Anka AJ-730 User manual

Combination Photoelectric
Smoke and Carbon
Monoxide Alarm
Model:AJ-730;AJ-731;
AJ-732;AJ-933;
AJ-938;AJ-939.
This user's manual contains important information about
your smoke and cO alarm's operation. lf you are
installing this smoke and CO alarm for use by others, you
must leave this manual or a copy of it with the end user.
Photoelectric alarms are generally more effective at
detecting slow, smoldering fires that smolder for hours
before bursting into flame. Sources of these fires may
include cigarettes burning in couches or bedding.
lonization alarms are generally more effective at detecting
fast, flaming fires that consume combustible materials
rapidly and spread quickly.Sources of these fires may
include flammable liquids or paper burning in a waste
container.
For maximum protection, it is recommended to install
Combination Photoelectric
Smoke and Carbon
Monoxide Alarm
Combination Photoelectric
Smoke and Carbon
Monoxide Alarm
PLEASE READ CAREFULLY AND SAVE
IMPORTANT!
Combination Photoelectric
Smoke and Carbon
Monoxide Alarm
Combination Photoelectric
Smoke and Carbon
Monoxide Alarm
Combination Photoelectric
Smoke and Carbon
Monoxide Alarm
Combination Photoelectric
Smoke and Carbon
Monoxide Alarm
Combination Photoelectric
Smoke and Carbon
Monoxide Alarm
Combination Photoelectric
Smoke and Carbon
Monoxide Alarm
- 1 -
P/N 191111001-00 Rev.30

both ionization and photoelectric alarm.
We provide two tags with important information about what to
do in the case of co alerts.After installation, place one label
next to the alarm and another label near a fresh air source,
such as a door or window.
1.FUNCTION DESCRIPTION
2.IMPORTANT SAFETY INFORMATION
3.WHERE TO LOCATE
4.LOCATIONS TO AVOID
5.HOW TO INSTALL
6.DEACTIVATION OF ALARM
7.GENERAL CO INFORMATION
8.TESTING THE SMOKE AND CO AL ARM
9.MAINTENANCE AND CLEANING
10.PRACTICE FIRE SAFETY
11.WHAT TO DO WHEN THE ALARM SOUNDS
12.LIMITATIONS OF SMOKE AND CO AL ARM
13.LIMITED WARRANTY
1.1 Normal: 1 green led flashes,1 minute pause.
1.2 Smoke Alarm: 3 beeps with 3 red led flashes,1.5 seconds
pause.
1.3 CO Alarm: 4 beeps with 4 red led flashes,5 seconds pause.
1.4 Low Battery: 1 chirp with 1 yellow led flash,60 seconds
pause.Please replace alarm.
CONTENTS
1. FUNCTION DESCRIPTION
.
- 2 -

Trouble: 2 beeps with 2 red flashes,60 seconds pause,
Please replace alarm.
End of life: 2 chirps with 1 yellow led flash,60 seconds
pause.Deactivate and replace alarm.
Test Press and hold the test bu to.lf the alarm is normal,
the simulated smoke &CO (if compound CO alarm) alarm
sounds twice; If there is 1 beep or 3 beeps, the circuit may
fail, replace the alarm in time; If there is 2 beeps or 4 beeps,
move the alarm to fresh air. If it sill fails please replace the
alarm in time.
Silence: When the alarm is on, press the silence button,
and the alarm will be mute for 10(2 for CO alarm) minutes,
lf the alarm is not canceled after 10(2 for CO alarm)
minutes, the alarm sound will be resumed.Silence is not
allowed when smoke or carbon monoxide levels are too
high.Within 30 days after the end of life signal occurs, a
single press of the silence button can mute for 24 hours.
Alarm response time of CO sensor:
Alarm within 60-240 minutes at 70ppm.
Alarm within 10-50 minutes at 150ppm.
Alarm within 4-15 minutes at 400ppm.
DO NOT remove or disconnect battery to quiet unwanted
alarms.This will remove your protection. Open windows
or fan the air around smoke and CO alarm to silence it.
The test button accurately tests all smoke and CO alarm
functions. DO NOT use any other test method.Test
smoke and CO alarm weekly to ensure proper operation.
This smoke and CO alarm should be installed only by a
2.IMPORTANT SAFETY INFORMATION
PLEASE READ AND SAVE THESE INSTRUCTIONS.
2.1
2.2
2.3
WARNING!
1.5
1.6
1.7
1.8
- 3 -

