AMK Level 5 Operating instructions

Level 5
Manual
Level 5
Installation
Operation
Functions and options
Troubleshooting
Thank you for buying this product.
Read this manual carefully to get the best performance from this unit.
Please keep this manual carefully.
en

© AMK Solac 11252 DeltaSol_BX.monen.indd
|2
Level 5
Description of symbols
Signal words describe the danger that may occur, when it
is not avoided.
WARNING means that injury, possibly life-threatening
injury, can occur.
ATTENTION means that damage to the appliance can
occur.
Information about the product
Proper usage
The solar controller is designed for use in standard solar
thermal systems and heating systems in compliance with the
technical data specified in this manual.
Improper use excludes all liability claims.
CE-Declaration of conformity
The product complies with the relevant direc-
tives and is therefore labelled with the CE mark.
The Declaration of Conformity is available upon
request, please contact the manufacturer.
Note
Notes are indicated with an information
symbol.
Disposal
Dispose of the packaging in an environmentally sound
manner.
Dispose of old appliances in an environmentally sound
manner. Upon request we will take back your old appliances
bought from us and guarantee an environmentally sound
disposal of the devices.
Subject to technical change. Errors excepted.
ÎArrows indicate instruction steps that should be carried
out.
WARNING! Warnings are indicated with a
warning triangle!
They contain information on how
to avoid the danger described.
Safety advice
Please pay attention to:
- safety advice in order to avoid danger and damage to
people and property.
- the valid local standards, regulations and directives!
Target group
These instructions are exclusively addressed to authorised
skilled personnel.
Only qualified electricians should carry out electrical works.
Initial installation must be effected by qualified personnel
named by the manufacturer.
Note
Strong electromagnetic fields can impair the
function of the controller.
ÎMake sure the controller as well as the
system are not exposed to strong electro-
magnetic fields.
Contents
1 Overview............................................................. 3
2 Installation .......................................................... 4
2.1 Mounting....................................................................4
2.2 Electrical connection...............................................4
2.3 Data communication / Bus ....................................6
2.4 SD card slot ..............................................................6
2.5 Overview of the systems.......................................7
2.6 System layouts..........................................................9
3 Operation and function................................... 69
3.1 Buttons.................................................................... 69
3.2 Selecting menu points and adjusting values ... 69
3.3 Menu structure...................................................... 69
3.4 Indications and system monitoring display ..... 70
3.5 Further indications ............................................... 71
4 Status menu ..................................................... 72
5 Initial commissioning....................................... 73
6 Functions and options ..................................... 75
6.1 Status level.............................................................. 75
6.2 Adjustment channels............................................ 78
6.3 Overview of options and their parameters.... 94
7 User code and short menu -
Adjustment values............................................ 96
8 Messages ........................................................... 97
9 Troubleshooting ............................................... 98
9.1 Miscellaneous......................................................... 99
10 Accessories .................................................... 101
10.1 Sensors and measuring instruments............... 101
10.2 Interface adapters............................................... 101
10.3 Visualisation modules ........................................ 102
11 Index ................................................................ 103

© AMK Solac 11252 DeltaSol_BX.monen.indd
3 |
Level 5
• Extra large graphic display
• 4 relay outputs
• 7 sensor inputs,
2 of them for Grundfos Direct Sensors™
• 2 PWM outputs for speed control of high-
efficiency pumps
• Data logging onto SD card
• Drainback option
• Time-controlled thermostat function
• VBus®
• Energy-saving switch-mode power supply
1 Overview
Included:
1 x Level 5
1 x accessory bag
3 x screw and wall plug
8 x strain relief and screw
Additionally included in the full kit:
2 x FKP6 sensor
2 x FRP6 sensor
Technical data:
Housing:
plastic, PC-ABS and PMMA
Protection type: IP 20 / EN 60 529
Protection class: I
Ambient temp.: 0 ... 40 °C
Dimensions: 204 x 170 x 47 mm
Mounting: wall mounting, also suitable for mounting into
patch panels
Display: System-Monitoring-Display for system visuali-
sation, 16-segment display, 7-segment display, 8 symbols,
control lamp (directional pad) and background illumination
Operation: 7 push buttons at the front of the housing
Functions: System controller for solar and heating sy-
stems. Functions such as: ∆T control, pump speed control,
heat quantity measurement, operating hours counter
for the solar pump, tube collector function, thermostat
function, store loading in layers, priority logic, drainback
option, booster function, heat dump function, thermal
disinfection function, PWM pump control, function control
according to BAFA guidelines.
Inputs:
5 inputs for Pt1000 temperature sensors, inputs for 1
Grundfos Direct Sensor™ VFS and 1 Grundfos Direct
Sensor™ RPS, 1 Impulse input V40
Outputs:
3 semiconductor relays, 1 standard relay, 2 PWM outputs
Interfaces: VBus®, SD card slot
Power supply:
100 ... 240 V~, 50 ... 60 Hz
Switching capacity per relay:
1 (1) A 100 ... 240 V~ (semiconductor relay)
2 (1) A 100 ... 240 V~ (standard relay)
Total switching capacity: 4 A
Standby power consumption: < 1W
Mode of operation: type 1.Y
Note:
For more information about accessories,see p.101.
Note:
The SD card is not included with the controller

