and to assist in maintaining and
improving the quality of the environment.
Daikin units comply with the European
regulations that guarantee the safety of the
product.
Daikin Europe N.V. is approved by LRQA for its
Quality Management System in accordance
with the ISO9001 standard. ISO9001 pertains
to quality assurance regarding design,
development, manufacturing as well as to
services related to the product.
“ The present publication is drawn up by way of
information only and does not constitute an offer binding
upon Daikin Europe N.V.. Daikin Europe N.V. has compiled
the content of this publication to the best of its
knowledge. No express or implied warranty is given for
the completeness, accuracy, reliability or fitness for
particular purpose of its content and the products and
services presented therein. Specifications are subject to
change without prior notice. Daikin Europe N.V. explicitly
rejects any liability for any direct or indirect damage, In the
broadest sense, arising from or related to the use and/or
interpretation of this publication. All content is
copyrighted by Daikin Europe N.V..”
Altherma
ERYQ005-007A
EKHBH007A / EKHBX007A
EKSWW150-300
EEDE06-9 - 07/2006
Printed in Belgium by Goekint Graphics
EEDE06- 9

technical data
ERYQ005-007A
EKHBH007A / EKHBX007A
EKSWW150-300
EEDE06-9
Altherma

• Chillers • R-410A • ALTHERMA
• Altherma • Chillers
4
ChilleAltherAltherR-410A
Cooling only
Heating only
Heat pump

• Altherma • Outdoor units 5
• Outdoor units • R-410A • ERYQ
TABLE OF CONTENTS
ERYQ
1Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Cooling/Heating capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 11
Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5 Piping diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6 Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7 Sound data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

• Outdoor units • R-410A • ERYQ
• Altherma • Outdoor units
6
1 Features
1
1
Outdooruni AlthermaERYQR-410A
• Cost effective alternative to a fossil fuel boiler
• Low energy bills and low CO2 emissions
• Easy to install
• Total solution for year round comfort

• Altherma • Outdoor units 7
• Outdoor units • R-410A • ERYQ
2 Specifications
1
2
2-1 NOMINAL CAPACITY AND
NOMINAL INPUT EKHBH* EKHBX*
ERYQ005A ERYQ006A ERYQ007A ERYQ005A ERYQ006A ERYQ007A
Indoor Units EKHBH007A* EKHBH007A* EKHBH007A* EKHBX007A* EKHBX007A* EKHBX007A*
Condition 1 Heating
capacity Minimum kW 4.36 4.36 4.36 4.36 4.36 4.36
Nominal kW 5.75 6.84 8.43 5.75 6.84 8.43
Maximum kW 7.45 8.79 9.58 7.45 8.79 9.58
Cooling
capacity Minimum kW - - - 3.67 3.67 3.67
NominalkW- - - 5.125.866.08
Maximum kW - - - 5.12 6.13 7.10
Heating PI Nominal kW 1.26 1.58 2.08 1.26 1.58 2.08
Cooling PI Nominal kW - - - 2.16 2.59 2.75
COP Nominal - 4.56 4.34 4.05 4.56 4.34 4.05
EER Nominal - - - - 2.37 2.26 2.21
Condition 2 Heating Minimum kW 3.87 3.87 3.87 3.87 3.87 3.87
Nominal kW 5.03 6.10 7.64 5.03 6.10 7.64
Maximum kW 6.68 7.98 8.76 6.68 7.98 8.76
Cooling Minimum kW - - - 4.82 4.82 4.82
NominalkW- - - 7.208.168.37
Maximum kW - - - 7.20 8.50 8.91
Heating PI Nominal kW 1.58 1.95 2.54 1.58 1.95 2.54
Cooling PI Nominal kW - - - 2.16 2.59 2.75
COP Nominal - 3.18 3.13 3.00 3.18 3.13 3.00
EER Nominal - - - - 3.33 3.15 3.04
Notes *Condition 1
- cooling Ta 35°C - LWE 7°C
- heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
* Condition 2
- cooling Ta 35°C - LWE 18°C (DT = 5°C)
- heating Ta DB/WB 7°C/6°C - LWC 45°C (DT = 5°C)
2-2 TECHNICAL SPECIFICATIONS ERYQ005A
(+ EKHBH) ERYQ006A
(+ EKHBH) ERYQ007A
(+ EKHBH) ERYQ005A
(+ EKHBX) ERYQ006A
(+ EKHBX) ERYQ007A
(+ EKHBX)
Casing Colour Ivory white
Material Polyester painted galvanised steel
Dimensions Unit Height mm 797
Width mm 960
Depth mm 390
Packing Height mm 735
Width mm 825
Depth mm 300
Weight Unit kg 56
Packed Unit kg 61
Packing Material EPS
Carton
Weight kg 5
Heat
Exchanger Dimensions Length mm 845
Nr of Rows 2
Fin Pitch mm 1.8
Nr of Stages 32
Tube type Hi-Xa(8)
Fin Type WF fin
Treatment Anti-corrosion treatment (PE)
Fan Type Propeller
Quantity 1
Motor Quantity 1
Output W 53
Compressor Quantity 1
Motor Model 2YC63BXD#C
Type Hermetically sealed swing compressor
Motor
Output W 1920

