Ampac 226-0003 User manual

ADVANCED WARNING
SYSTEMS
Apartment Module
Installation Guide Item Numbers: 226-0003
MAN1570-2
N1236
Page 1
WORLD LEADER OF INNOVATIVE SOLUTIONS IN FIRE DETECTION AND ALARM SYSTEMS
Ampac Technologies Australia Tel: +61 8 9201 6100 Europe Tel: +44 (0) 1302 833 522 New Zealand Tel: +64 9 443 8072 www.ampac.net
Description:
The Apartment Module (AM) is a loop powered
addressable device that helps reduce the costly
consequences of an unwanted alarm
An occupant is able to silence a local audible warning,
activated by a local smoke detector, and allowing a
preset time to investigate the cause of the alarm. Local
smoke detectors can be connected directly to the AM
(conventional) or connected to the addressable loop
(addressable) and assigned to the AM.
The local smoke detector is self resetting and if the
smoke clears, then the system will return to normal. If
the smoke remains, then the local audible warning will
resound at the expiry of the preset timeout. A local
smoke detector will NOT cause a general fire alarm.
The fire system will go into general fire alarm (thus
calling the brigade) if:
Any thermal detector has gone into alarm
(conventional connected to the AM or addressable
connected to the addressable loop)
Any smoke detector in common areas has gone
into alarm
Any call point activated
ConfigManager is programmed to identify the
associations of AM’s with the local smoke detectors
(conventional and addressable) and adjustment of the
“Investigation” period.
AM Features
Loop interface with Short Circuit Isolator (SCI)
On-board Hush Switch with integrated front panel
Fire LED (red) and external hush input
Indicators: Poll / SCI LED (green – behind cover),
Fault LED (yellow – behind cover)
100V Line output with EOL monitoring
Conventional Zone circuit with selectable EOL
Installation:
Observe anti-static precautions at all times
1. Two DIP switches are provided, SW2 for
addressing (8 way) and SW1 for module options
(4 way) as below.
DIP SW1 Name Operational Parameters
1 Not used
2 EOL Zone EOL
selection
2 off: EOL = 10uF
(default setting)
2 on: EOL = 6K2
3 Ext. Hush Ext. HUSH
Input
ON for monitoring the
External Hush Input
4 Poll Poll LED ON for Poll LED operation
2. Establish the operational criteria for the module
and configure the FACP software accordingly
3. Remove the white face plate and set the
address and operational parameters via the dip
switches
4. All cabling should be run into a general purpose
wall box and connected as per Figure 1
5. The AM is then screwed to the wall box and
tested – replace the face plate once testing is
complete
Testing
1. Prepare the most suitable situation for the
installation to test the AM then create a local
“alarm”
2. The alarm indicator should illuminate when the
alarm is recognised by the AM
3. Check the silence function, the configured
“Acknowledgement” and “Investigation” timing
4. Introduce a fault condition eg 1. remove the “Ext.
Hush” EOL, 2. check short circuit isolation
operation.
ADDRESS SWITCH
EOL, EXT HUSH,
POLL SELECTION
SWITCH
POLL LED
FAULT LED
ALARM LED
LOOP IN -VE
LOOP IN +VE
EXTERNAL "HUSH"
ZONE ( CONVENTIONAL DEVICES )
100V LINE
IN
OUT
-
+
-
+
-
+
-
+
-
+
+
+
-
-
100V LINE
TO SPEAKERS
EOL
47K
EOL
22K
4K7
NOTES:
#1 SELECTED EOL MUST BE A APPLIED
EVEN IF THE FUNCTION IS UN-USED
ZONE ( CONVENTIONAL DEVICES ) EOL
10uF ( SW1 / 2 OFF )
6K2 ( SW1 / 2 ON )
FAULT TESTING
1. SHORT/OPEN THE ZONE
2. REMOVE EACH EOL IN TURN
3. REMOVE THE 100V LINE IN
POLL/SCI FAULTS
1. OPEN THE LOOP
2. SHORT THE LOOP
Figure 1: Apartment Module general wiring

ADVANCED WARNING
SYSTEMS
Apartment Module
Installation Guide Item Numbers: 226-0003
MAN1570-2
N1236
Page 2
WORLD LEADER OF INNOVATIVE SOLUTIONS IN FIRE DETECTION AND ALARM SYSTEMS
Ampac Technologies Australia Tel: +61 8 9201 6100 Europe Tel: +44 (0) 1302 833 522 New Zealand Tel: +64 9 443 8072 www.ampac.net
Addressing DIL Switch Settings
DIL switch setting DIL switch setting DIL switch setting DIL switch setting DIL switch setting
Addr 1234567 Addr 1234567 Addr 1234567 Addr 1234567 Addr 1234567
1 1000000 26 0101100 51 1100110 76 0011001 101 1010011
2 0100000 27 1101100 52 0010110 77 1011001 102 0110011
3 1100000 28 0011100 53 1010110 78 0111001 103 1110011
4 0010000 29 1011100 54 0110110 79 1111001 104 0001011
5 1010000 30 0111100 55 1110110 80 0000101 105 1001011
6 0110000 31 1111100 56 0001110 81 1000101 106 0101011
7 1110000 32 0000010 57 1001110 82 0100101 107 1101011
8 0001000 33 1000010 58 0101110 83 1100101 108 0011011
9 1001000 34 0100010 59 1101110 84 0010101 109 1011011
10 0101000 35 1100010 60 0011110 85 1010101 110 0111011
11 1101000 36 0010010 61 1011110 86 0110101 111 1111011
12 0011000 37 1010010 62 0111110 87 1110101 112 0000111
13 1011000 38 0110010 63 1111110 88 0001101 113 1000111
14 0111000 39 1110010 64 0000001 89 1001101 114 0100111
15 1111000 40 0001010 65 1000001 90 0101101 115 1100111
16 0000100 41 1001010 66 0100001 91 1101101 116 0010111
17 1000100 42 0101010 67 1100001 92 0011101 117 1010111
18 0100100 43 1101010 68 0010001 93 1011101 118 0110111
19 1100100 44 0011010 69 1010001 94 0111101 119 1110111
20 0010100 45 1011010 70 0110001 95 1111101 120 0001111
21 1010100 46 0111010 71 1110001 96 0000011 121 1001111
22 0110100 47 1111010 72 0001001 97 1000011 122 0101111
23 1110100 48 0000110 73 1001001 98 0100011 123 1101111
24 0001100 49 1000110 74 0101001 99 1100011 124 0011111
25 1001100 50 0100110 75 1101001 100 0010011 125 1011111
126 0111111
Table of contents
Other Ampac Firefighting Equipment manuals
Popular Firefighting Equipment manuals by other brands

Unifire
Unifire FORCE 50 Generic installation and Setup manual

TransTank
TransTank PantherPatrol Product handbook

American Flow Control
American Flow Control B-84-B-5 product manual

FoamPRO
FoamPRO Turbo Stream S108-4008 Installation and operation manual

ELKHART BRASS
ELKHART BRASS 8393-H Installation operation & maintenance

QTAC
QTAC 70HPK owner's manual