© AMK Solac 11252 DeltaSol_BX.monen.indd
|4
Level 5
The unit must only be located in dry interior rooms.
The controller must additionally be supplied from a double
pole switch with contact gap of at least 3 mm.
Please pay attention to separate routing of sensor cables
and mains cables.
In order to mount the device to the wall, carry out the
following steps:
ÎUnscrew the cross-head screw from the cover and re-
move it along with the cover from the housing
ÎMark the upper fastening point on the wall. Drill and
fasten the enclosed wall plug and screw leaving the head
protruding
ÎHang the housing from the upper fastening point and
mark the lower fastening points (centres 150 mm)
ÎInsert lower wall plugs
ÎFasten the housing to the wall with the lower fastening
screws and tighten
ÎCarry out the electrical wiring in accordance with the
terminal allocation, see chap. 2.2
ÎPut the cover on the housing
ÎAttach with the fastening screw
2 Installation
2.1 Mounting
2.2 Electrical connection
Note:
The pump speed must be set to 100 % when
auxiliary relays or valves are connected.
WARNING! Electric shock!
Upon opening the housing, live parts
are exposed.
ÎAlways disconnect the control-
ler from power supply before
opening the housing!
ATTENTION! ESD damage!
Electrostatic discharge can lead to da-
mage to electronic components!
ÎTake care to discharge proper-
ly before touching the inside
of the device! To do so, touch
a grounded surface such as a
radiator or tap!
upper fastening
point
lower fastening point
cover
screw
Note
Strong electromagnetic fields can impair the
function of the controller.
ÎMake sure the controller as well as the
system are not exposed to strong electro-
magnetic fields.

© AMK Solac 11252 DeltaSol_BX.monen.indd
5 |
Level 5
Temp. Sensor
Pt1000
T4A
100 ... 240 V~
50-60 Hz
1 (1) A (100 ... 240) V~
2 (1) A (100 ... 240) V~
R1-R3
R4
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PWM 1
PWM 2
N
R4
V40
L'
VFS
RPS
CU 72102083.01
DeltaSol BX
®
Made in Germany
IP 20
The controller is supplied with power via a mains cable.
The power supply of the device must be 100 ...240 V~
(50 ...60 Hz).
The controller is equipped with 4 relays in total to which
loads such as a pump, a valve, etc. can be connected:
• Relays R1 ... R3 are semiconductor relays, designed for
pump speed control
Conductor R1... R3
Neutral conductor N
Ground terminal
• Relay 4 is a standard relay
Conductor R4
Neutral conductor N
Ground terminal
Depending on the product version, mains cable and sensor
cables are already connected to the device. If that is not the
case, please proceed as follows:
Connect the temperature sensors (S1 to S5) to the
corresponding terminals with either polarity:
S1 = sensor 1 (collector sensor )
S2 = sensor 2 (e. g. store sensor base)
S3 = sensor 3 (e. g. store sensor top)
S4 = sensor 4 (e. g. store sensor store 2)
S5 = sensor 5 (e. g. collector sensor collector 2)
Connect the Grundfos sensors to theVFS and RPS inputs.
A V40 owmeter can be connected to the terminalsV40
and GND (either polarity).
The terminals marked “PWM” are control outputs for a
high-efficiency pump (PWM1 is allocated to R1 and PWM2
is allocated to R2).
The mains connection is at the terminals:
Neutral conductor N
Conductor L
Conductor L' (L' is not connected with the mains cable. L'
is a fused contact permanently carrying voltage)
Ground terminal
WARNING! Electric shock!
Upon opening the housing, live parts
are exposed.
ÎAlways disconnect the control-
ler from power supply before
opening the housing!
Note:
Connecting the device to the power supply must
always be the last step of the installation!
Note:
For more details about the initial commissioning
procedure, see chap. 5, page 73.
Note:
The connection depends on the system selected,
see chap. 2.6.“System layouts”
WARNING! Electric shock!
L' is a fused contact permanently
carrying voltage
ÎAlways disconnect the control-
ler from power supply before
opening the housing!