• Outdoor units • R-410A • ERYQ
• Altherma • Outdoor units
8
2 Specifications
1
2
Operation
Range Heating Min °CWB -20
Max °CWB 25
Cooling Min °CDB 7
Max °CDB 20
Sanitary water Min °CDB -20
Max °CDB 43
Sound Level
(nominal) Heating Sound
Power dBA646466646466
Sound
Pressure dBA484852484852
Cooling Sound
Power dBA 63 64 66
Sound
Pressure dBA 47 47 53
Refrigerant Type R-410A
Charge kg 1.7
Control Expansion valve(electronic type)
Nr of Circuits 1
Refrigerant Oil Type FVC50K
Charged Volume l 0.75
Piping
connections Liquid (OD) Type Flare connection
Diameter
(OD) mm 6,35
Gas Type Flare connection
Diameter
(OD) mm 15,9
Drain Quantity 1
Type Socket
Diameter
(OD) mm 18
Piping Length Minimum m 3
Maximum m 30
Additional Refrigerant
Charge kg/m 0.02 IF > 10m
Installation
height
difference
Maximum m 15
Max. internunit level
difference m20
Defrost Method Reverse cycle
Defrost Control Sensor for outdoor heatexchanger temperature
Capacity Control Method Inverter controlled
Standard
Accessories Item Installation manual
Quantity 1
Item Drain plug
Quantity 1
2-2 TECHNICAL SPECIFICATIONS ERYQ005A
(+ EKHBH) ERYQ006A
(+ EKHBH) ERYQ007A
(+ EKHBH) ERYQ005A
(+ EKHBX) ERYQ006A
(+ EKHBX) ERYQ007A
(+ EKHBX)

• Altherma • Outdoor units 9
• Outdoor units • R-410A • ERYQ
2 Specifications
1
2
2-3 ELECTRICAL SPECIFICATIONS ERYQ005A
(+ EKHBH) ERYQ006A
(+ EKHBH) ERYQ007A
(+ EKHBH) ERYQ005A
(+ EKHBX) ERYQ006A
(+ EKHBX) ERYQ007A
(+ EKHBX)
Power Supply Name V1
Phase 1˜
Frequency Hz 50
Voltage V 220-440
Voltage range Maximum V +10%
Current Maximum
running
Current
Cooling A 11
Heating A 11
Cooling A 16.25
Heating A 18
Recomended fuses A 20
Wiring
connections For Power
Supply Quantity 3
For connection
with indoor Quantity 4
Remark Included earth wiring

