AP Bio-Dri II User manual

Date: 05-06-16 V1.0 PNEG-1984
Instructions
1004 East Illinois Street • Assumption, IL 62510 • 1-217-226-4421
PNEG-1984
Page 1 of 4
Printed in the U.S.A.
Copyright © 2016 by The GSI Group, LLC
www.gsiag.com CN-324780
Bio-Dri II™ Air Inlet Door
Assembly Instructions
Inlet Door Assembly Instructions
1. Construct frame and rough opening for inlet door. Ensure that the inside surface of both rough
openings is 3'' from the inside corner of the door hinge according to detail. (See Figure 1.)
2. Assemble two (2) hinges (B) to top and bottom of door (A), using bolt (C) and nylock nut (D).
With two (2) persons, lift door and hinges over rough opening on inside of air mixing chamber and
center vertically. Ensure that the corner of the hinges are against the inside corner of the framing as
shown in Figure 1. Secure door and hinges to frame with four (4) lag screws (E) through each of the
four (4) hinges (B) and into the framing.
Figure 1
3. According to Figure 2 on Page 2. Install long diagonal brace (G) to inside of rough opening closest
to hinge. Ensure it is centered vertically within the rough opening and secure with four (4) lag screws
(E) into the framing. Also vertically centered on opposite side of rough opening, install short straight
brace (H) and secure with four (4) lag screws (E) into the framing.
4. Install the tubular brace (J) to the lower hole on the outer face of the short straight brace (H). Rotate
the tubular brace downward to about 45° until the bottom end fits inside the rough opening. Secure
with a lag screw (E) to the framing.
5. Install the bottom anchor plate (I) between diagonal and straight braces, using four (4) bolts (L) and
four (4) nylock nuts (M).
6. Lay linear actuator (F) on top of bottom anchor plate (I) and connect rod end of actuator to pivot hole
in door. Secure rod connection with bolt (N) and nylock nut (D).
7. Lay top anchor plate (I) on top of linear actuator (F), diagonal brace (G) and straight brace (H),
then install long pivot bolt (K) through top anchor plate, actuator and bottom anchor plate. Secure
with nylock nut (D). Align top anchor plate mounting holes with diagonal brace and straight brace.
Secure with four (4) bolts (L) and four (4) nylock nuts (M).
Ref # Part # Description Qty Ref # Part # Description Qty
AAP-5292 Inlet Door 4' x 6' Black 1 D S-8260 Nylock Nut 1/2''-13 ZN Grade 5 2
B AP-5291 Inlet Door Pivot Frame Support - Hinge 4 E S-7308 Lag Screw 3/8'' x 2'' HH ZN 16
CS-7935 Bolt, HHCS 1/2''-13 x 1'' ZN Grade 5 2
Inside corner for
door hinge
3''Critical
3''Critical

Page 2 of 4 PNEG-1984
Bio-Dri II™ Air Inlet Door Assembly Instructions
Inlet Door Assembly Instructions (Continued)
Figure 2
Ref # Part # Description Qty
DS-8260 Nylock Nut 1/2''-13 ZN Grade 5 2
E S-7308 Lag Screw 3/8'' x 2'' HH ZN 9
FAP-5300 Linear Actuator Assembly for Inlet Door 1
G AP-5301 Brace, Diagonal for Linear Actuator 1
HAP-5302 Brace, Straight for Linear Actuator 1
I AP-5303 Plate, Anchor for Linear Actuator 2
JAP-4488-24 Brace for Linear Actuator 1
K S-8232 Bolt, HHCS 1/2''-13 x 4-1/2'' ZN Grade 5 1
LS-4275 Bolt, 5/16''-18 x 3/4'' ZN Grade 5 9
M S-7382 Nylock Nut 5/16''-18 ZN Grade 5 9
NS-7876 Bolt, HHCS 1/2''-13 x 1-3/4'' ZN Grade 5 1
O D03-0177 Rubber Grommet 11/16" I.D. x 1" O.D.
P6 mm Allen Wrench (Not Provided)