© AMK Solac 11252 DeltaSol_BX.monen.indd
|6
Level 5
2.3 Data communication / Bus
The controller is equipped with an SD card slot for storing
system data onto an SD card.The values can be opened and
visualised, e. g. in a spreadsheet programme.
Note:
Do not use an SD-HC card!
A standard SD card is not included with the Level5.
For more information about using an SD card, see chap. 6.2
(page 93) “SD card“.
2.4 SD card slot
The controller is equipped with the VBus®for data transfer
with and energy supply to external modules. The connec-
tion is carried out at the two terminals marked “VBus” and
GND (any polarity). One or more VBus®modules can be
connected via this data bus, such as:
• GA3 Large display module / Smart Display SD3
• AM1 Alarm module
• DL2 Datalogger
Furthermore, the controller can be connected to a PC via
the VBus®/USB or VBus®/LAN interface adapter (not in-
cluded with the Level5).With the ServiceCenter Software,
measured values can be read, processed and visualised.The
software allows easier function control and adjustment of
the system.
Note:
For more information about accessories,see p.101.

© AMK Solac 11252 DeltaSol_BX.monen.indd
7 |
Level 5
Standard solar system with 1
store (page 9)
Solar system with 2 stores
and heat exchange (page 11)
Solar system with 1 store
and afterheating (page 13)
Solar system with 1 store and
3-port valve for store loading
in layers (page 15)
2-store system with valve
logic, 1 pump, 3 sensors and
3-port valve (page 17)
2-store solar system with
pump logic (page 19)
Solar system with east-/west
collectors (page 21)
Solar system with 1 store and
afterheating with solid fuel
boiler (page23)
Solar system with 1 store
and heating circuit return
preheating (page 25
Solar system with 1 store,
heating circuit return pre-
heating and thermostatic
afterheating (page 27)
Solar system with store
loading in layers and heat
exchange control (page 29)
Solar system with store loa-
ding in layers and thermosta-
tic afterheating (page 31)
Solar system with store
loading in layers and after-
heating with solid fuel boiler
(page 33)
Solar system with store
loading in layers and return
preheating (page 35)
Solar system with store
loading in layers and after-
heating with heating backup
(page 37)
2-store solar system with
valve logic and heat exchange
control (page 40)
2-store solar system with
pump logic and heat ex-
change control (page 42)
Solar system with east-/west
collectors and heat exchange
control (page 45)
Solar system with east-/west
collectors and thermostatic
afterheating (page 47)
Solar system with east-/
west collectors, thermosta-
tic afterheating and return
preheating (page 49)
2.5 Overview of the systems
1234
5678
9 10 11 12
13 14 15 16
17 18 19 20

© AMK Solac 11252 DeltaSol_BX.monen.indd
|8
Level 5
Solar system with east-/west
collectors and heating circuit
return preheating (page 51)
Solar system with east-/west
collectors, store loading in
layers and and thermostatic
afterheating (page 62)
Solar system with store loa-
ding in layers and east-/west
collectors (page 53)
Solar system with east-/west
collectors, store loading in
layers and afterheating with
solid fuel boiler (page 65)
Solar system with east-/west
collectors and 2 stores (valve
logic) (page 56)
Solar system with east-/west
collectors, store loading in
layers and heat exchange
(page 59)
25 26
21 22 23 24

© AMK Solac 11252 DeltaSol_BX.monen.indd
9 |
Level 5
2.6 System layouts
System 1
Standard solar system with 1 store
The controller calculates the temperature difference bet-
ween collector sensor S1 and store sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
Relay Description
R1 Solar pump
R2 optional:
Thermal disinfection
Booster pump
Parallel relay
Heat dump
R3
R4
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory
setting
Change to Description Page
ARR 1 System 78
LOAD > Loading
DT O 4 K Switch-on temperature difference 78
DT F 2 K Switch-off temperature difference 78
DT S 10 K Set temperature difference 78
RIS 2 K Rise 78
S MAX 75 °C Store maximum limitation 78
SMAXS 2 Sensor store max 79
COL > Collector
CEM 115°C Collector emergency temperature 80
OCCO** OFF Option collector cooling 80
CMAX 95 °C Maximum collector temperature 80
OCMI OFF Option collector minimum limitation 80
Sensor/Ter-
minal
Designation Description
S1 TCOL Temperature collector
S2 TSTB Temperature store base
S3 Optional sensor for measurement
purposes or options
S4
S5
VFS
RPS
V40
temperature difference, the pump (R1) will be switched on
and the store will be loaded until the switch-off temperature
difference or the maximum store temperature is reached.
R1
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PWM 1
PWM 2
N
R4
V40
L'
VFS
RPS
out in