• Outdoor units • R-410A • ERYQ
• Altherma • Outdoor units
10
3 Capacity tables
3 - 1 Cooling/Heating capacity tables
1
3
COOLING
Model
Tamb (°C) 20 25 30 35 40 43
LWE (°C)
CC PI CC PI CC PI CC PI CC PI CC PI
005
7 6.01 1.56 5.73 1.75 5.43 1.95 5.12 2.16 4.80 2.39 4.59 2.53
11 6.81 1.57 6.50 1.77 6.17 1.98 5.83 2.21 5.30 2.32 4.98 2.38
13 7.23 1.57 6.90 1.78 6.56 2.00 6.20 2.23 5.56 2.28 5.18 2.30
16 7.88 1.56 7.54 1.78 7.17 2.01 6.79 2.26 5.95 2.22 5.46 2.18
20 8.80 1.55 8.42 1.79 8.03 2.03 7.63 2.29 6.48 2.13 5.82 1.99
006
7 7.15 2.05 6.84 2.28 6.50 2.52 6.13 2.77 5.35 2.68 4.89 2.59
11 8.09 2.09 7.73 2.34 7.34 2.59 6.94 2.87 5.84 2.62 5.21 2.43
13 8.57 2.11 8.20 2.36 7.79 2.63 7.36 2.91 6.09 2.59 5.36 2.34
16 9.33 2.13 8.92 2.40 8.49 2.68 8.03 2.97 6.46 2.53 5.57 2.20
20 10.4 2.16 9.9 2.44 9.48 2.73 8.99 3.04 6.96 2.44 5.82 1.99
007
7 8.24 2.43 7.90 2.68 7.52 2.94 7.10 3.23 5.68 2.86 4.87 2.59
11 9.26 2.49 8.87 2.76 8.45 3.05 7.79 3.31 6.12 2.80 5.18 2.43
13 9.79 2.52 9.38 2.80 8.93 3.10 8.14 3.36 6.34 2.77 5.33 2.35
16 10.6 2.57 10.17 2.86 9.69 3.17 8.68 3.41 6.67 2.71 5.55 2.20
20 11.7 2.63 11.3 2.94 10.75 3.26 9.39 3.48 7.09 2.61 5.80 1.99
HEATING (Peak values)
Model
LWC 30 35 40 45 50
Tamb
HC PI HC PI HC PI HC PI HC PI
005
-15 3.93 1.48 3.67 1.59 3.47 1.71 3.33 1.84 3.25 1.99
-10 4.65 1.52 4.32 1.65 4.07 1.79 3.89 1.94 3.78 2.10
-7 5.14 1.54 4.77 1.68 4.49 1.83 4.28 1.99 4.15 2.16
-2 6.06 1.57 5.62 1.72 5.28 1.88 5.03 2.06 4.87 2.25
2 6.89 1.57 6.38 1.74 6.00 1.91 5.72 2.11 5.53 2.31
7 8.03 1.57 7.45 1.75 7.00 1.94 6.68 2.15 6.47 2.37
006
-15 4.87 1.82 4.62 1.94 4.43 2.08 4.30 2.23 4.24 2.40
-10 5.67 1.88 5.34 2.02 5.09 2.18 4.92 2.36 4.82 2.55
-7 6.21 1.91 5.83 2.07 5.55 2.24 5.35 2.42 5.23 2.63
-2 7.23 1.95 6.77 2.13 6.42 2.32 6.17 2.52 6.02 2.75
2 8.14 1.97 7.61 2.16 7.21 2.37 6.92 2.59 6.74 2.83
7 9.40 1.98 8.79 2.19 8.32 2.42 7.98 2.66 7.78 2.92
007
-15 5.42 2.06 5.16 2.19 4.97 2.34 4.86 2.51 4.80 2.70
-10 6.27 2.13 5.93 2.29 5.68 2.46 5.51 2.65 5.42 2.86
-7 6.84 2.17 6.46 2.34 6.17 2.53 5.97 2.73 5.86 2.95
