Ametek Drexelbrook ThePoint Series User manual

Leader in
Level Measurement
Installation and
Operating Instructions
ThePoint™ Series Point Level Switch
Auto Calibration or Manual Calibration
Selectable
Telephone: +1 215-674-1234
Fax: +1 215-674-2731
Website: www.drexelbrook.com

AMETEK Drexelbrook makes no warranty of any kind with regard to the material contained in
this manual, including, but not limited to, implied warranties or tness for a particular purpose.
Drexelbrook shall not be liable for errors contained herein or for incidental or consequential
damages in connection with the performance or use of material.
©AMETEK Drexelbrook

EDO # 05-19-110
PML1-LM
Issue # 16
ThePointTM Series Point Level Switch
Auto Calibration or Manual Calibration
Selectable

Contents

Contents
Section 1: Introduction...............................................................................................1
1.1 System Description.....................................................................................1
1.2 Technology..................................................................................................1
1.3 Model Number ............................................................................................2
1.4 Housing Dimensions...................................................................................4
Section 2: Installation.................................................................................................5
2.1 Unpacking...................................................................................................5
2.2 Mounting and Installation Guidelines..........................................................5
2.3 Installation of Flush-Mounted Sensing Elements........................................7
2.4 Input Wiring.................................................................................................8
2.5 Output Wiring – Relay Version....................................................................8
2.6 Output and LED Status...............................................................................9
2.7 Electronic Unit.............................................................................................10
2.8 Spark Protection .........................................................................................11
2.9 Sensing Element Connection......................................................................12
2.10 Calibration...................................................................................................14
Section 3: Troubleshooting........................................................................................23
3.1 Testing Sensing Element ............................................................................23
3.2 Testing Electronic Unit ................................................................................24
3.3 Testing Relay Circuits .................................................................................25
3.4 Over Range.................................................................................................25
3.5 Under Range...............................................................................................25
3.6 Testing Integral Cable .................................................................................26
3.7 Testing Remote Cable.................................................................................26
3.8 Factory Assistance......................................................................................27
3.9 Field Service ...............................................................................................27
3.10 Customer Training.......................................................................................27
3.11 Equipment Return.......................................................................................28
3.12 RF Point Level Troubleshooting Guide .......................................................29
............................................................................................31
4.1 Approvals Available.....................................................................................32
Section 5: Control Drawings......................................................................................33
5.1 FM / FMc Control Drawings ........................................................................33
5.2 ATEX Control Drawings ..............................................................................44
5.3 Heavy Duty Spark Protection......................................................................50
5.4 Adding a Padded Capacitor........................................................................52
5.5 Dual Seal Assembly for 700 Series Sensing Elements...............................55
Shortening or Lengthening Sensing Element .............................................................A1
CE Installation Supplement...........................................................................................A2

Section 1

Introduction
1
Section 1: Introduction
1.1 System Description
The AMETEK Drexelbrook ThePoint™ Series uses No-Cal™
technology to detect the presence or absence of material without
calibration or initiation via setpoint adjustments, push-buttons
or magnets.
Installation is simple and easy. Simply apply power and
ThePoint system is ready to detect the presence or absence
of material. Since ThePoint instrument does not require
calibration or setpoint adjustments, it is capable of operating
in non-dedicated tanks regardless of the material being
measured.
1.2 Technology
In a simple capacitance probe type sensing element, when
the level rises and material covers the probe, the capacitance
within the circuit between the probe and the media (conductive
applications) or the probe and the vessel wall (insulating
applications) increases. This is due to the dielectric constant (k)
of the material, which causes a bridge imbalance. The signal is
demodulated (rectied), amplied and the output is increased.
There are drawbacks, however, especially when there is coating
of the probe.
An RF Admittance level transmitter is the next generation.
Although similar to the capacitance concept, ThePoint employs
a radio frequency signal and adds the Cote-Shield™ circuitry
within the Electronics Unit.
This patented Cote-Shield™ circuitry is designed into ThePoint
series and enables the instrument to ignore the effect of buildup
or material coating on the sensing element. The sensing element
is mounted in the vessel and provides a change in RF admittance
indicating presence or absence of material. The Cote-ShieldTM
element of the sensor prevents the transmission of RF current
through the coating on the sensing element. The only path to
ground available for the RF current is through the material
being measured.
The result is an accurate measurement regardless of the amount
of coating on the probe, making it by far the most versatile
technology, good for very wide range conditions from cryogenics
to high temperature, from vacuum to 10,000 psi pressure, and
works with all types of materials.
k
air
A
d
Ckmedia
C=kA
d
C = k A
d
A
k
air
d
C
kmedia
Material to be
measured must be below
sensor when power is
applied.
Figure 1-2
RF Admittance Probe
with Cote-Shield
Figure 1-1
Simple Capacitance
Probe
(Insulating Media)