licensed, qualified electrician. Observe and follow all local
and national electrical and building codes for installation.
This smoke and CO alarm lS NOT designed to be the
PRIMARY protection for buildings that require complete
fire alarm systems.Buildings of this type include hotels,
motels, dormitories, hospitals, nursing homes, and group
homes.This is true even if they were once single family
homes. However, this smoke and CO alarm MAY be used
inside individual rooms as SUPPL EMENTAL protection.
lnstall a smoke and CO alarm in every room and on every
level of the home. Smoke may not reach the smoke and
CO alarm for many reasons.For example, if a fire starts in
a remote part of the home, on another level, in a chimney,
wall , roof , or on the other side of a closed door, smoke
may not reach the smoke and CO alarm in time to alert
household members.A smoke and CO alarm will not
promptly detect a fire EXCEPT in the area or room in
which it is installed.
Smoke and CO alarms may not alert every household
member every time.The alarm horn is oud in order to alert
individuals to a potential danger. However, there may be
limiting circumstances where a household member may
not hear the alarm (i.e., outdoor or indoor noise, sound
sleepers, drug or alcohol usage, the hard of hearing, etc.).
lf you suspect that this smoke and CO alarm may not alert
a household member, install and maintain specialty smoke
and cO alarm. Household members must hear the alarm's
warning sound and quickly respond to it to reduce the risk
of damage, injury, or death that may result from fire. lf a
household member is hard of hearing, install special
smoke and CO alarm with lights or vibrating devices to
alert occupants.
Smoke and cO alarms can sound their alarms only
when they detect smoke. smoke and CO alarms
2.4
2.5
2.6
2.7
- 4 -

detect combustion particles in the air.They do not
sense heat, flame, or gas.This smoke and CO alarm
is designed to give audible warning of a developing
fire.However, many fires are fast-burning, explosive,
or intentional. Others are caused by carelessness or
safety hazards. Smoke may not reach the smoke and
CO alarm QUICKLY ENOUGH to ensure safe
escape.smoke and CO alarms have limitations.This
smoke and CO alarm is not foolproof and is not
warranted to protect lives or property from fire. smoke
and CO alarms are not a substitute for insurance.
Homeowners and renters should insure their lives
and property. In addition, it is possible for the smoke
and Co alarm to fail at any time.For this reason, you
must test the smoke and CO alarm weekly and
replace every 10 years.
As a minimum, smoke and CO alarms should be
located between sleeping areas and potential sources
of fire such as living rooms and kitchens.In single
story homes with one sleeping area, a smoke and CO
alarm should be installed in the hallway, as close as
possible to the living accommodation. To ensure
audibility in bedrooms, no smoke and CO alarm
should be further away than 3m from any bedroom
door. It may be necessary to install more than one
smoke and CO alarm, particularly the hallway is more
than 15m long. ln single story homes with two separate
sleeping areas, a minimum of two smoke and CO
alarms is required, one outside each sleeping area. ln
multilevel or split level homes, as a minimum a smoke
3.WHERE TO LOCATE
3.
1
- 5 -