-2 7.92 2.22 7.45 2.41 7.10 2.62 6.85 2.85 6.70 3.10
2 8.9 2.26 8.35 2.46 7.93 2.69 7.65 2.93 7.47 3.20
7 10.2 2.28 9.58 2.51 9.10 2.76 8.76 3.02 8.56 3.31
HEATING (integrated values*)
Model
LWC 30 35 40 45 50
Tamb
HC PI HC PI HC PI HC PI HC PI
005
-15 3.50 1.40 3.27 1.51 3.09 1.62 2.97 1.75 2.89 1.89
-10 4.14 1.45 3.85 1.56 3.62 1.70 3.46 1.84 3.36 2.00
-7 4.52 1.45 4.20 1.58 3.95 1.72 3.77 1.87 3.65 2.03
-2 5.27 1.46 4.89 1.60 4.59 1.75 4.38 1.92 4.24 2.10
2 5.92 1.45 5.49 1.60 5.16 1.76 4.92 1.94 4.76 2.13
7 8.03 1.57 7.45 1.75 7.00 1.94 6.68 2.15 6.47 2.37
006
-15 4.34 1.73 4.11 1.85 3.94 1.98 3.83 2.12 3.77 2.28
-10 5.04 1.79 4.75 1.92 4.53 2.07 4.38 2.24 4.29 2.42
-7 5.46 1.80 5.13 1.94 4.88 2.10 4.71 2.28 4.60 2.47
-2 6.29 1.81 5.89 1.98 5.59 2.15 5.37 2.35 5.23 2.56
2 7.00 1.81 6.55 1.99 6.20 2.18 5.96 2.38 5.80 2.61
7 9.40 1.98 8.79 2.19 8.32 2.42 7.98 2.66 7.78 2.92
007
-15 4.82 1.96 4.59 2.08 4.43 2.23 4.32 2.39 4.27 2.56
-10 5.58 2.03 5.28 2.17 5.06 2.34 4.91 2.52 4.82 2.72
-7 6.02 2.04 5.69 2.20 5.43 2.37 5.26 2.57 5.15 2.78
-2 6.89 2.07 6.48 2.25 6.17 2.44 5.96 2.65 5.83 2.88
2 7.6 2.08 7.18 2.27 6.82 2.47 6.58 2.70 6.43 2.94
7 10.2 2.28 9.58 2.51 9.10 2.76 8.76 3.02 8.56 3.31
4TW56712-1A
SYMBOLS
CC : Cooling capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
HC : Heating capacity at maximum operating frequency, measured acc.
Eurovent 6/C/003-2006 (kW)
PI : Power input (kW)
LWE : Leaving Water Evaporator temperature (°C)
LWC : Leaving Water Condensor temperature (°C)
Tamb : Ambient temperature (°C) RH=85%
NOTES
1Cooling capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
2Heating capacity
Capacity is according to Eurovent rating standard 6/C/003-2006 and valid for
chilled water range Dt = 3∼8°C
3Power input
Power input is total input according to Eurovent rating standard 6/C/003-2006
* The integrated heating capacity and power
input, is the average heating capacity and
power input during 1 cycle. (from end of
defrost till end of the next defrost).