ThePoint Series
2
Sensing Element
Application Sensing Element Pressure/Temperature Wetted Parts
00 General purpose 700-1202-001 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and PEEK
700-1202-021 integral
01 Floating roof with 700-1202-012 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS, Brass,
cable attachment 700-1202-022 integral and PEEK
and brass bottom weight
02 General purpose, 700-1202-014 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and PEEK
longer insertion lengths 700-1202-024 integral
with cable attachment
and 316SS bottom weight
03 Proximity 700-1202-018 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and PEEK
700-1202-028 integral with 76 mm (3)
316SS proximity plate
04 General purpose, 700-1202-041 remote 69 bar @ 121°C (1000 PSI @ 250°F) 316SS and PEEK
high temperature 700-1202-042 integral 20.7 bar @ 232°C (300 PSI @ 450°F)
and pressure
06 General purpose with 700-1202-031 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and FDA grade
FDA approved 700-1202-032 integral PEEK
materials of construction
07 General purpose 700-1202-010 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and PEEK with
Granular materials 700-1202-020 integral 7/8 inch dia. 316SS collar
09 General purpose 700-1202-033 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and FDA grade
Granular materials with 700-1202-034 integral PEEK with 7/8 inch dia.
FDA approved 316SS collar
10 Corrosive liquids (2)(4)(9) 700-0001-018 remote 3.4 bar @ 149°C (50 PSI @ 300°F) PFA
11 General purpose, 700-0201-005 int/rem 69 bar @ 38°C (1000 PSI @ 100°F) 316SS and TFE
TFE compatibility required 34.5 bar @ 149°C (500psi @ 300°F)
12 Corrosive material, 700-0201-005 int/rem 69 bar @ 38°C (1000 PSI @ 100°F) Hastelloy C and TFE
higher pressure Hastelloy C 34.5 bar @ 149°C (500psi @ 300°F)
13 Sanitary (3) Non 3A 700-0201-019 int/rem 13.8 bar @ 149°C (200 PSI @ 300°F) 316/316L SS and TFE
14 General Purpose, LP 700-0202-002 int/rem 3.4 bar @ 149°C (50 PSI @ 300°F) 316SS and TFE
15 Heavy duty, agitated 700-0202-043 remote 69 bar @ 38°C (1000 PSI @ 100°F) 316SS and TFE
tanks or material 34.5 bar @ 149°C (500psi @ 300°F)
with high bulk density (1)
16 High Integrity Seal for 700-0002-360 int/rem 34.5 bar @ 149°C (500 PSI @ 300°F) PFA
Hazardous Materials
17 Sanitary (3) Non 3A LP 700-0202-029 int/rem 3.4 bar @ 149°C (50 PSI @ 300°F) 316SS and TFE
18 Corrosive material, 700-0001-022 int/rem 69 bar @ 38°C (1000 PSI @ 100°F) TFE
higher pressure with 34.5 bar @ 149°C (500 PSI @ 300°F)
waterlike viscosity (4)
19 Interface Measurement 700-0002-023 int/rem 69 bar @ 38°C (1000 PSI @ 100°F) 316SS and TFE
34.5 bar @ 149°C (500 PSI @ 300°F)
20 Miniature Pilot 700-0209-002 remote 6.9 bar @ 121°C (100 PSI @ 250°F) 316 SS and TFE
Plant Sensor (1)(7) 0 bar @ 232°C (0 PSI @ 450°F)
Fly Ash Precipitators, Baghouse, and Economizers (1) (6)
31 No hopper Installation 700-0029-001 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
32 Hopper Installation 700-0029-002 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
up to 200mm (8 inches)
33 Hopper Installation 700-0029-003 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
up to 406mm (16 inches)
34 Hopper Instalation 700-0029-004 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
up to 521mm (20.5 inches)
35 Hopper Installation 700-0029-005 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
up to 635mm (25 inches)
Plugged Chute Detection (1) (5)
50 Flush Mount Sensor 700-0207-001 remote 0.1 bar @ 82°C (1 PSI @ 180°F) 304 SS and
305mm2(12 inches2) Polyurethane
heavy duty
51 Flush Mount Sensor 700-0207-002 remote 0.1 bar @ 149°C (1 PSI @ 300°F) 304 SS and TFE
305mm2(12 inches2)
higher temperature
52 Flush Mount Sensor 700-0207-003 remote 0.1 bar @ 82°C (1 PSI @ 180°F) 304 SS and Neoprene
305mm2(12 inches2)
with curved radius 153, 229, 305 mm (6, 9, or 12 inches)
53 Flush Mount Sensor 700-0207-004 remote 0.1 bar @ 82°C (1 PSI @ 180°F) 410 SS and UHMW
305mm2(12 inches2) Polyethylene
extra heavy duty
55 Flush Mount Sensor 700-0207-006 remote 0.1 bar @ 82°C (1 PSI @ 180°F) 304 SS and
203mm2 (8 inches2) Polyurethane
heavy duty
67 3A Sanitary Sensor 700-3201-001 remote 13.8 bar @ 121°C (200 psi @ 250°F) 316 SS and PEEK
700-3201-002 integral
High Pressure / High Temperature
60 High Pressure & Temp. 700-0204-038 remote 137.9 bar @ 93°C (2000 PSI @ 200°F) 316SS and Ceramic
68.9 bar @ 260°C (1000 PSI @ 500°F)
61 High Temperature (1) 700-0204-002 remote 0 bar @ 816°C (0 PSI @ 1500°F) 316SS and Ceramic
62 High Pressure & Temp. 700-0204-048 remote 275.8 bar @316°C (4000 PSI @ 600°F) 316SS
ZZ Sensing Element Not Listed
Output
1One DPDT Relay, dry contacts, 5A, 120VAC (Min 100 mA / 12 VDC)
2One DPDT Relay, gold plated contacts (Max 200 mA / 12 VDC)
Housing
Technology
PRF Admittance
Input
LUniversal Power Supply 19-250 VAC, 18-200 VDC
Measurement Type
N Std Auto Cal
LStd 2 pF Fixed
T10 pF Auto Cal
V10 pF Fixed
HHi Sense .5 pF Auto Cal
PHi Sense .5 pF Fixed
GHi Sense Manual
MStd Sense Manual
Electronics
0Integral
1Remote, no cable
2Rmt. w/ 3 m (10 ft.) G.P. cable
3Rmt. w/ 7.6 m (25 ft.) G.P. cable
4Rmt. w/ 10.6 m (35 ft.) G.P. cable
5Rmt. w/ 15.2 m (50 ft.) G.P. cable
6Rmt. w/ 23 m (75 ft.) G.P. cable
IL CSL
xxxG 457 mm (18") 0 mm (0")
xxxH 914 mm (36") 254 mm (10")
xxxJ 914 mm (36") 0 mm (0")
xxxK 1219 mm (48") 254 mm (10")
xxxL 1524 mm (60") 254 mm (10")
P00X IL/CSL Other
A1BX IL/CSL factory set for Fly Ash
xxxZ Other
IL CSL
xxx1 457 mm (18") 152 mm (6")
xxx2 305 mm (12") 152 mm (6")
xxxA 152 mm (6") 51 mm (2")
xxxB 305 mm (12") 51 mm (2")
xxxC 305 mm (12") 89 mm (3.5")
xxxD 457 mm (18") 51 mm (2")
xxxE 457 mm (18") 89 mm (3.5")
xxxF 457 mm (18") 254 mm (10")
Mounting Type (See separate Mounting Chart for first three digits)
(1) Available with remote electronics only
(2) Use A1P mounting option
(3) Choose only sanitary mounting options
(4) Available with 0-inch CSL only
(5) Use P00X mounting option
(6) Use A1B mounting option
(7) Use A8B mounting option (¼-inch NPT)
(8) Choose from flange mounting only
(9) FM approved with remote electronics only
Not all mounting options available with all
sensing elements
7Rmt. w/ (25 ft.) Tri-Ax Cable
8Rmt. w/ (50 ft.) Tri-Ax Cable
9Rmt. w/ (75 ft.) Tri-Ax Cable
ARmt. w/ (10 ft.) Hi-Temp. Cable
BRmt. w/ (25 ft.) 1st 10ft Hi-Temp. Cbl.
CRmt. w/ (35 ft.) 1st 10ft Hi-Temp. Cbl.
DRmt. w/ (50 ft.) 1st 10ft Hi-Temp. Cbl.
ERmt. w/ (75 ft.) 1st 10ft Hi-Temp. Cbl.
FRmt. w/ (5 ft.) G.P. Cable
GRmt. w/ (5 ft.) Tri-Ax Cable
HRmt. w/ (10 ft.) Tri-Ax Cable
JRmt. w/ (35 ft.) Tri-Ax Cable
KRmt. w/ (5 ft.) Hi-Temp. Cable
Notes: CSL (Cote-Shield Length) should extend through Nozzle + Typical "Wall Buildup" + 2 Inches
Sensing Element
Application Sensing Element Pressure/Temperature Wetted Parts
00 General purpose 700-1202-001 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and PEEK
700-1202-021 integral
01 Floating roof with 700-1202-012 remote 13.8 bar @ 177°C (200 PSI @ 350°F) 316SS, Brass,
cable attachment 700-1202-022 integral and PEEK
and brass bottom weight
02 General purpose, 700-1202-014 remote 13.8 bar @ 177°C (200 PSI @ 350°F) 316SS and PEEK
longer insertion lengths 700-1202-024 integral
with cable attachment
and 316SS bottom weight
03 Proximity 700-1202-018 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and PEEK
700-1202-028 integral with 76 mm (3)
316SS proximity plate
04 General purpose, 700-1202-041 remote 69 bar @ 121°C (1000 PSI @ 250°F) 316SS and PEEK
high temperature 700-1202-042 integral 20.7 bar @ 232°C (300 PSI @ 450°F)
and pressure
06 General purpose with 700-1202-031 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and FDA grade
FDA approved 700-1202-032 integral PEEK
materials of construction
07 General purpose 700-1202-010 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and PEEK with
Granular materials 700-1202-020 integral 7/8 inch dia. 316SS collar
09 General purpose 700-1202-033 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and FDA grade
Granular materials with 700-1202-034 integral PEEK with 7/8 inch dia.
FDA approved 316SS collar
materials of construction
10 Corrosive liquids (2)(4)(9) 700-0001-018 remote 3.4 bar @ 149°C (50 PSI @ 300°F) PFA
11 General purpose, 700-0201-005 int/rem 69 bar @ 38°C (1000 PSI @ 100°F) 316SS and TFE
higher pressure 13.8 bar @ 232°C (200 PSI @ 450°F)
TFE compatibility required
12 Corrosive material, 700-0201-005 int/rem 69 bar @ 38°C (1000 PSI @ 100°F) Hastelloy C and TFE
higher pressure Hastelloy C 13.8 bar @ 232°C (200 PSI @ 450°F)
13 Sanitary (3) Non 3A 700-0201-019 int/rem 13.8 bar @ 149°C (200 PSI @ 300°F) 316/316L SS and TFE
14 General Purpose, 700-0202-002 int/rem 3.4 bar @ 149°C (50 PSI @ 300°F) 316SS and TFE
low pressure 1.4 bar @ 232°C (20 PSI @ 450°F)
15 Heavy duty, agitated 700-0202-043 remote 69 bar @ 38°C (1000 PSI @ 100°F) 316SS and TFE
tanks or material 13.8 bar @ 232°C (200 PSI @ 450°F)
with high bulk density (1)
16 High Integrity Seal for 700-0002-360 int/rem 34.5 bar @ 149°C (500 PSI @ 300°F) PFA
Hazardous Materials
17 Sanitary (3) Non 3A LP 700-0202-029 int/rem 3.4 bar @ 149°C (50 PSI @ 300°F) 316SS and TFE
18 Corrosive material, 700-0001-022 int/rem 69 bar @ 38°C (1000 PSI @ 100°F) TFE
higher pressure with 34.5 bar @ 149°C (500 PSI @ 300°F)
waterlike viscosity (4)
19 Interface Measurement 700-0002-023 int/rem 69 bar @ 38°C (1000 PSI @ 100°F) 316SS and TFE
34.5 bar @ 149°C (500 PSI @ 300°F)
20 Miniature Pilot 700-0209-002 remote 6.9 bar @ 121°C (100 PSI @ 250°F) 316 SS and TFE
Plant Sensor (1)(7) 0 bar @ 232°C (0 PSI @ 450°F)
Fly Ash Precipitators, Baghouse, and Economizers (1) (6)
31 No hopper Installation 700-0029-001 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
32 Hopper Installation 700-0029-002 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
up to 200mm (8 inches)
33 Hopper Installation 700-0029-003 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
up to 406mm (16 inches)
34 Hopper Instalation 700-0029-004 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
up to 521mm (20.5 inches)
35 Hopper Installation 700-0029-005 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
up to 635mm (25 inches)
Plugged Chute Detection (1) (5)
50 Flush Mount Sensor 700-0207-001 remote 0.1 bar @ 82°C (1 PSI @ 180°F) 304 SS and
305mm2(12 inches2) Polyurethane
heavy duty
51 Flush Mount Sensor 700-0207-002 remote 0.1 bar @ 149°C (1 PSI @ 300°F) 304 SS and TFE
305mm2(12 inches2)
higher temperature
52 Flush Mount Sensor 700-0207-003 remote 0.1 bar @ 82°C (1 PSI @ 180°F) 304 SS and Neoprene
305mm2(12 inches2)
with curved radius 153, 229, 305 mm (6, 9, or 12 inches)
53 Flush Mount Sensor 700-0207-004 remote 0.1 bar @ 82°C (1 PSI @ 180°F) 410 SS and UHMW
305mm2(12 inches2) Polyethylene
extra heavy duty
55 Flush Mount Sensor 700-0207-006 remote 0.1 bar @ 82°C (1 PSI @ 180°F) 304 SS and
203mm2 (8 inches2) Polyurethane
heavy duty
67 3A Sanitary Sensor 700-3201-001 remote 13.8 bar @ 121°C (200 psi @ 250°F) 316 SS and PEEK
700-3201-002 integral
High Pressure / High Temperature
60 High Pressure & Temp. 700-0204-038 remote 137.9 bar @ 93°C (2000 PSI @ 200°F) 316SS and Ceramic
68.9 bar @ 260°C (1000 PSI @ 500°F)
61 High Temperature (1) 700-0204-002 remote 0 bar @ 816°C (0 PSI @ 1500°F) 316SS and Ceramic
62 High Pressure & Temp. 700-0204-048 remote 275.8 bar @316°C (4000 PSI @ 600°F) 316SS
ZZ Sensing Element Not Listed
Output
08-16 mA
Housing
Technology
PRF Admittance
Input
TTwo Wire Power Supply 13 to 30 Vdc
Electronics
0Integral
1Remote, no cable
2Rmt. w/ 3 m (10 ft.) G.P. cable
3Rmt. w/ 7.6 m (25 ft.) G.P. cable
4Rmt. w/ 10.6 m (35 ft.) G.P. cable
5Rmt. w/ 15.2 m (50 ft.) G.P. cable
6Rmt. w/ 23 m (75 ft.) G.P. cable
IL CSL
xxxG 457 mm (18") 0 mm (0")
xxxH 914 mm (36") 254 mm (10")
xxxJ 914 mm (36") 0 mm (0")
xxxK 1219 mm (48") 254 mm (10")
xxxL 1524 mm (60") 254 mm (10")
P00X IL/CSL Other
A1BX IL/CSL factory set for Fly Ash
xxxZ Other
IL CSL
xxx1 457 mm (18") 152 mm (6")
xxx2 305 mm (12") 152 mm (6")
xxxA 152 mm (6") 51 mm (2")
xxxB 305 mm (12") 51 mm (2")
xxxC 305 mm (12") 89 mm (3.5")
xxxD 457 mm (18") 51 mm (2")
xxxE 457 mm (18") 89 mm (3.5")
xxxF 457 mm (18") 254 mm (10")
Mounting Type (See separate Mounting Chart for first three digits)
7Rmt. w/ (25 ft.) Tri-Ax Cable
8Rmt. w/ (50 ft.) Tri-Ax Cable
9Rmt. w/ (75 ft.) Tri-Ax Cable
ARmt. w/ (10 ft.) Hi-Temp. Cable
BRmt. w/ (25 ft.) 1st 10ft Hi-Temp. Cbl.
CRmt. w/ (35 ft.) 1st 10ft Hi-Temp. Cbl.
DRmt. w/ (50 ft.) 1st 10ft Hi-Temp. Cbl.
ERmt. w/ (75 ft.) 1st 10ft Hi-Temp. Cbl.
FRmt. w/ (5 ft.) G.P. Cable
GRmt. w/ (5 ft.) Tri-Ax Cable
HRmt. w/ (10 ft.) Tri-Ax Cable
JRmt. w/ (35 ft.) Tri-Ax Cable
KRmt. w/ (5 ft.) Hi-Temp. Cable
TP 0
NPT Threads
A1B ¾"NPT 316SS
A1C ¾"NPT Hastelloy C
A1P ¾"NPT PFA
A2B 1"NPT 316SS
A2C 1"NPT Hastelloy C
Sanitary TriClamps
C2B 1"TriClamp 316SS
C3B 1½"TriClamp 316SS
C4B 2"TriClamp 316SS
C5B 2-1/2" TriClamp 316SS
C6B 3” TriClamp 316SS
C7B 4" TriClamp 316SS
ANSI Flanges
DA1 1" 150# RF 316/316L SS
DB1 1½" 150# RF 316/316L SS
DC1 2" 150# RF 316/316L SS
DD1 2½" 150# RF 316/316L SS
DE1 1" 300# RF 316/316L SS
DF1 1½" 300# RF 316/316L SS
DG1 2" 300# RF 316/316L SS
DH1 2½" 300# RF 316/316L SS
DI1 3" 150# RF 316/316L SS
DJ1 3" 300# RF 316/316L SS
DK1 4" 150# RF 316/316L SS
DL1 4" 300# RF 316/316L SS
DM1 6" 150# RF 316/316L SS
DN1 6" 300# RF 316/316L SS
DA2 1" 150# RF CS
DB2 1½" 150# RF CS
DC2 2" 150# RF CS
DD2 2½" 150# RF CS
DE2 1" 300# RF CS
DF2 1½" 300# RF CS
DG2 2" 300# RF CS
DH2 2½" 300# RF CS
DI2 3" 150# RF CS
DJ2 3" 300# RF CS
DK2 4" 150# RF CS
DL2 4" 300# RF CS
DM2 6" 150# RF CS
DN2 6" 300# RF CS
DIN Flanges
E01 25 mm 16 bar RF 316/316L SS
EP1 25 mm 40 bar RF 316/316L SS
EQ1 50 mm 16 bar RF 316/316L SS
ER1 50 mm 40 bar RF 316/316L SS
ES1 80 mm 16 bar RF 316/316L SS
ET1 80 mm 40 bar RF 316/316L SS
EU1 100 mm 16 bar RF 316/316L SS
EV1 100 mm 40 bar RF 316/316L SS
EW1 150 mm 16 bar RF 316/316L SS
EX1 150 mm 40 bar RF 316/316L SS
E02 25 mm 16 bar RF CS
EP2 25 mm 40 bar RF CS
EQ2 50 mm 16 bar RF CS
ER2 50 mm 40 bar RF CS
ES2 80 mm 16 bar RF CS
ET2 80 mm 40 bar RF CS
EU2 100 mm 16 bar RF CS
EV2 100 mm 40 bar RF CS
EW2 150 mm 16 bar RF CS
EX2 150 mm 40 bar RF CS
NPT Threads
A1B ¾"NPT 316SS
A1C ¾"NPT Hastelloy C
A1P ¾"NPT PFA
A2B 1"NPT 316SS
A2C 1"NPT Hastelloy C
Sanitary TriClamps
C2B 1"TriClamp 316SS
C3B 1½"TriClamp 316SS
C4B 2"TriClamp 316SS
C5B 2-1/2" TriClamp 316SS
C6B 3” TriClamp 316SS
C7B 4" TriClamp 316SS
ANSI Flanges
DA1 1" 150# RF 316/316L SS
DB1 1½" 150# RF 316/316L SS
DC1 2" 150# RF 316/316L SS
DD1 2½" 150# RF 316/316L SS
DE1 1" 300# RF 316/316L SS
DF1 1½" 300# RF 316/316L SS
DG1 2" 300# RF 316/316L SS
DH1 2½" 300# RF 316/316L SS
DI1 3" 150# RF 316/316L SS
DJ1 3" 300# RF 316/316L SS
DK1 4" 150# RF 316/316L SS
DL1 4" 300# RF 316/316L SS
DM1 6" 150# RF 316/316L SS
DN1 6" 300# RF 316/316L SS
DA2 1" 150# RF CS
DB2 1½" 150# RF CS
DC2 2" 150# RF CS
DD2 2½" 150# RF CS
DE2 1" 300# RF CS
DF2 1½" 300# RF CS
DG2 2" 300# RF CS
DH2 2½" 300# RF CS
DI2 3" 150# RF CS
DJ2 3" 300# RF CS
DK2 4" 150# RF CS
DL2 4" 300# RF CS
DM2 6" 150# RF CS
DN2 6" 300# RF CS
DIN Flanges
E01 25 mm 16 bar RF 316/316L SS
EP1 25 mm 40 bar RF 316/316L SS
EQ1 50 mm 16 bar RF 316/316L SS
ER1 50 mm 40 bar RF 316/316L SS
ES1 80 mm 16 bar RF 316/316L SS
ET1 80 mm 40 bar RF 316/316L SS
EU1 100 mm 16 bar RF 316/316L SS
EV1 100 mm 40 bar RF 316/316L SS
EW1 150 mm 16 bar RF 316/316L SS
EX1 150 mm 40 bar RF 316/316L SS
E02 25 mm 16 bar RF CS
EP2 25 mm 40 bar RF CS
EQ2 50 mm 16 bar RF CS
ER2 50 mm 40 bar RF CS
ES2 80 mm 16 bar RF CS
ET2 80 mm 40 bar RF CS
EU2 100 mm 16 bar RF CS
EV2 100 mm 40 bar RF CS
EW2 150 mm 16 bar RF CS
EX2 150 mm 40 bar RF CS
(1) Available with remote electronics only
(2) Use A1P mounting option
(3) Choose only sanitary mounting options
(4) Available with 0-inch CSL only
(5) Use P00X mounting option
(6) Use A1B mounting option
(7) Use A8B mounting option (¼-inch NPT)
(8) Choose from flange mounting only
(9) FM approved with remote electronics only
Not all mounting options available with all
sensing elements
Notes: CSL (Cote-Shield Length) should extend through Nozzle + Typical "Wall Buildup" + 2 Inches
0 No Approvals(Remote), NEMA 4X/IP66, M20 X 1.5 conduit entries
1 No Approvals, NEMA 4X/IP66, ¾” conduit entries
2 ATEX / IECEx, NEMA 4X/IP66, M20 X 1.5 conduit entries
3 FM / FMc approved, NEMA 4X/IP66, ¾” conduit entries
5 No Approvals, NEMA 4X/IP66, M20 conduit entries, Dual Seal, Perm-a-Seal Sensors – only
6 FM / FMc approved (Integral), No Approvals (Remote), NEMA 4X/IP66, ¾” conduit entries, Dual Seal, Perm-a-Seal Sensors – only
7 FM / FMc approved (Remote), NEMA 4X/IP66, ¾” conduit entries, Dual Seal, Perm-a-Seal Sensors – only
8 No Approvals (Integral), NEMA 4X/IP66, ¾” conduit entries, Dual Seal, Perm-a-Seal Sensors – only
9 FM / FMc approved (Integral), No Approvals (Remote), NEMA 4X/IP66, M20 conduit entries, Dual Seal, Perm-a-Seal Sensors – only
A No Approvals (Remote), NEMA 4X/IP66, ¾” conduit entries, Dual Seal,Perm-a-Seal Sensors – only
B FM / FMc approved (Remote), NEMA 4X/IP66, ¾” conduit entries, Dual Seal, Perm-a-Seal Sensors – only
0No Approvals, NEMA 4X/IP66, M20 X 1.5 conduit entries
1No Approvals, NEMA 4X/IP66, ¾” NPT conduit entries
2ATEX / IECEx, NEMA 4X/IP66, M20 X 1.5 conduit entries
3FM / FMc, NEMA 4X/IP66, ¾” NPT conduit entries
5No Approvals, NEMA 4X/IP66, M20 conduit entries, Dual Seal, Perm-a-Seal sensors – only
6No approvals, NEMA 4X/IP66, ¾” NPT conduit entries, Dual Seal, Perm-a-Seal sensors – only
7FM / FMc Approved, NEMA 4X/IP66, ¾” NPT conduit entries, Dual Seal, Perm-a-Seal sensors – only
9No approvals, NEMA 4X/IP66, M20 conduit entries, Dual Seal, Non Perm-a-Seal sensors – only
ANo Approvals, NEMA 4X/IP66, ¾” NPT conduit entries, Dual Seal, Non Perm-a-Seal sensors – only
BFM / FMc Approved, NEMA 4X/IP66, ¾” NPT conduit entries, Dual Seal, Non Perm-a-Seal sensors – only
Measurement Type
N Std Auto Cal
LStd 2 pF Fixed
T10 pF Auto Cal
V10 pF Fixed
HHi Sense .5 pF Auto Cal
PHi Sense .5 pF Fixed
GHi Sense Manual
MStd Sense Manual
1.3 Model Number
Continued on Next Page
All Calibration modes are built into the standard unit.
Modes can be changed in the eld as required
(See Section 2.9.9)