and CO alarm should be installed on the ground floor
between the staircase and any rooms in which a fire
might start and on each story in circulation areas which
form part of escape route (normally hallways and
landings).
Additional alarms should be installed in bedrooms in
anticipation of fires originating here, caused by faulty
wiring, lights, appliances, smokers or other hazards.
For best protection,smoke and CO alarms should be
installed in every room in your home, apart from those
listed in the Section 4 LOCATIONS TO AVOID. Heat
alarms should be used in kitchens, boiler rooms,
laundry, rooms, garages and such like, where smoke
and CO alarms would be unsuitable.
Install smoke and CO alarms in circulation areas at a
distance no greater than 7.5m from the farthest wall,
no greater than 7.5m from a door to any room in which
a fire might start and no greater than 7.5m from the
next smoke and CO alarm.
As it is impossible to predict the source of a fire, the
best location for an alarm is usually the center of a
room or hallway. If it is necessary to place a smoke
and cO alarm on a wall, always locate the detection
element of the alarm 150mm to 300mm(6 to 12
inches) below the ceiling and the bottom of the alarm
above the level of doors and other openings.
In rooms with simple sloped, peaked or gabled ceilings,
install smoke and CO alarms on the ceiling 900mm
(3feet) from the highest point of the ceiling. "Dead air
at the peak of a ceiling may prevent the smoke from
reaching the alarm in time to provide an early warning.
Read Section 4 LOCATIONS TO AVOID and Section
and 13 LIMITATIONS OF smoke and CO alarms in
this manual.
3.2
3.3
3.4
3.5
3.6
3.7
- 6 -

CAUTION:
Research indicates that substantial increases in warning
time can be obtained with each properly installed,
additional alarm. It is strongly recommended that advice
in 3.3 above be followed to ensure maximum protection.
- 7 -

●For your information, the National Fire Alarm and Signaling
Code,NFPA72, reads as follows:
●29.5.1 *Required Detection.
●*29.5.1.1 Where required by applicable laws, codes, or
standards for a specific type of occupancy, approved
single- and multiple-station smoke alarms shall be installed
as follows:
(1)*In all sleeping rooms and guest rooms
(2)*Outside of each separate dwelling unit sleeping area,
within 21 ft(6.4 m) of any door to a sleeping room, the
distance measured along a path of travel
(3)On every level of a dwelling unit, including basements
(4) On every level of a residential board and care occupancy
(small facility),including basements and excluding crawl
spaces and unfinished attics
(5) *In the living area(s) of a guest suite
(6) In the living area(s) of a residential board and care
occupancy.
●(Reprinted with permission from NFPA72R, National Fire Alarm
and Signaling Code Copyright c 2012 National Fire Protection
Association, Quincy, MA 02269.This reprinted material is not the
complete and official position of the National Fire Protection
Association, on the referenced subject which is represented only
by the standard in its entirety).
(National Fire Alarm and Signaling Code Rand NFPA72R are
registered trademarks of the National Fire Protection
Association, Inc., Quincy, MA 02269.)
IMPORTANT:
These alarms are intended to primarily for
single-occupancy private dwellings.For use in other
applications the manufacturer's advice must be sought.
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL FIRE PROTECTION
AssOCIATION'S STANDARD 72 (National Fire Protection
Association, Batterymarch Park, Quincy, MA 02269).
- 8 -

In turbulent air from fans, heaters, doors, windows, etc.,
which could draw smoke away from the alarm.
ln high humidity area such as bathrooms and shower
rooms, or where the temperature exceeds 37.8°C(100°F)
or falls below 4.4°C(40°F), as high humidity can trigger
nuisance alarm,
At the peal of an "A" frame ceiling. "Dead air" at the top
may prevent smoke from reaching the alarm in time to
provide early warning.
Less than 300mm (12 inches) from the wall when mounted
on the ceiling.
In insect-infested areas.Tiny insects may affect performance.
ln kitchens, boiler rooms, laundry rooms, garages.
Combustion particles from cooking or car exhaust and
dust and moisture could trigger a nuisance alarm.The
alarm is not to be located within 5 feet (1.5 m) of any
cooking appliance.
In very dusty or dirty areas. Dirt and dust can build up and
impair performance.
Within 300mm(12 inches)of light fittings or room corners.
In locations which would make routine testing or
maintenance hazardous (e.g.over a stairwell).
On Poorly insulated walls or ceilings.
Near objects such as ceiling decorations which might
impede the path of smoke to the alarm.
Within 1500mm (5 feet) of fluorescent light fittings.
4.LOCATIONS TO AVOID
5.HOW TO INSTALL
4.1
4.2
4.
3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12
DO NOT locate smoke and CO alarms:
- 9 -