• Altherma • Outdoor units 11
• Outdoor units • R-410A • ERYQ
4 Dimensional drawing & centre of gravity
4 - 1 Dimensional drawing
1
4
ERYQ unit (mm)
3D051658B
Minimum space for air passage
Wall height on air outlet side =
less than 1200
Drain outlet
(I.D. J15.9 hose for connection)
4 x holes for anchor bolts (M8 or M10)
Name plate
Terminal strip with earth
terminal
Wiring inlet
Gas stop valve
(J15.9 CuT)
Liquid stop valve
(J6.4 CuT)
Service port
Outdoor air thermistor
Brand name label
In case of removing stop valve cover

• Outdoor units • R-410A • ERYQ
• Altherma • Outdoor units
12
4 Dimensional drawing & centre of gravity
4 - 2 Centre of gravity
1
4
ERYQ
4D042258G
The position of foundation bolt

• Altherma • Outdoor units 13
• Outdoor units • R-410A • ERYQ
5 Piping diagram
1
5
3D052750A
ERYQ
Outdoor temperature thermistor
Heat exchanger
Propeller fan
Capillary tube 2
Capillary tube 3
Liquid stop valve
Field piping
Filter
Muffler
Compressor
Muffler
Refrigerant flow
Cooling
Heating
Discharge pipe
thermistor
Heat
exchanger
thermistor
Muffler with
filter
Accumulator
Motor operated
valve
Four way valve
on : heating
Outdoor unit
Gas stop valve with
service port
Field piping
Muffler with filter
Capillary tube 1
Capillary tube 4
Filter

• Outdoor units • R-410A • ERYQ
• Altherma • Outdoor units
14
6 Wiring diagram
6 - 1 Wiring diagram
1
6
3D052296B
ERYQ
Z1C∼Z7C : Ferrite core
X1M, X2M : Terminal strip
Y1E : Electronic expansion valve coil
V2, V3, V5, V9, V100 : Varistor
SA2 : Surge arrester
FU1, FU2, FU3: : Fuse
AC1, AC2
U, V, W, X11A, X12A
E1, E2
HR1, HR2 : Connector
Q1L : Overload protector
PM1 : Power module
PCB1,2 : Printed circuit board
Y1R : Reversing solenoide valve coil
Sheet metal : Terminal strip fixed plate
g
Field wiring
Indoor
Outdoor
(outdoor)
(Condenser)
(discharge)
Power supply
To indoor unit
Sheet metal
MRM10, MRM20
MRC/W : Magnetic relay
R1T∼R3T : Thermistor
S2∼S102 : Connector
LEDA : Pilot lamp
L : Live
N : Neutral
SW1 : Forced operation on/off switch SW (SW1)
SW4 : Local setting SW (SW4)
M1C : Compressor motor
M1F : Fan motor
L1R : Reactor

• Altherma • Outdoor units 15
• Outdoor units • R-410A • ERYQ
6 Wiring diagram
6 - 2 External connection diagram
1
6
3TW56719-6
EKHB-A
Optional parts
Outdoor unit
Backup heater power supply (3/6/9kW): 400V or
230V + earth
NO valve:
NC valve:
Booster heater power supply (3kW): 400V or 230V
+ earth
Optional power supply
X1M:7-8-Earth
X1M:L-N-Earth
For more details please check unit wiring
diagram
4 core
Standard parts
Field supply
A3P (optional)
4 core
Indoor unit
X2M:1-2-3-Earth
Sanitary tank
R5T - Thermistor water
temperature
230V or 400V
2 core
Signal
Power supply booster
heater
Power supply
M2S (EKHBX Units)
for cooling mode
Room thermostat
User interface
X1M:9-10-11-Earth
Q2L - Clixon booster
heater
5 core
3 or 4 core
3 core
M3S (when EKSWW is installed)
selection sanitary-floorheating
2 core
2 core
2 way valve
3 way valve
Thermistor cable
Note: min. distance
to power cable =
3cm
3 core
Unit power supply: 230V + earth