Introduction
3
1.3 Model Number (continued)
Continued from Previous Page
Sensing Element
Application Sensing Element Pressure/Temperature Wetted Parts
00 General purpose 700-1202-001 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and PEEK
700-1202-021 integral
01 Floating roof with 700-1202-012 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS, Brass,
cable attachment 700-1202-022 integral and PEEK
and brass bottom weight
02 General purpose, 700-1202-014 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and PEEK
longer insertion lengths 700-1202-024 integral
with cable attachment
and 316SS bottom weight
03 Proximity 700-1202-018 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and PEEK
700-1202-028 integral with 76 mm (3)
316SS proximity plate
04 General purpose, 700-1202-041 remote 69 bar @ 121°C (1000 PSI @ 250°F) 316SS and PEEK
high temperature 700-1202-042 integral 20.7 bar @ 232°C (300 PSI @ 450°F)
and pressure
06 General purpose with 700-1202-031 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and FDA grade
FDA approved 700-1202-032 integral PEEK
materials of construction
07 General purpose 700-1202-010 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and PEEK with
Granular materials 700-1202-020 integral 7/8 inch dia. 316SS collar
09 General purpose 700-1202-033 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and FDA grade
Granular materials with 700-1202-034 integral PEEK with 7/8 inch dia.
FDA approved 316SS collar
10 Corrosive liquids (2)(4)(9) 700-0001-018 remote 3.4 bar @ 149°C (50 PSI @ 300°F) PFA
11 General purpose, 700-0201-005 int/rem 69 bar @ 38°C (1000 PSI @ 100°F) 316SS and TFE
TFE compatibility required 34.5 bar @ 149°C (500psi @ 300°F)
12 Corrosive material, 700-0201-005 int/rem 69 bar @ 38°C (1000 PSI @ 100°F) Hastelloy C and TFE
higher pressure Hastelloy C 34.5 bar @ 149°C (500psi @ 300°F)
13 Sanitary (3) Non 3A 700-0201-019 int/rem 13.8 bar @ 149°C (200 PSI @ 300°F) 316/316L SS and TFE
14 General Purpose, LP 700-0202-002 int/rem 3.4 bar @ 149°C (50 PSI @ 300°F) 316SS and TFE
15 Heavy duty, agitated 700-0202-043 remote 69 bar @ 38°C (1000 PSI @ 100°F) 316SS and TFE
tanks or material 34.5 bar @ 149°C (500psi @ 300°F)
with high bulk density (1)
16 High Integrity Seal for 700-0002-360 int/rem 34.5 bar @ 149°C (500 PSI @ 300°F) PFA
Hazardous Materials
17 Sanitary (3) Non 3A LP 700-0202-029 int/rem 3.4 bar @ 149°C (50 PSI @ 300°F) 316SS and TFE
18 Corrosive material, 700-0001-022 int/rem 69 bar @ 38°C (1000 PSI @ 100°F) TFE
higher pressure with 34.5 bar @ 149°C (500 PSI @ 300°F)
waterlike viscosity (4)
19 Interface Measurement 700-0002-023 int/rem 69 bar @ 38°C (1000 PSI @ 100°F) 316SS and TFE
34.5 bar @ 149°C (500 PSI @ 300°F)
20 Miniature Pilot 700-0209-002 remote 6.9 bar @ 121°C (100 PSI @ 250°F) 316 SS and TFE
Plant Sensor (1)(7) 0 bar @ 232°C (0 PSI @ 450°F)
Fly Ash Precipitators, Baghouse, and Economizers (1) (6)
31 No hopper Installation 700-0029-001 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
32 Hopper Installation 700-0029-002 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
up to 200mm (8 inches)
33 Hopper Installation 700-0029-003 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
up to 406mm (16 inches)
34 Hopper Instalation 700-0029-004 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
up to 521mm (20.5 inches)
35 Hopper Installation 700-0029-005 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
up to 635mm (25 inches)
Plugged Chute Detection (1) (5)
50 Flush Mount Sensor 700-0207-001 remote 0.1 bar @ 82°C (1 PSI @ 180°F) 304 SS and
305mm2(12 inches2) Polyurethane
heavy duty
51 Flush Mount Sensor 700-0207-002 remote 0.1 bar @ 149°C (1 PSI @ 300°F) 304 SS and TFE
305mm2(12 inches2)
higher temperature
52 Flush Mount Sensor 700-0207-003 remote 0.1 bar @ 82°C (1 PSI @ 180°F) 304 SS and Neoprene
305mm2(12 inches2)
with curved radius 153, 229, 305 mm (6, 9, or 12 inches)
53 Flush Mount Sensor 700-0207-004 remote 0.1 bar @ 82°C (1 PSI @ 180°F) 410 SS and UHMW
305mm2(12 inches2) Polyethylene
extra heavy duty
55 Flush Mount Sensor 700-0207-006 remote 0.1 bar @ 82°C (1 PSI @ 180°F) 304 SS and
203mm2 (8 inches2) Polyurethane
heavy duty
67 3A Sanitary Sensor 700-3201-001 remote 13.8 bar @ 121°C (200 psi @ 250°F) 316 SS and PEEK
700-3201-002 integral
High Pressure / High Temperature
60 High Pressure & Temp. 700-0204-038 remote 137.9 bar @ 93°C (2000 PSI @ 200°F) 316SS and Ceramic
68.9 bar @ 260°C (1000 PSI @ 500°F)
61 High Temperature (1) 700-0204-002 remote 0 bar @ 816°C (0 PSI @ 1500°F) 316SS and Ceramic
62 High Pressure & Temp. 700-0204-048 remote 275.8 bar @316°C (4000 PSI @ 600°F) 316SS
ZZ Sensing Element Not Listed
Output
1One DPDT Relay, dry contacts, 5A, 120VAC (Min 100 mA / 12 VDC)
2One DPDT Relay, gold plated contacts (Max 200 mA / 12 VDC)
Housing
Technology
PRF Admittance
Input
LUniversal Power Supply 19-250 VAC, 18-200 VDC
Measurement Type
N Std Auto Cal
LStd 2 pF Fixed
T10 pF Auto Cal
V10 pF Fixed
HHi Sense .5 pF Auto Cal
PHi Sense .5 pF Fixed
GHi Sense Manual
MStd Sense Manual
Electronics
0Integral
1Remote, no cable
2Rmt. w/ 3 m (10 ft.) G.P. cable
3Rmt. w/ 7.6 m (25 ft.) G.P. cable
4Rmt. w/ 10.6 m (35 ft.) G.P. cable
5Rmt. w/ 15.2 m (50 ft.) G.P. cable
6Rmt. w/ 23 m (75 ft.) G.P. cable
IL CSL
xxxG 457 mm (18") 0 mm (0")
xxxH 914 mm (36") 254 mm (10")
xxxJ 914 mm (36") 0 mm (0")
xxxK 1219 mm (48") 254 mm (10")
xxxL 1524 mm (60") 254 mm (10")
P00X IL/CSL Other
A1BX IL/CSL factory set for Fly Ash
xxxZ Other
IL CSL
xxx1 457 mm (18") 152 mm (6")
xxx2 305 mm (12") 152 mm (6")
xxxA 152 mm (6") 51 mm (2")
xxxB 305 mm (12") 51 mm (2")
xxxC 305 mm (12") 89 mm (3.5")
xxxD 457 mm (18") 51 mm (2")
xxxE 457 mm (18") 89 mm (3.5")
xxxF 457 mm (18") 254 mm (10")
Mounting Type (See separate Mounting Chart for first three digits)
(1) Available with remote electronics only
(2) Use A1P mounting option
(3) Choose only sanitary mounting options
(4) Available with 0-inch CSL only
(5) Use P00X mounting option
(6) Use A1B mounting option
(7) Use A8B mounting option (¼-inch NPT)
(8) Choose from flange mounting only
(9) FM approved with remote electronics only
Not all mounting options available with all
sensing elements
7Rmt. w/ (25 ft.) Tri-Ax Cable
8Rmt. w/ (50 ft.) Tri-Ax Cable
9Rmt. w/ (75 ft.) Tri-Ax Cable
ARmt. w/ (10 ft.) Hi-Temp. Cable
BRmt. w/ (25 ft.) 1st 10ft Hi-Temp. Cbl.
CRmt. w/ (35 ft.) 1st 10ft Hi-Temp. Cbl.
DRmt. w/ (50 ft.) 1st 10ft Hi-Temp. Cbl.
ERmt. w/ (75 ft.) 1st 10ft Hi-Temp. Cbl.
FRmt. w/ (5 ft.) G.P. Cable
GRmt. w/ (5 ft.) Tri-Ax Cable
HRmt. w/ (10 ft.) Tri-Ax Cable
JRmt. w/ (35 ft.) Tri-Ax Cable
KRmt. w/ (5 ft.) Hi-Temp. Cable
Notes: CSL (Cote-Shield Length) should extend through Nozzle + Typical "Wall Buildup" + 2 Inches
Sensing Element
Application Sensing Element Pressure/Temperature Wetted Parts
00 General purpose 700-1202-001 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and PEEK
700-1202-021 integral
01 Floating roof with 700-1202-012 remote 13.8 bar @ 177°C (200 PSI @ 350°F) 316SS, Brass,
cable attachment 700-1202-022 integral and PEEK
and brass bottom weight
02 General purpose, 700-1202-014 remote 13.8 bar @ 177°C (200 PSI @ 350°F) 316SS and PEEK
longer insertion lengths 700-1202-024 integral
with cable attachment
and 316SS bottom weight
03 Proximity 700-1202-018 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and PEEK
700-1202-028 integral with 76 mm (3)
316SS proximity plate
04 General purpose, 700-1202-041 remote 69 bar @ 121°C (1000 PSI @ 250°F) 316SS and PEEK
high temperature 700-1202-042 integral 20.7 bar @ 232°C (300 PSI @ 450°F)
and pressure
06 General purpose with 700-1202-031 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and FDA grade
FDA approved 700-1202-032 integral PEEK
materials of construction
07 General purpose 700-1202-010 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and PEEK with
Granular materials 700-1202-020 integral 7/8 inch dia. 316SS collar
09 General purpose 700-1202-033 remote 13.8 bar @ 232°C (200 PSI @ 450°F) 316SS and FDA grade
Granular materials with 700-1202-034 integral PEEK with 7/8 inch dia.
FDA approved 316SS collar
materials of construction
10 Corrosive liquids (2)(4)(9) 700-0001-018 remote 3.4 bar @ 149°C (50 PSI @ 300°F) PFA
11 General purpose, 700-0201-005 int/rem 69 bar @ 38°C (1000 PSI @ 100°F) 316SS and TFE
higher pressure 13.8 bar @ 232°C (200 PSI @ 450°F)
TFE compatibility required
12 Corrosive material, 700-0201-005 int/rem 69 bar @ 38°C (1000 PSI @ 100°F) Hastelloy C and TFE
higher pressure Hastelloy C 13.8 bar @ 232°C (200 PSI @ 450°F)
13 Sanitary (3) Non 3A 700-0201-019 int/rem 13.8 bar @ 149°C (200 PSI @ 300°F) 316/316L SS and TFE
14 General Purpose, 700-0202-002 int/rem 3.4 bar @ 149°C (50 PSI @ 300°F) 316SS and TFE
low pressure 1.4 bar @ 232°C (20 PSI @ 450°F)
15 Heavy duty, agitated 700-0202-043 remote 69 bar @ 38°C (1000 PSI @ 100°F) 316SS and TFE
tanks or material 13.8 bar @ 232°C (200 PSI @ 450°F)
with high bulk density (1)
16 High Integrity Seal for 700-0002-360 int/rem 34.5 bar @ 149°C (500 PSI @ 300°F) PFA