© AMK Solac 11252 DeltaSol_BX.monen.indd
|10
Level 5
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory
setting
Change to Description Page
CMIN 10 °C Minimum collector temperature 80
OTCO OFF Option tube collector function 81
TCST 07:00 Tube collector starting time 81
TCEN 19:00 Tube collector ending time 81
TCRU 30 s Tube collector runtime 81
TCIN 30 min Tube collector standstill interval 81
OCFR OFF Option collector frost protection 81
CFR O 4 °C Antifreeze temperature collector on 81
CFR F 5 °C Antifreeze temperature collector off 81
LLOGI > Loading logic
ODB > OFF Drainback option 83
OOVRU* OFF Overrun option 84
COOL > Cooling functions
OSYC** OFF System cooling 85
OSTC OFF Store cooling 85
OHDP** OFF Heat dump 85
PUMP > Pump speed
PUMP1 PULS Speed variant pump 1 79
PUMP2 OnOF Speed variant pump 2 79
PUMP3 OnOF Speed variant pump 3 79
MAN > Manual mode
MAN1 Auto Manual mode 1 88
MAN2 Auto Manual mode 2 88
MAN3 Auto Manual mode 3 88
MAN4 Auto Manual mode 4 88
BLPR > OFF Blocking protection 88
OTDIS > OFF Thermal disinfection option 89
OPARR > OFF Parallel relay option 90
OHQM > OFF Heat quantity measurement option 90
GFDS > OFF Registration Grundfos sensors 90
PRS* > OFF Pressure monitoring option 92
DATE > OFF Enter date 92
LANG > En Language 93
UNIT > °C Unit 92
OSDC > SD card option 93
CODE 0000 User code 96
RESET OFF Factory setting
* This channel is only available if the Grundfos sensors have been registered in the GFDS channel.
** are blocked against each other

© AMK Solac 11252 DeltaSol_BX.monen.indd
11 |
Level 5
System 2
Solar system with 2 stores and heat exchange
The controller calculates the temperature difference bet-
ween collector sensor S1 and store sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference, the pump (R1) will be switched on
and the store will be loaded until the switch-off temperature
difference or the maximum store temperature is reached.
Heat exchange between S3 and S4 is possible.
Relay Description
R1 Solar pump
R2 Heat exchange pump
R3 optional:
Thermal disinfection
Booster pump
Parallel relay
Heat dump
R4
Sensor/Ter-
minal
Designation Description
S1 TCOL Temperature collector
S2 TST1B Temperature store 1 base
S3 TST1T Temperature store 1 top
S4 TST2B Temperature store 2 top
S5 Optional sensor for measurement
purposes or options
VFS
RPS
V40
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory
setting
Change to Description Page
ARR 1 2 System 78
LOAD > Loading
DT O 4 K Switch-on temperature difference 78
DT F 2 K Switch-off temperature difference 78
DT S 10 K Set temperature difference 78
RIS 2 K Rise 78
S MAX 75 °C Store maximum limitation 79
SMAXS 2 Sensor store max 79
COL > Collector
CEM 115 °C Collector emergency temperature 80
OCCO** OFF Option collector cooling 80
CMAX 95 °C Maximum collector temperature 80
OCMI OFF Option collector minimum limitation 80
R2
R1
S4
S3
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PWM 1
PWM 2
N
R4
V40
L'
VFS
RPS
out in