Taking the bracket from the detector.
Draw a horizontal or vertical line 6 inches (10cm)
long on the area of ceilings or walls where this smoke
and cO alarm is intended to locate (see Section 3
WHERE TO LOCATE)
Locate the mounting bracket in your chosen position.
Align the two longest mounting slots with the line.
Draw a mark in the center of each slot.
Drill the holes at the marks Mountings with a 3/16-inch
(5mm) dill.
Insert the anchor plugs and screw the mounting
bracket to the chosen position. DO NOT
5.1
5.2
5.3
5.
4
5.5
- 10 -

6.DEACTIVATION OF ALARM
7. GENERAL CO INFORMATION
Please deactivate the alarm at the end of the 10-year
life.The deactivation of alarm is permanent and
unrecoverable, and the smoke or co cannot be
detected after it is deactivated.After the failure, the
battery will be depleted.
Break the label witha
screwdriver andturn the
device ofdeactivation 90
degrees clockwise,
then the alarm will
be deactivated.
7.1The following conditions can result in transient CO
situations, such as:
When the alarm is first installed on the mounting board,
itwill automatically start the alarm.Once activated, the
battery will power the alarm under normal conditions and
will last for 10 years.
WARNING!
- 11 -
OVER-TIGHT THE SCREWs, this will distort the
mounting bracket.
Attach the alarm to the mounting bracket and turn
clockwise to lock into place.
Test the smoke and cO alarm. See Section 8
TESTING THE smoke and CO alarm.
5.7
5.6

- 12 -
1)Excessive spillage or reverse venting of fuel burning
appliances caused by:
i) Outdoor ambient conditions such as wind direction
and/or velocity, including high gusts of wind; heavy air in
the vent pipes(cold/humid air with extended periods
between cycles).
ii) Negative pressure differential resulting from the use of
exhaust fans.
ii) Simultaneous operation of several fuel burming appliances
competing for limited internal air.
iv) Vent pipe connection vibrating loose from clothes dryers,
furnaces, or water heaters.
v) Obstructions in or unconventional vent pipe designs
which amplify the above situations.
2) Extended operation of unvented fuel burning devices
(range, oven, fireplace, etc.).
3)Temperature inversions which can trap exhaust gasses
near the ground.
4) Car idling in an open or closed attached garage, or near a
home.
7.2 The following symptoms are related to CARBON
MONOXIDE POISONING and should be discussed with
ALL members of the household:
●Mild Exposure: Slight headache.nausea,vomiting,fatigue
(often described as "Flu-like' symptoms).
●Medium Exposure: Severe throbbing headache,drowsiness,
confusion, fast heat rate.
●Extreme Exposure: Unconsciousness,convulsions,
cardiorespiratory failure, death.
●Many cases of reported carbon monoxide poisoning indicate
that while victims are aware they are not well, they become
so disoriented they are unable to save themselves by
either exiting the building, or calling for assistance.Also,

8.TESTING THE SMOKE AND CO ALARM WARNING
NOTE: REPLACE OR RETURN THE ALARM IF THE TEST
FUNCTION DOES NOT OPERATE PROPERLY AFTER
FOLLOWING THE PROCEDURES OUTLINED ABOVE.
young children and household pets may be the first
effected.Familiarization with the effects of each level
isimportant.
●Test each smoke and CO alarm to be sure it is installed
correctly and operating properly.
●The test button accurately tests all functions. DO NOT use
an open flame to test this smoke and CO alarm. You many
ignite and damage the smoke and CO alarm or your home.
●Test smoke and CO alarms weekly and upon returning from
vacation or when no one has been in the household for
several days.
●Stand at arm's length from the smoke and co alarm when
testing.The alarm horn is loud to alert you to an emergency
and can be harmful to hearing.
Press and release the test button to test the alarm.The
alarm will sound loud short beeps.
●The alarm may stop sounding once releasing the test button.
- 13 -
DANGER: if alarm horn
sounds, and smoke and CO
alarm is not being tested, the
smoke and CO alarm is
sensing smoke.
THE SOUND OF THE AL ARM
HORN REQUIRES YOUR
IMMEDIATEATTENTION AND
ACTION.