Hazardous Materials
17 Sanitary (3) Non 3A LP 700-0202-029 int/rem 3.4 bar @ 149°C (50 PSI @ 300°F) 316SS and TFE
18 Corrosive material, 700-0001-022 int/rem 69 bar @ 38°C (1000 PSI @ 100°F) TFE
higher pressure with 34.5 bar @ 149°C (500 PSI @ 300°F)
waterlike viscosity (4)
19 Interface Measurement 700-0002-023 int/rem 69 bar @ 38°C (1000 PSI @ 100°F) 316SS and TFE
34.5 bar @ 149°C (500 PSI @ 300°F)
20 Miniature Pilot 700-0209-002 remote 6.9 bar @ 121°C (100 PSI @ 250°F) 316 SS and TFE
Plant Sensor (1)(7) 0 bar @ 232°C (0 PSI @ 450°F)
Fly Ash Precipitators, Baghouse, and Economizers (1) (6)
31 No hopper Installation 700-0029-001 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
32 Hopper Installation 700-0029-002 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
up to 200mm (8 inches)
33 Hopper Installation 700-0029-003 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
up to 406mm (16 inches)
34 Hopper Instalation 700-0029-004 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
up to 521mm (20.5 inches)
35 Hopper Installation 700-0029-005 remote 0.1 bar @ 260°C (2 PSI @ 500°F) 316SS and TFE
up to 635mm (25 inches)
Plugged Chute Detection (1) (5)
50 Flush Mount Sensor 700-0207-001 remote 0.1 bar @ 82°C (1 PSI @ 180°F) 304 SS and
305mm2(12 inches2) Polyurethane
heavy duty
51 Flush Mount Sensor 700-0207-002 remote 0.1 bar @ 149°C (1 PSI @ 300°F) 304 SS and TFE
305mm2(12 inches2)
higher temperature
52 Flush Mount Sensor 700-0207-003 remote 0.1 bar @ 82°C (1 PSI @ 180°F) 304 SS and Neoprene
305mm2(12 inches2)
with curved radius 153, 229, 305 mm (6, 9, or 12 inches)
53 Flush Mount Sensor 700-0207-004 remote 0.1 bar @ 82°C (1 PSI @ 180°F) 410 SS and UHMW
305mm2(12 inches2) Polyethylene
extra heavy duty
55 Flush Mount Sensor 700-0207-006 remote 0.1 bar @ 82°C (1 PSI @ 180°F) 304 SS and
203mm2 (8 inches2) Polyurethane
heavy duty
67 3A Sanitary Sensor 700-3201-001 remote 13.8 bar @ 121°C (200 psi @ 250°F) 316 SS and PEEK
700-3201-002 integral
High Pressure / High Temperature
60 High Pressure & Temp. 700-0204-038 remote 137.9 bar @ 93°C (2000 PSI @ 200°F) 316SS and Ceramic
68.9 bar @ 260°C (1000 PSI @ 500°F)
61 High Temperature (1) 700-0204-002 remote 0 bar @ 816°C (0 PSI @ 1500°F) 316SS and Ceramic
62 High Pressure & Temp. 700-0204-048 remote 275.8 bar @316°C (4000 PSI @ 600°F) 316SS
ZZ Sensing Element Not Listed
Output
08-16 mA
Housing
Technology
PRF Admittance
Input
TTwo Wire Power Supply 13 to 30 Vdc
Electronics
0Integral
1Remote, no cable
2Rmt. w/ 3 m (10 ft.) G.P. cable
3Rmt. w/ 7.6 m (25 ft.) G.P. cable
4Rmt. w/ 10.6 m (35 ft.) G.P. cable
5Rmt. w/ 15.2 m (50 ft.) G.P. cable
6Rmt. w/ 23 m (75 ft.) G.P. cable
IL CSL
xxxG 457 mm (18") 0 mm (0")
xxxH 914 mm (36") 254 mm (10")
xxxJ 914 mm (36") 0 mm (0")
xxxK 1219 mm (48") 254 mm (10")
xxxL 1524 mm (60") 254 mm (10")
P00X IL/CSL Other
A1BX IL/CSL factory set for Fly Ash
xxxZ Other
IL CSL
xxx1 457 mm (18") 152 mm (6")
xxx2 305 mm (12") 152 mm (6")
xxxA 152 mm (6") 51 mm (2")
xxxB 305 mm (12") 51 mm (2")
xxxC 305 mm (12") 89 mm (3.5")
xxxD 457 mm (18") 51 mm (2")
xxxE 457 mm (18") 89 mm (3.5")
xxxF 457 mm (18") 254 mm (10")
Mounting Type (See separate Mounting Chart for first three digits)
7Rmt. w/ (25 ft.) Tri-Ax Cable
8Rmt. w/ (50 ft.) Tri-Ax Cable
9Rmt. w/ (75 ft.) Tri-Ax Cable
ARmt. w/ (10 ft.) Hi-Temp. Cable
BRmt. w/ (25 ft.) 1st 10ft Hi-Temp. Cbl.
CRmt. w/ (35 ft.) 1st 10ft Hi-Temp. Cbl.
DRmt. w/ (50 ft.) 1st 10ft Hi-Temp. Cbl.
ERmt. w/ (75 ft.) 1st 10ft Hi-Temp. Cbl.
FRmt. w/ (5 ft.) G.P. Cable
GRmt. w/ (5 ft.) Tri-Ax Cable
HRmt. w/ (10 ft.) Tri-Ax Cable
JRmt. w/ (35 ft.) Tri-Ax Cable
KRmt. w/ (5 ft.) Hi-Temp. Cable
TP 0
NPT Threads
A1B ¾"NPT 316SS
A1C ¾"NPT Hastelloy C
A1P ¾"NPT PFA
A2B 1"NPT 316SS
A2C 1"NPT Hastelloy C
Sanitary TriClamps
C2B 1"TriClamp 316SS
C3B 1½"TriClamp 316SS
C4B 2"TriClamp 316SS
C5B 2-1/2" TriClamp 316SS
C6B 3” TriClamp 316SS
C7B 4" TriClamp 316SS
ANSI Flanges
DA1 1" 150# RF 316/316L SS
DB1 1½" 150# RF 316/316L SS
DC1 2" 150# RF 316/316L SS
DD1 2½" 150# RF 316/316L SS
DE1 1" 300# RF 316/316L SS
DF1 1½" 300# RF 316/316L SS
DG1 2" 300# RF 316/316L SS
DH1 2½" 300# RF 316/316L SS
DI1 3" 150# RF 316/316L SS
DJ1 3" 300# RF 316/316L SS
DK1 4" 150# RF 316/316L SS
DL1 4" 300# RF 316/316L SS
DM1 6" 150# RF 316/316L SS
DN1 6" 300# RF 316/316L SS
DA2 1" 150# RF CS
DB2 1½" 150# RF CS
DC2 2" 150# RF CS
DD2 2½" 150# RF CS
DE2 1" 300# RF CS
DF2 1½" 300# RF CS
DG2 2" 300# RF CS
DH2 2½" 300# RF CS
DI2 3" 150# RF CS
DJ2 3" 300# RF CS
DK2 4" 150# RF CS
DL2 4" 300# RF CS
DM2 6" 150# RF CS
DN2 6" 300# RF CS
DIN Flanges
E01 25 mm 16 bar RF 316/316L SS
EP1 25 mm 40 bar RF 316/316L SS
EQ1 50 mm 16 bar RF 316/316L SS
ER1 50 mm 40 bar RF 316/316L SS
ES1 80 mm 16 bar RF 316/316L SS
ET1 80 mm 40 bar RF 316/316L SS
EU1 100 mm 16 bar RF 316/316L SS
EV1 100 mm 40 bar RF 316/316L SS
EW1 150 mm 16 bar RF 316/316L SS
EX1 150 mm 40 bar RF 316/316L SS
E02 25 mm 16 bar RF CS
EP2 25 mm 40 bar RF CS
EQ2 50 mm 16 bar RF CS
ER2 50 mm 40 bar RF CS
ES2 80 mm 16 bar RF CS
ET2 80 mm 40 bar RF CS
EU2 100 mm 16 bar RF CS
EV2 100 mm 40 bar RF CS
EW2 150 mm 16 bar RF CS
EX2 150 mm 40 bar RF CS
NPT Threads
A1B ¾"NPT 316SS
A1C ¾"NPT Hastelloy C
A1P ¾"NPT PFA
A2B 1"NPT 316SS
A2C 1"NPT Hastelloy C
Sanitary TriClamps
C2B 1"TriClamp 316SS
C3B 1½"TriClamp 316SS
C4B 2"TriClamp 316SS
C5B 2-1/2" TriClamp 316SS
C6B 3” TriClamp 316SS
C7B 4" TriClamp 316SS
ANSI Flanges
DA1 1" 150# RF 316/316L SS
DB1 1½" 150# RF 316/316L SS
DC1 2" 150# RF 316/316L SS
DD1 2½" 150# RF 316/316L SS
DE1 1" 300# RF 316/316L SS
DF1 1½" 300# RF 316/316L SS
DG1 2" 300# RF 316/316L SS
DH1 2½" 300# RF 316/316L SS
DI1 3" 150# RF 316/316L SS
DJ1 3" 300# RF 316/316L SS
DK1 4" 150# RF 316/316L SS
DL1 4" 300# RF 316/316L SS
DM1 6" 150# RF 316/316L SS
DN1 6" 300# RF 316/316L SS
DA2 1" 150# RF CS
DB2 1½" 150# RF CS
DC2 2" 150# RF CS
DD2 2½" 150# RF CS
DE2 1" 300# RF CS
DF2 1½" 300# RF CS
DG2 2" 300# RF CS
DH2 2½" 300# RF CS
DI2 3" 150# RF CS
DJ2 3" 300# RF CS
DK2 4" 150# RF CS
DL2 4" 300# RF CS
DM2 6" 150# RF CS
DN2 6" 300# RF CS
DIN Flanges
E01 25 mm 16 bar RF 316/316L SS
EP1 25 mm 40 bar RF 316/316L SS
EQ1 50 mm 16 bar RF 316/316L SS
ER1 50 mm 40 bar RF 316/316L SS
ES1 80 mm 16 bar RF 316/316L SS
ET1 80 mm 40 bar RF 316/316L SS
EU1 100 mm 16 bar RF 316/316L SS
EV1 100 mm 40 bar RF 316/316L SS
EW1 150 mm 16 bar RF 316/316L SS
EX1 150 mm 40 bar RF 316/316L SS
E02 25 mm 16 bar RF CS
EP2 25 mm 40 bar RF CS
EQ2 50 mm 16 bar RF CS
ER2 50 mm 40 bar RF CS
ES2 80 mm 16 bar RF CS
ET2 80 mm 40 bar RF CS
EU2 100 mm 16 bar RF CS
EV2 100 mm 40 bar RF CS
EW2 150 mm 16 bar RF CS
EX2 150 mm 40 bar RF CS
(1) Available with remote electronics only
(2) Use A1P mounting option
(3) Choose only sanitary mounting options
(4) Available with 0-inch CSL only
(5) Use P00X mounting option
(6) Use A1B mounting option
(7) Use A8B mounting option (¼-inch NPT)
(8) Choose from flange mounting only
(9) FM approved with remote electronics only
Not all mounting options available with all
sensing elements
Notes: CSL (Cote-Shield Length) should extend through Nozzle + Typical "Wall Buildup" + 2 Inches
0 No Approvals(Remote), NEMA 4X/IP66, M20 X 1.5 conduit entries
1 No Approvals, NEMA 4X/IP66, ¾” conduit entries
2 ATEX / IECEx, NEMA 4X/IP66, M20 X 1.5 conduit entries
3 FM / FMc approved, NEMA 4X/IP66, ¾” conduit entries
5 No Approvals, NEMA 4X/IP66, M20 conduit entries, Dual Seal, Perm-a-Seal Sensors – only
6 FM / FMc approved (Integral), No Approvals (Remote), NEMA 4X/IP66, ¾” conduit entries, Dual Seal, Perm-a-Seal Sensors – only
7 FM / FMc approved (Remote), NEMA 4X/IP66, ¾” conduit entries, Dual Seal, Perm-a-Seal Sensors – only
8 No Approvals (Integral), NEMA 4X/IP66, ¾” conduit entries, Dual Seal, Perm-a-Seal Sensors – only
9 FM / FMc approved (Integral), No Approvals (Remote), NEMA 4X/IP66, M20 conduit entries, Dual Seal, Perm-a-Seal Sensors – only
A No Approvals (Remote), NEMA 4X/IP66, ¾” conduit entries, Dual Seal,Perm-a-Seal Sensors – only
B FM / FMc approved (Remote), NEMA 4X/IP66, ¾” conduit entries, Dual Seal, Perm-a-Seal Sensors – only
0No Approvals, NEMA 4X/IP66, M20 X 1.5 conduit entries
1No Approvals, NEMA 4X/IP66, ¾” NPT conduit entries
2ATEX / IECEx, NEMA 4X/IP66, M20 X 1.5 conduit entries
3FM / FMc, NEMA 4X/IP66, ¾” NPT conduit entries
5No Approvals, NEMA 4X/IP66, M20 conduit entries, Dual Seal, Perm-a-Seal sensors – only
6No approvals, NEMA 4X/IP66, ¾” NPT conduit entries, Dual Seal, Perm-a-Seal sensors – only
7FM / FMc Approved, NEMA 4X/IP66, ¾” NPT conduit entries, Dual Seal, Perm-a-Seal sensors – only
9No approvals, NEMA 4X/IP66, M20 conduit entries, Dual Seal, Non Perm-a-Seal sensors – only
ANo Approvals, NEMA 4X/IP66, ¾” NPT conduit entries, Dual Seal, Non Perm-a-Seal sensors – only
BFM / FMc Approved, NEMA 4X/IP66, ¾” NPT conduit entries, Dual Seal, Non Perm-a-Seal sensors – only
Measurement Type
N Std Auto Cal
LStd 2 pF Fixed
T10 pF Auto Cal
V10 pF Fixed
HHi Sense .5 pF Auto Cal
PHi Sense .5 pF Fixed
GHi Sense Manual
MStd Sense Manual