© AMK Solac 11252 DeltaSol_BX.monen.indd
|12
Level 5
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory
setting
Change to Description Page
CMIN 10 °C Minimum collector temperature 80
OTCO OFF Option tube collector function 81
TCST 07:00 Tube collector starting time 81
TCEN 19:00 Tube collector ending time 81
TCRU 30 s Tube collector runtime 81
TCIN 30 min Tube collector standstill interval 81
OCFR OFF Option collector frost protection 81
CFR O 4 °C Antifreeze temperature collector on 81
CFR F 5 °C Antifreeze temperature collector off 81
LLOGI > Loading logic
ODB > OFF Drainback option 83
OOVRU* OFF Overrun option 84
COOL > Cooling functions
OSYC** OFF System cooling 85
OSTC OFF Store cooling 85
OHDP** OFF Heat dump 85
DT3 > Heat exchange
DT3O 6 K Switch-on difference 86
DT3F 4 K Switch-off difference 86
DT3S 10 K Set difference 86
RIS3 2 K Rise 86
MAX3O 60 °C Switch-on temperature (maximum limitation) 86
MAX3F 58 °C Switch-off temperature (maximum limitation) 86
MIN3O 5 °C Switch-on temperature (minimum limitation) 86
MIN3F 10 °C Switch-off temperature (minimum limitation) 86
S2DT3 4 Reference sensor heat sink 86
PUMP > Pump speed
PUMP1 PULS Speed variant pump 1 79
PUMP2 OnOF Speed variant pump 2 79
PUMP3 OnOF Speed variant pump 3 79
MAN > Manual mode
MAN1 Auto Manual mode 1 88
MAN2 Auto Manual mode 2 88
MAN3 Auto Manual mode 3 88
MAN4 Auto Manual mode 4 88
BLPR > OFF Blocking protection 88
OTDIS > OFF Thermal disinfection option 89
OPARR > OFF Parallel relay option 90
OHQM > OFF Heat quantity measurement option 90
GFDS > OFF Registration Grundfos sensors 90
PRS* > OFF Pressure monitoring option 92
DATE> OFF Enter date 92
LANG > En Language 93
UNIT > °C Unit 92
OSDC > SD card option 93
CODE 0000 User code 96
RESET OFF Factory setting
* This channel is only available if the Grundfos sensors have been registered in the GFDS channel.
** are blocked against each other

© AMK Solac 11252 DeltaSol_BX.monen.indd
13 |
Level 5
System 3
Solar system with 1 store and afterheating
The controller calculates the temperature difference bet-
ween collector sensor S1 and store sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference, the pump (R1) will be switched on
and the store will be loaded until the switch-off temperature
difference or the maximum store temperature is reached.
Domestic hot water afterheating (R4) can be carried out
with a thermostat function (S3). If the value at S3 reaches
the switch-on temperature for the afterheating, the relay is
energised. If the value exceeds the switch-off temperature
for the afterheating, the relay is switched off again.
Sensor/Ter-
minal
Designation Description
S1 TCOL Temperature collector
S2 TSTB Temperature store base
S3 TSTT Temperature store top
S4 Optional sensor for measurement
purposes or options
S5
VFS
RPS
V40
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory
setting Change to Description Page
ARR 1 3 System 78
LOAD > Loading
DT O 4 K Switch-on temperature difference 78
DT F 2 K Switch-off temperature difference 78
DT S 10 K Set temperature difference 78
RIS 2 K Rise 78
S MAX 75 °C Store maximum limitation 79
SMAXS 2 Sensor store max 79
COL > Collector
CEM 115 °C Collector emergency temperature 80
R4
R1 S3
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PWM 1
PWM 2
N
R4
V40
L'
VFS
RPS
out in

© AMK Solac 11252 DeltaSol_BX.monen.indd
|14
Level 5
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory
setting Change to Description Page
OCCO** OFF Option collector cooling 80
CMAX 95 °C Maximum collector temperature 80
OCMI OFF Option collector minimum limitation 80
CMIN 10 °C Minimum collector temperature 80
OTCO OFF Option tube collector function 81
TCST 07:00 Tube collector starting time 81
TCEN 19:00 Tube collector ending time 81
TCRU 30 s Tube collector runtime 81
TCIN 30 min Tube collector standstill interval 81
OCFR OFF Option collector frost protection 81
CFR O 4 °C Antifreeze temperature collector on 81
CFR F 5 °C Antifreeze temperature collector off 81
LLOGI > Loading logic
ODB > OFF Drainback option 83
OOVRU* OFF Overrun option 84
COOL > Cooling functions
OSYC** OFF System cooling 85
OSTC OFF Store cooling 85
OHDP** OFF Heat dump 85
AH > Afterheating option
AH O 40 °C Afterheating switch-on temperature 87
AH F 45 °C Afterheating switch-off temperature 87
t1O 06:00 Switch-on time 1 88
t1F 22:00 Switch-off time 1 88
t2O 00:00 Switch-on time 2 88
t2F 00:00 Switch-off time 2 88
t3O 00:00 Switch-on time 3 88
t3F 00:00 Switch-off time 3 88
PUMP > Pump speed
PUMP1 PULS Speed variant pump 1 79
PUMP2 OnOF Speed variant pump 2 79
PUMP3 OnOF Speed variant pump 3 79
MAN > Manual mode
MAN1 Auto Manual mode 1 88
MAN2 Auto Manual mode 2 88
MAN3 Auto Manual mode 3 88
MAN4 Auto Manual mode 4 88
BLPR > OFF Blocking protection 88
OTDIS > OFF Thermal disinfection option 89
OPARR > OFF Parallel relay option 90
OHQM > OFF Heat quantity measurement option 90
GFDS > OFF Registration Grundfos sensors 90
PRS* > OFF Pressure monitoring option 92
DATE> Enter date 92
LANG > En Language 93
UNIT > °C Unit 92
OSDC > SD card option 93
CODE 0000 User code 96
RESET OFF Factory setting
* This channel is only available if the Grundfos sensors have been registered in the GFDS channel.
** are blocked against each other