9.MAINTENANCE AND CLEANING
10.PRACTICE FIRE SAFETY
To ensure your alarm works normally, reach the service life
that predicts, safeguard your life property safety, you should
undertake cleanness according to the following specification
and maintain.
9.1 Test your alarm at least once a week.
9.2 Clean your alarm at least once a year; Use a vacuum
cleaner to remove dust, or use a wet towel to gently wipe
the alarm.Please do not use water, detergent, solvent and
so on, so as not to damage the alarm.
9.3 Do not paint the alarm.This will affect the smoke and
carbon monoxide into the detection room, resulting in
alarm failure.If the smoke and CO alarm cannot be
cleaned, replace the unit immediately.
9.4 lf you often hear false alarms, See Section 4 LOCATIONS
TO AVOID and check if they are installed in the wrongplace.
lf the smoke and CO alarm sounds its alarm horn, and you
have not pushed the test button, it is warning of a dangerous
situation.Your immediate response is necessary.To prepare
for such occurrences, develop family escape plans, discuss
them with all household members, and practice them regularly.
10.1 Expose everyone to the sound of a smoke and co alarm
and explain what the sound means.
10.2 Determine two exits from each room and an escape
route to the outside from each exit.
10.3 Teach all household members to touch the door and use
- 14 -

11.WHAT TO DO WHEN THE ALARM SOUNDS
NOTE: These guidelines will assist you in the event
of a fire.However, to reduce the chance that fires will
start, practice fire safety rules and prevent hazardous
situations.
Current studies have shown smoke alarms may not
awaken all sleeping individuals, and that it is the
responsibility of individuals in the household that are
capable of assisting others to provide assistance to
those who may not be awakened by the alarm sound,
or to those who may be incapable of safely
evacuating the area unassisted.
an alternate exit if the door is hot.INSTRUCT THEM
NOT TO OPEN THE DOOR IF THE DOOR IS HOT,
10.4 Teach household members to crawl along the floor
to stay below dangerous smoke, fumes, and gases.
10.5 Determine a safe meeting place for all members
outside the building.
11.1 WHEN THE SOMKE ALARM SOUNDS
●Don't panic; stay calm.
●Leave the building as quickly as possible.Touch doors
to feel if they are hot before opening them. Use an
alternate exit if necessary. Crawl along the floor, and
DO NOT stop to collect anything.
●Meet at a pre-arranged meeting place outside the building.
●Call the fire department from OUTSIDE the building.
●DO NOT GO BACK INSIDEABURNING BUILDING.
Wait for the fire department to arrive.
- 15 -

11.2 WHEN THE CO ALARM SOUNDS
WARNING!
Actuation of your CO alarm
indicates the presence of carbon
monoxide (CO) which can KILL
YOU.lf alarm signal sounds:
1)Operate reset/silence button;
2)Call your emergency services
(Telephone Number
[fire department or 911];
3) lmmediately move to fresh air -
outdoors or by an open
door/window. Do a head count to
check that all persons are
accounted for. Do not reenter the
premises nor move away from the
open door/window until the
emergency services responders
have arrived, the premises have
been aired out, and your alarm
remains in its normal condition.
)
- 16 -

4)After following steps 1 - 3, if your
alarm reactivates within a 24 hour
period, repeat steps 1 - 3 and call a
qualified appliance technician
(Telephone Number ) to
investigate for sources of CO from
fuel burning equipment and
appliances, and inspect for proper
oper ation of this equipment. lf
problems are identified during this
inspection have the equipment
serviced immediately.Note any
combustion equipment not inspected
by the technician and consult the
manufacturers' instructions, or
contact the manufacturers directly,
for more information about Co safety
and this equipment. Make sure that
motor vehicles are not, and have not
been, operating in an attached
garage or adjacent to the residence.
- 17 -