ThePoint Series
4
1.4 Housing Dimensions
Figure 1-3
Compartment Housing Detail
Equipotential Terminal
(CENELEC Systems)
4.5"
(114mm)
6.5"
(165mm)
4.75"
(121mm)

Installation
5
Section 2: Installation
2.1 Unpacking
Carefully remove the contents of the shipping carton and check
each item against the packing list before destroying any packing
material. If there is any shortage or damage, immediately
report it to the factory at 1+ 215-674-1234.
2.2 Mounting and Installation Guidelines
CAUTION:
ThePoint instrument must not be powered before it is installed
in the application with material below the sensing element.
ThePoint instrument can be mounted vertically or horizontally
or at an angle. Mounting location should be as free as possible
from vibration, corrosive atmospheres, and any possibility of
mechanical damage. Ambient temperatures at electronics
should be between -30 to 70º C (-22 to 158º F).
NOTE:
To reduce possibility of damage caused by water in conduit,
install drip loop and breather drain in conduit to purge any
accumulating moisture as shown in Figure 2-1.
After system is installed and level is below sensing element,
apply power. ThePoint series instrument does not require
any calibration or setpoint adjustments and is ready to detect
change in level.
If properly installed, the green LED will
light when power is applied. Neither the
green nor red LED should be ashing.
If either of the LEDs are ashing, refer
to, Section 4, Troubleshooting.
Cable ttings supplied are
weather-resistant. They are NOT certied
as explosion proof (XP) or ameproof (d)
unless they are specically marked.
Figure 2-1
Recommended Conduit Connection