© AMK Solac 11252 DeltaSol_BX.monen.indd
15 |
Level 5
R3
R1 S3
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PWM 1
PWM 2
N
R4
V40
L'
VFS
RPS
out in
The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S3.If the measured tem-
perature differences are higher than the adjusted switch-on
temperature differences, the pump (R1) will be activated and
the corresponding store zone will be loaded up to the adju-
sted maximum temperature via the valve (R3).The priority
logic effects prior loading of the upper zone of the store.
Sensor/Ter-
minal
Designation Description
S1 TCOL Temperature collector
S2 TSTB Temperature store base
S3 TSTT Temperature store top
S4 Optional sensor for measurement
purposes or options
S5
VFS
RPS
V40
Relay Description
R1 Solar pump
R2/R4 optional:
Thermal disinfection
Parallel relay
Heat dump
R3 3-port valve store top/base
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory
setting
Change to Description Page
ARR 1 4 System 78
LOAD1 > Loading 1
DT1O 4 K Switch-on temperature difference 1 78
DT1F 2 K Switch-off temperature difference 1 78
DT1S 10 K Set temperature difference 1 78
RIS1 2 K Rise 1 78
S1MAX 75 °C Store maximum limitation 1 78
SMXS1 2 Sensor store max 1 79
LOAD2 > Loading 2
DT2O 4 K Switch-on temperature difference 2 78
DT2F 2 K Switch-off temperature difference 2 78
DT2S 10 K Set temperature difference 2 78
RIS2 2 K Rise 2 78
System 4
Solar system with 1 store and 3-port valve for store loading in layers
Note: 3-port valve normally open - store base

© AMK Solac 11252 DeltaSol_BX.monen.indd
|16
Level 5
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory
setting
Change to Description Page
S2MAX 60 Store maximum limitation 2 78
LST2 ON Loading store 2 79
COL > Collector
CEM 115 °C Collector emergency temperature 80
OCCO** OFF Option collector cooling 80
CMAX 95 °C Maximum collector temperature 80
OCMI OFF Option collector minimum limitation 80
CMIN 10 °C Minimum collector temperature 80
OTCO OFF Option tube collector function 81
TCST 07:00 Tube collector starting time 81
TCEN 19:00 Tube collector ending time 81
TCRU 30 s Tube collector runtime 81
TCIN 30 min Tube collector standstill interval 81
OCFR OFF Option collector frost protection 81
CFR O 4 °C Antifreeze temperature collector on 81
CFR F 5 °C Antifreeze temperature collector off 81
LLOGI > Loading logic
PRIO Priority logic 82
PRIO 2 Priority logic 82
OSTS OFF Store set option 82
TST1 60 °C Set store temperature store 1 82
TST2 45 °C Set store temperature store 2 82
tLB 2 min Loading break time 82
tRUN 15 min Circulation runtime 82
PSPEE OFF Pause speed option 83
PDELA OFF Pump delay option 83
OOVRU* OFF Overrun option 84
COOL > Cooling functions
OSYC** OFF System cooling 85
OSTC OFF Store cooling 85
OHDP** OFF Heat dump 85
PUMP > Pump speed
PUMP1 PULS Speed variant pump 1 79
PUMP2 OnOF Speed variant pump 2 79
PUMP3 OnOF Speed variant pump 3 79
MAN > Manual mode
MAN1 Auto Manual mode 1 88
MAN2 Auto Manual mode 2 88
MAN3 Auto Manual mode 3 88
MAN4 Auto Manual mode 4 88
BLPR > OFF Blocking protection 88
OTDIS > OFF Thermal disinfection option 89
OPARR > OFF Parallel relay option 90
OHQM > OFF Heat quantity measurement option 90
GFDS > OFF Registration Grundfos sensors 90
PRS* > OFF Pressure monitoring option 92
DATE> OFF Enter date 92
LANG > En Language 93
UNIT > °C Unit 92
OSDC > SD card option 93
CODE 0000 User code 96
RESET OFF Factory setting
* This channel is only available if the Grundfos sensors have been registered in the GFDS channel.
** are blocked against each other