12.LIMITATIONS OF SMOKE AND CO ALARM
Smoke and CO alarms have played a key role in reducing
deaths resulting from home fires worldwide. However, like any
warning device, smoke and cO alarms can only work if they
are properly located, installed , and maintained , and if smok
ereaches the Alarms.They are not foolproof.
12.1 Smoke and CO alarms may not wake everyone up.
Sleeping children or others are less likely to be awakened
by the sound of a smoke/carbon monoxide alarm, or a
family member with a baby or mobility problems needs
someone to help them escape.Practice your escape plan
every year. It is recommended that you do it while your
family is asleep.Always let your child master the escape
plan and practice before the fire drill at night.
12.2 Smoke and CO alarms cannot work without power.
Battery operated units cannot work if the batteries are
dead.Smoke alarms must be tested regularly to make
sure the battery and the alarm circuits are in good
operating condition.
12.3 Smoke alarms cannot provide an alarm if smoke does
not reach the alarm. Smoke from fires in chimneys or
walls, on roofs, or on the other side of closed doors may
not reach bedroom or sleeping area-especially if bedroom
or sleeping area doors are closed at night and in the
hallway between them.
12.4 smoke and CO alarms may not have time to alarm
before the fire itself causes damage, injury, or death, since
smoke from some fires may not reach the unit immediately.
Examples of this include persons smoking in bed, children
playing with matches, or fires caused by violent explosions
resulting from escaping gas.
12.5 smoke and CO alarms are not foolproof.Like any
- 18 -

WARNING!
electronic device, smoke and CO alarms are made of
components that can wear out or fail at any time. You
must test the unit weekly to ensure your continued
protection. smoke and CO alarms cannot prevent or
extinguish fires.They are not a substitute for property or
life insurance.
12.6 smoke and cO alarms have a limited life,The unit
should be replaced immediately if it is not operating
properly. You should always replace a smoke and CO
alarm after 10 years from date of purchase. Write the
purchase date on the space provided on back of unit.
●Smoke alarms are not to be used with smoke alarm guards.
The smoke alarm and the CO alarm are two separatesensors.
●The CO alarm not designed to detect fire or any other gas,
and it is only designed to detect carbon monoxide gas.
The smoke alarm will only indicate the presence of smok
ethat reaches the sensor,and it is not designed to sense
gas, heat or flames.
This product is intended for use in ordinary indoor
locations of family living units. It is not designed to
measure compliance with Occupational Safety and
Health Administration (OSHA) commercial or
industrial standards.
This alarm will only indicate the presence of carbon
monoxide gas at the sensor. Carbon monoxide gas
may be present in other areas.
WARNING!
- 19 -

13.LIMITED WARRANTY
We warrants to the original consumer purchasere
ach new smoke and cO alarm to be free from
defects in material and workmanship under normal
use and service for a period of ten years from the
date of purchase.This warranty does not cover
damage resulting from accident, misuse or abuse or
lack of reasonable care of the product.This warranty
is in lieu of all other express warranties, obligations
or liabilities.
THE IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE ARE
LIMITED TO APERIOD OF TEN YEARS FOR THE
smoke and CO alarm FROM PURCHASE DATE.
lndividuals with medical problems may consider
using warning devices which provide audible and
visual signals for carbon monoxide concentrations
under 30 ppm.
- 20 -
ANKA Sci-Tech Co.,Ltd.
4th Floor, Building J, No.1, North District,
Shangxue Technology Park, Bantian Street, Longgang District,
Shenzhen, Guangdong, China.
This manual suits for next models
5
Table of contents
Popular Carbon Monoxide Alarm manuals by other brands

Shenzhen Yongchangda Electronics
Shenzhen Yongchangda Electronics OJB-CR701-YZ quick start guide

BRK electronic
BRK electronic CO250LB Specifications

Kidde
Kidde P4010ACLEDSCOCA user guide

Deltronic Security
Deltronic Security CN-1231 owner's manual

First Alert
First Alert CO606 user manual

WOXTER
WOXTER domotify user manual