ThePoint Series
6
• When installing ThePoint instrument, ambient temperature
at electronics must not exceed 70°C (158°F).
• When installing ange-mounted sensing elements, keep
mating surfaces and bolts free of paint and corrosion to
ensure proper electrical contact with vessel. Avoid using
excessive amounts of Teon™ tape when installing threaded
sensing elements.
• Install systems with threaded NPT connection via wrench
ats on the process connection ONLY.
• Locate sensing element to avoid enhancing electrostatic
discharge from process medium, as is good practice with
any thermowell, displacer, or sampler. This includes correct
bonding to tank or silo wall.
• If installation area is rated explosion proof and requires
conduit seal ttings, they should be used in accordance with
company standards and local codes.
2.2 Mounting and Installation Guidelines (continued)
WARNING:
ThePoint equipment is rated explosion proof. When installing
in explosion hazardous areas [rated “potentially hazardous”
(EU) or “hazardous classied” (USA)] observe all national and
local regulations as well as specications in the certicate.
Mount sensing element using the following installation
guidelines. Refer to Figure 2-2.
NOZZLE
NOZZLE
Wall build-up
does not extend
past first
insulator.
Cote-shield must
extend through
nozzle and wall
build-up by 2".
Wrong
Nozzle too long;
Cote-shield too short.
Factory-supplied Cote-shield
extends through nozzle and
wall build-up.
Best
Best
No Nozzle
Good
Long Nozzle
Figure 2-2
Installation Considerations