© AMK Solac 11252 DeltaSol_BX.monen.indd
17 |
Level 5
The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S4. If the measured tem-
perature differences are higher than the adjusted switch-on
temperature differences, the pump (R1) will be activated and
the corresponding store will be loaded up to the adjusted
maximum temperature via the valve (R3). Store 1 is loaded
with priority.
Sensor/Ter-
minal
Designation Description
S1 TCOL Temperature collector
S2 TST1B Temperature store 1 base
S3 Optional sensor for measurement
purposes or options
S4 TST2B Temperature store 2 base
S5 Optional sensor for measurement
purposes or options
VFS
RPS
V40
Relay Description
R1 Solar pump
R2/R4 optional:
Thermal disinfection
Parallel relay
Heat dump
R3 3-port valve store 1 / 2
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory
setting
Change to Description Page
ARR 1 5 System 78
LOAD1 > Loading 1
DT1O 4 K Switch-on temperature difference 1 78
DT1F 2 K Switch-off temperature difference 1 78
DT1S 10 K Set temperature difference 1 78
RIS1 2 K Rise 1 78
S1MAX 75 °C Store maximum limitation 1 78
SMXS1 2 Sensor store max 1 79
LOAD2 > Loading 2
DT2O 4 K Switch-on temperature difference 2 78
System 5
2-store system with valve logic, 1 pump, 3 sensors and 3-port valve
R3
R1
S4
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PWM 1
PWM 2
N
R4
V40
L'
VFS
RPS
out in
Note: 3-port valve normally open - store 1 (S2)

© AMK Solac 11252 DeltaSol_BX.monen.indd
|18
Level 5
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory
setting
Change to Description Page
DT2F 2 K Switch-off temperature difference 2 78
DT2S 10 K Set temperature difference 2 78
RIS2 2 K Rise 2 78
S2MAX 60 °C Store maximum limitation 2 78
SMXS2 4 Sensor store max 2 79
LST2 ON Loading store 2 79
COL > Collector
CEM 115 °C Collector emergency temperature 80
OCCO** OFF Option collector cooling 80
CMAX 95 °C Maximum collector temperature 80
OCMI OFF Option collector minimum limitation 80
CMIN 10 °C Minimum collector temperature 80
OTCO OFF Option tube collector function 81
TCST 07:00 Tube collector starting time 81
TCEN 19:00 Tube collector ending time 81
TCRU 30 s Tube collector runtime 81
TCIN 30 min Tube collector standstill interval 81
OCFR OFF Option collector frost protection 81
CFR O 4 °C Antifreeze temperature collector on 81
CFR F 5 °C Antifreeze temperature collector off 81
FRPST 1 Antifreeze store selection 81
LLOGI > Loading logic
PRIO Priority logic 82
PRIO 1 Priority logic 82
OSTS OFF Store set option 82
TST1 60 °C Set store temperature store 1 82
TST2 45 °C Set store temperature store 2 82
tLB 2 min Loading break time 82
tRUN 15 min Circulation runtime 82
PSPEE OFF Pause speed option 83
PDELA OFF Pump delay option 83
OOVRU* OFF Overrun option 84
COOL > Cooling functions
OSYC** OFF System cooling 85
OSTC OFF Store cooling 85
OHDP** OFF Heat dump 85
PUMP > Pump speed
PUMP1 PULS Speed variant pump 1 79
PUMP2 OnOF Speed variant pump 2 79
PUMP3 OnOF Speed variant pump 3 79
MAN > Manual mode
MAN1 Auto Manual mode 1 88
MAN2 Auto Manual mode 2 88
MAN3 Auto Manual mode 3 88
MAN4 Auto Manual mode 4 88
BLPR > OFF Blocking protection 88
OTDIS > OFF Thermal disinfection option 89
OPARR > OFF Parallel relay option 90
OHQM > OFF Heat quantity measurement option 90
GFDS > OFF Registration Grundfos sensors 90
PRS* > OFF Pressure monitoring option 92
DATE> Enter date 92
LANG > En Language 93
UNIT > °C Unit 92
OSDC > SD card option 93
CODE 0000 User code 96
RESET OFF Factory setting
* This channel is only available if the Grundfos sensors have been registered in the GFDS channel.
** are blocked against each other