• Outdoor units • R-410A • ERYQ
• Altherma • Outdoor units
16
7 Sound data
7 - 1 Sound pressure spectrum
1
7
3TW56717-1
Sound pressure level (dB)
Octave band center frequency (Hz)
ERYQ005ABV3
Cooling
NOTES
1 Data is valid at free field condition (measured in a
semi-anachoic room)
2 dB(A) = A-weighted sound power level (A-scale
according to IEC)
3 Reference acoustic pressure 0dB = 20μPa
4 If sound is measured under actual installation
conditions, the measured value will be higher due to
environmental noise and sound reflections.
Location of microphone
Microphone
Coil
3TW56717-1
Sound pressure level (dB)
Octave band center frequency (Hz)
ERYQ006ABV3
Cooling
NOTES
1 Data is valid at free field condition (measured in a
semi-anachoic room)
2 dB(A) = A-weighted sound power level (A-scale
according to IEC)
3 Reference acoustic pressure 0dB = 20μPa
4 If sound is measured under actual installation
conditions, the measured value will be higher due to
environmental noise and sound reflections.
Location of microphone
Microphone
Coil
3TW56717-1
Sound pressure level (dB)
Octave band center frequency (Hz)
ERYQ007ABV3
Cooling
NOTES
1 Data is valid at free field condition (measured in a
semi-anachoic room)
2 dB(A) = A-weighted sound power level (A-scale
according to IEC)
3 Reference acoustic pressure 0dB = 20μPa
4 If sound is measured under actual installation
conditions, the measured value will be higher due to
environmental noise and sound reflections.
Location of microphone
Microphone
Coil
3TW56717-2
Sound pressure level (dB)
Octave band center frequency (Hz)
ERYQ005ABV3
Heating
NOTES
1 Data is valid at free field condition (measured in a
semi-anachoic room)
2 dB(A) = A-weighted sound power level (A-scale
according to IEC)
3 Reference acoustic pressure 0dB = 20μPa
4 If sound is measured under actual installation
conditions, the measured value will be higher due to
environmental noise and sound reflections.
Location of microphone
Microphone
Coil

• Altherma • Outdoor units 17
• Outdoor units • R-410A • ERYQ
7 Sound data
7 - 1 Sound pressure spectrum
1
7
3TW56717-2
Sound pressure level (dB)
Octave band center frequency (Hz)
ERYQ006ABV3
Heating
NOTES
1 Data is valid at free field condition (measured in a
semi-anachoic room)
2 dB(A) = A-weighted sound power level (A-scale
according to IEC)
3 Reference acoustic pressure 0dB = 20μPa
4 If sound is measured under actual installation
conditions, the measured value will be higher due to
environmental noise and sound reflections.
Location of microphone
Microphone
Coil
3TW56717-2
Sound pressure level (dB)
Octave band center frequency (Hz)
ERYQ007ABV3
Heating
NOTES
1 Data is valid at free field condition (measured in a
semi-anachoic room)
2 dB(A) = A-weighted sound power level (A-scale
according to IEC)
3 Reference acoustic pressure 0dB = 20μPa
4 If sound is measured under actual installation
conditions, the measured value will be higher due to
environmental noise and sound reflections.
Location of microphone
Microphone
Coil

• Outdoor units • R-410A • ERYQ
• Altherma • Outdoor units
18
8 Operation range
1
8
4TW56713-1A
Cooling mode
Outdoor temp. (°CDB)
Leaving evaporator water temperature (°C)
Leaving condenser water temperature (°C)
Heating mode
Outdoor temp. (°CDB)
: Booster heater operation
only
Outdoor temp. (°CDB)
Sanitary mode
Leaving condenser water temperature (°C)

• Altherma • Indoor units 19
• Indoor units • R-410A • EKHBH / EKHBX
TABLE OF CONTENTS
EKHBH / EKHBX
1Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2 Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 25
Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5 Piping diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6 Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
External connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
7 Hydraulic performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Static pressure drop unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

• Indoor units • R-410A • EKHBH / EKHBX
• Altherma • Indoor units
20
1 Features
2
1
Indoorunit AlthermaEKHBH/EKH R-410A
• Cost effective alternative to a fossil fuel boiler
• Low energy bills and low CO2 emissions
• Easy to install
• Total solution for year round comfort
This manual suits for next models
3
Table of contents
Other Altherma Air Conditioner manuals
Popular Air Conditioner manuals by other brands

Sharp
Sharp Plasmacluster GS-XP07ER Operation manual

Vogue
Vogue 373008 Installation instructions & user guide

Whynter
Whynter MSFS-024H23016-01NE instruction manual

Mitsubishi Electric
Mitsubishi Electric CITY MULTI PKFY-P-VBM-E installation manual

Mitsubishi Electric
Mitsubishi Electric Mr.Slim PLA-RP-BA Series Operation manual

RV Products
RV Products Airxcel Chillgrille 8330 634 Series installation instructions