Installation
7
2.2 Mounting and Installation Guidelines (continued)
• Do not mount a Cote-Shield sensing element through a
nozzle that exceeds length of rst insulator.
• Ensure that there are no obstructions or agitator blades to
interfere with sensing element.
• Rigid sensing elements can be mounted at any angle.
2.3 Installation of Flush-Mounted Sensing Elements
These instructions apply to all ush on/off sensing elements,
models 700-0207-001, 700-0207-002, 700-0207-003, 700-0207-
004, 700-0207-006. These systems will sense presence of
material (no ow or plugged chute) and absence of material
(ow or empty chute) at the sensing element. The Flush Sensing
Element will ignore free falling material.
Material Backed-Up Above
Sensing Element
(No Flow)
Sensing Element at the Top of a Chute.
• The ush sensing element should be mounted In
The Flow Stream.These sensing elements are
designed and built to withstand the impact of coal,
rock, wood, chips, etc. This location is important
to prevent excessive build up of material on the
face of the sensing element.
• Excessive build up, typically consisting of wet and/
or sticky nes, can occur if the sensing element is
protected from falling material.
Sensing Element in an angle chute.
• Do not mount on the top or bottom.
• Best mounted on either side
Sensing Element at the Bottom
• Mount on any side.
• Low-Level sensors can be used to detect
a plug or to insure that a seal is present
(chute is full at this point).