© AMK Solac 11252 DeltaSol_BX.monen.indd
19 |
Level 5
System 6
2-store solar system with pump logic
The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S4. If the measured
temperature differences are higher than the adjusted switch-
on temperature differences, the pump (R1 and R2) will be
activated and the corresponding store will be loaded up to
the adjusted maximum temperature at most.
Sensor/Ter-
minal
Designation Description
S1 TCOL Temperature collector
S2 TST1B Temperature store 1 base
S3 Optional sensor for measurement
purposes or options
S4 TST2B Temperature store 2 base
S5 Optional sensor for measurement
purposes or options
VFS
RPS
V40
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory
setting
Change to Description Page
ARR 1 6 System 78
LOAD1 > Loading 1
DT1O 4 K Switch-on temperature difference 1 78
DT1F 2 K Switch-off temperature difference 1 78
DT1S 10 K Set temperature difference 1 78
RIS1 2 K Rise 1 78
S1MAX 75 °C Store maximum limitation 1 78
SMXS1 2 Sensor store max 1 79
LOAD2 > Loading 2
DT2O 4 K Switch-on temperature difference 2 78
DT2F 2 K Switch-off temperature difference 2 78
DT2S 10 K Set temperature difference 2 78
R2R1
S4
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PWM 1
PWM 2
N
R4
V40
L'
VFS
RPS
out in

© AMK Solac 11252 DeltaSol_BX.monen.indd
|20
Level 5
Adjustment channels
Channel Sub channel 1 Sub channel 2 Factory
setting
Change to Description Page
RIS2 2 K Rise 2 78
S2MAX 60 °C Store maximum limitation 2 78
SMXS2 4 Sensor store max 2 79
LST2 ON Loading store 2 79
COL > Collector
CEM 115 °C Collector emergency temperature 80
OCCO** OFF Option collector cooling 80
CMAX 95 °C Maximum collector temperature 80
OCMI OFF Option collector minimum limitation 80
CMIN 10 °C Minimum collector temperature 80
OTCO OFF Option tube collector function 81
TCST 07:00 Tube collector starting time 81
TCEN 19:00 Tube collector ending time 81
TCRU 30 s Tube collector runtime 81
TCIN 30 min Tube collector standstill interval 81
OCFR OFF Option collector frost protection 81
CFR O 4 °C Antifreeze temperature collector on 81
CFR F 5 °C Antifreeze temperature collector off 81
FRPST 1 Antifreeze store selection 81
LLOGI > Loading logic
PRIO Priority logic 82
PRIO 1 Priority logic 82
OSTS OFF Store set option 82
TST1 60 °C Set store temperature store 1 82
TST2 45 °C Set store temperature store 2 82
OSE ON Spread function option 83
DTSE 30 Spread difference 83
tLB 2 min Loading break time 82
tRUN 15 min Circulation runtime 82
PSPEE OFF Pause speed option 83
PDELA OFF Pump delay option 83
OOVRU* OFF Overrun option 84
COOL > Cooling functions
OSYC** OFF System cooling 85
OSTC OFF Store cooling 85
OHDP** OFF Heat dump 85
PUMP > Pump speed
PUMP1 PULS Speed variant pump 1 79
PUMP2 OnOF Speed variant pump 2 79
PUMP3 OnOF Speed variant pump 3 79
MAN > Manual mode
MAN1 Auto Manual mode 1 88
MAN2 Auto Manual mode 2 88
MAN3 Auto Manual mode 3 88
MAN4 Auto Manual mode 4 88
BLPR > OFF Blocking protection 88
OTDIS > OFF Thermal disinfection option 89
OPARR > OFF Parallel relay option 90
OHQM > OFF Heat quantity measurement option 90
GFDS > OFF Registration Grundfos sensors 90
PRS* > OFF Pressure monitoring option 92
DATE> Enter date 92
LANG > En Language 93
UNIT > °C Unit 92
OSDC > SD card option 93
CODE 0000 User code 96
RESET OFF Factory setting