PNEG-1984 Page 3 of 4
Bio-Dri II™ Air Inlet Door Assembly Instructions
Inlet Door Adjustment Instructions
1. Prior to adjustments the linear actuator must be wired up tothe PLC panel and capable of operation.
Please refer to Air Inlet Door Actuator wiring diagram. Once wired up, the two (2) dial switches on
the controls on the outside of the PLC panel can be used to operate the linear actuator. One dial
switch is used to go between Auto, Off and Hand (Manual). When in Manual mode, the other dial
switch has two (2) operating positions: Purge and Re-Cycle. When in Purge, the linear actuator will
attempt to extend a full 24'' until the internal limit switch shuts it off. When in Re-Cycle, the linear
actuator will attempt to retract until the external limit switch shown in Figure 3 on Page 4, shuts
it off.
2. Change the switch position on the outside of the PLC panel to manual Mode/Purge and let the
linear actuator extend the full 24'' until the unit comes to a stop. There will probably be a 1'' to 2''
gap remaining between the door and the framing in the Purge position. Remove the eight (8) plastic
plugson topofthe linearactuatortoprovide accesstotheallen headscrewsunderneath.Loosen all
eight(8) allenhead screwson topof theactuator with a 6mm allen wrench(P) not provided.Loosen
each screw approximately 5 complete turns.
3. Rotate the door counterclockwise slightly, until the 1'' to 2'' gap between the door and the framing
in the Purge position is closed up. As the door is rotated, the linear actuator will slide inside the
housing to the correct adjustment position. Tighten the eight (8) allen head screws securely.
Replace the eight (8) plastic plugs in the top of the linear actuator.
4. Refer to Figure 3 on Page 4. Change the switch position on the outside of the PLC panel to
Manual/Re-Cycle and let the linear actuator retract until the external limit switch (A) strikes the
actuator bracket (D) and the unit comes to a stop. There will probably be a 1'' to 2'' gap remaining
between the door and the framing in the Re-Cycle position. Change the switch position on the
outside of the PLC panel from manual to off.
5. Using a 1/2'' Wrench (G), loosen the nylock nuts (F) on the U-Bolt (E) and slide the actuator
bracket(D)forward towardstherodend ofthelinearactuator approximately1/4''.Tightenthe nylock
nuts (F) on the U-Bolt (E). Change the switch position on the outside of the PLC panel from Off to
Manual. The linear actuator will retract slightly until the external limit switch causes it to shut off.
Ensure that the 1'' to 2'' gapbetween the door and the framing in the Re-Cycle position is closed up.
If not, repeat this step until the door gap is closed.
6. Change the dial switches on the outside of the PLC panel to Auto/Re-Cycle. The inlet door is now
ready for normal operation. In normal operation, when the Bio-Dri II™ is not running, the inlet door
should remain in Re-Cycle position in order to keep birds and debris from entering the air mixing
chamber. When the Bio-Dri II™ is in Pre-Bake mode, Bake mode or Post Bake mode, the inlet door
should be in Re-Cycle position in order to allow the hot air to Re-Cycle through the system. The only
time the inlet door should be in Purge position, is during the 8 minute purge time at the end of the
cycle, in order to clear out deadly gas fumes and quickly cool the room down, prior to safe entry.

Page 4 of 4 PNEG-1984
Bio-Dri II™ Air Inlet Door Assembly Instructions
Inlet Door Adjustment Instructions (Continued)
Figure 3
Ref # Part # Description Qty
ATD-101463 Limit Switch 1
B AP-5388 Bracket, Limit Switch Mounting 1
CS-10171 U-Bolt, 5/16''-18 for 1-1/4" Pipe ZN 1
D AP-5389 Actuator Bracket 1
E326-1047-9 U-Bolt, 5/16''-18 x 1-3/8'' x 2-3/1'' 1
F S-7382 Nylock Nut 5/16''-18 ZN Grade 5 4
G1/2'' Wrench (Not Provided)
Table of contents
Other AP Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

IRO
IRO IWF 2231-B operating instructions

Emerson
Emerson Penberthy Installation, operation and maintenance instructions

Endress+Hauser
Endress+Hauser Prothermo NMT 539 operating instructions

Siemens
Siemens SINAMICS G120P operating instructions

ferrotec
ferrotec Temescal FC-4400 FACILITY AND INSTALLATION GUIDE

Bosch
Bosch Rexroth VT-MSPA2-2X/ A5/1A0/000 manual