ThePoint Series
8
2.4 Input Wiring
WARNING:
If ThePoint instrument is located in a hazardous environment,
do not open enclosure cover or make/break any electrical
connections without rst disconnecting electrical power at
the source. Ensure that wiring, electrical ttings and conduit
connections conform to electrical codes for the specic location
and hazard level.
ThePoint instrument uses a universal power supply and
can be operated from any source between 19 to 250 VAC or
18 to 200 VDC. The universal power supply automatically
detects input voltage regardless of polarity and does not require
jumper changes. See Figure 2-3.
Figure 2-4
Relay Wiring
19 to 250 VAC
18 to 200 VDC
Auto-Detecting Without Jumpers
32
L2L1
1
G
GND
Figure 2-3
Input Wiring
2.5 Output Wiring – Relay Version
ThePoint series instrument is supplied with two sets of contacts
using one 5A DPDT alarm relay. See Figure 2-4.
IMPORTANT
Ground Must be Provided for Proper Operation and Safety.

Installation
9
2.6 Output and LED Status
There are two status LEDs located on top of Electronic Unit.
The green LED is used to indicate that unit has power.
The red LED is used to indicate condition of the relay.
See Figure 2-6.
LED
On
LED
Off
Relay 1
RED
Power
GREEN
4 6 75 8 9
High Level FailSafe
Tank Empty
4 6 75 8 9
High Level FailSafe
Tank Full
4 6 75 8 9
Low Level FailSafe
Tank Full
4 6 75 8 9
Low Level FailSafe
Tank Empty
Tank Condition Relay Status
LED
On
LED
On
Relay 1
RED
Power
GREEN
LED
On
LED
On
Relay 1
RED
Power
GREEN
LED
On
LED
Off
Relay 1
RED
Power
GREEN
Figure 2-5
Output and LED Status
Note: Relays Shown as Powered State

ThePoint Series
10
2.7 Electronic Unit
Remove housing lid to access status LEDs, time delay
adjustment, and conguration jumpers. See Figure 2-6.
2.7.1 Time Delay
adjustment is used to avoid an oscillating relay
output due to agitation or waves in the vessel. The time delay
adjustment can be eld adjusted from 0 to 60 seconds. Unit is
shipped with time delay setting at zero seconds.
The Time Delay adjustment is a 270-Degree turn pot and is at
zero seconds when in the full counter-clockwise position. Do
not force the pot past the stop or damage will occur.
2.7.2 Time Delay Action
describes whether the relay contacts are
delayed from going into the alarm state or recovering from an
alarm state.
• : delays system from coming out of alarm.
• : delays system from going into alarm.
• The instrument is supplied with time delay action set in
forward mode () position.
• Time delay action is eld-selectable using the Time Delay
Jumper located on top of Electronic Unit. See Figure 2-6.
Figure 2-6
Electronic Unit Adjustments
Do not push
the Recal button
without rst ensuring
that the material
being measured is
below the sensing
element.
Time Delay Adjustment - 0-60 Seconds
Failsafe Jumper
Up = High Level
Down = Low Level
Time Delay Jumper
Up = Forward Acting
Down = Reverse Acting
Green LED = Power
Red LED = Alarm
ReCal Button
Manual Calibration
Adjustment Pot
Pin #1

Installation
11
2.7.3 Failsafe
describes the level condition that causes the output
relay to de-energize, and also the state of the relay upon loss
of power.
• High Level Failsafe (). The relay will de-energize when
level is high, indicating high level upon loss of power. (N.O.
contacts open and N.C. contacts closed)
• Low Level Failsafe (). The relay will de-energize when
level is low, indicating low level upon loss of power. (N.O.
contacts open and N.C. contacts closed)
• Instrument is supplied with failsafe jumper set in high
level () position.
• Failsafe is eld-selectable using the Failsafe Jumper located
on top of Electronic Unit. See Figure 2-6.
2.7.4 ReCal Button, Memory Reset
If power has been applied to ThePoint prior to installation (on a
test bench) or, if ThePoint is moved from one vessel to another,
RECAL is necessary. RECAL allows the system's software to
capture the air capacitance generated by the sensing element
in tank.
Merely press and hold the RECAL button (shown in Figure
2-6) for ve (5) seconds. After ve seconds, ThePoint's two
LED’s ash for sixty seconds before the recalibration occurs.
(Removing power from the system while the LED's are ashing
will reset the memory immediately upon next power up).
Do not push the Recal button without rst ensuring
that the material being measured is below the sensing
element.
The system is now ready for installation.
2.8 Spark Protection
Applications involving insulating granulars and insulating
liquids may produce a static discharge that can damage the
electronics. The RF series instrument is supplied with integral
heavy-duty spark protection to prevent static discharges from
damaging the electronic circuits.

ThePoint Series
12
2.9 Sensing Element Connection (Integral Sensing Elements)
Figure 2-7
Sensing Element Connection
(Integral Housing)
Sensing element connects to the rear side of the circuit board
and is factory-installed.
The sensing element is sealed to the housing and cannot be
removed without permanent damage.

Installation
13
2.9 Sensing Element Connection (continued)
For ThePoint instruments mounted remotely from sensing
element, cable connections from sensing element to Electronic
Unit are made to terminals beneath the Electronic Unit. See
Figure 2-8.
Figure 2-8
Sensing Element Connection
(Remote Housing)
GROUND
(GREEN)
COTE-SHIELD
(RED)
CENTER WIRE
(BLUE)
REMOVE
ELECTRONIC
UNIT TO ACCESS
SENSOR HARNESS
(2.5mm Hex-Head Screws)
Cable Fitting
(M20 AdapterOptional)
EQUIPOTENTIAL
TERMINAL
+
SHIELD WIRE MUST BE CLIPPED BY USER
CLIPPED SHIELD WIRE MUST NOT TOUCH CONDULET HOUSING
2 TERMINAL PROBE (TYP)
3 TERMINAL PROBE (TYP)
Ground Wire
(GREEN)
Ground Wire
(GREEN)
Center Wire
(BLUE)
Shield Wire
(CLIPPED)
Center Wire
(BLUE)
Shield Wire
(RED)

ThePoint Series
14
2.10 Calibration
ThePoint™ level measurement switch features both Auto-Cal
and manual calibration. The standard Auto-Calibration mode is
applicable to most liquid and slurry point level measurements.
If preferred, the manual calibration can be used and is
recommended for some application. ThePoint electronic unit
has auto and manual calibration modes built into the standard
unit and can be accessed through a simple routine (see section
2.10.4). The inclusion of these calibration modes allows the
Drexelbrook RF Point Level Products application exibility
that is far greater then any other point level product on the
market. This RF Point Level switch can be used in Liquids,
Solids, Slurries, and Interface applications.
2.10.1 Selecting the Calibration Mode for your application.
The following table is a list of measurement types and the
recommended calibration mode for each of these applications.
ThePoint has eight calibration modes however; only four are
used on the majority of applications.
ThePoint will be shipped in the standard Auto-Cal mode #2
unless pre-ordered in a specic mode. To determine if the
ThePoint has been shipped in a mode other than #2, look at the
label on the inside of the unit housing. The model number will
start with PXL1. The “X” indicates the pre-set mode typically
an “L” for mode #2.
Common Calibration Modes
Mode 2 = L - Fixed Cal 2pF: 2pF differential, set point locked
2pF above starting capacitance
Mode 6 = P - Fixed Cal 0.5pF: 0.5pF differential, set point
locked 0.5pF above starting capacitance
Mode 7 = M - Manual calibration standard sensitivity – pots
adjusts from 0 to 65pF
Mode 8 = G - Manual calibration High sensitivity – pot adjusts
from 0 to 27 pF
Additional calibration modes for specialty applications
(consult factory)
Mode # 1 = N Auto Mode 2pF
Mode # 3 = T Auto Mode 10pF
Mode # 4 = V Auto Mode 10pF
Mode # 5 = H Auto Mode 0.5pF
For explanation of mode See Section 2.10.4
Table of contents