Apollo 29600-239 User manual

PP2184/2004/Issue 1 PP2184/2004/Issue 1
FIRE DETECTORS LIMITED
Apollo DIN-Rail Enclosure
When using the Apollo DIN-Rail Enclosure (part nos 29600-239, 29000-240)
in intrinsically safe systems, please ensure the following:
It is important that segregation be provided between the IS and non-
IS circuits. A distance of at least 50mm must be preserved between
live conducting parts of IS and other circuits.
A warning label should be attached to the box cover to indicate that IS
circuits are present. This label is provided inside the enclosure.
The enclosure must always be installed inside the safe area. Never install
this enclosure in the hazardous area.
Figures 1, 2 and 3 show how to connect a conventional and an addressable
IS circuit safely using the Apollo enclosure.
PP2184/2004/Issue 1
FIRE DETECTORS LIMITED
Apollo DIN-Rail Enclosure
When using the Apollo DIN-Rail Enclosure (part nos 29600-239, 29000-240)
in intrinsically safe systems, please ensure the following:
It is important that segregation be provided between the IS and non-
IS circuits. A distance of at least 50mm must be preserved between
live conducting parts of IS and other circuits.
A warning label should be attached to the box cover to indicate that IS
circuits are present. This label is provided inside the enclosure.
The enclosure must always be installed inside the safe area. Never install
this enclosure in the hazardous area.
Figures 1, 2 and 3 show how to connect a conventional and an addressable
IS circuit safely using the Apollo enclosure.
PP2184/2004/Issue 1
FIRE DETECTORS LIMITED
Apollo DIN-Rail Enclosure
When using the Apollo DIN-Rail Enclosure (part nos 29600-239, 29000-240)
in intrinsically safe systems, please ensure the following:
It is important that segregation be provided between the IS and non-
IS circuits. A distance of at least 50mm must be preserved between
live conducting parts of IS and other circuits.
A warning label should be attached to the box cover to indicate that IS
circuits are present. This label is provided inside the enclosure.
The enclosure must always be installed inside the safe area. Never install
this enclosure in the hazardous area.
Figures 1, 2 and 3 show how to connect a conventional and an addressable
IS circuit safely using the Apollo enclosure.
FIRE DETECTORS LIMITED
Apollo DIN-Rail Enclosure
When using the Apollo DIN-Rail Enclosure (part nos 29600-239, 29000-240)
in intrinsically safe (IS) systems, please ensure the following:
It is important that segregation be provided between the IS and non-
IS circuits. A distance of at least 50mm must be preserved between
live conducting parts of IS and other circuits.
A warning label should be attached to the box cover to indicate that IS
circuits are present. This label is provided inside the enclosure.
The enclosure must always be installed inside the safe area. Never install
this enclosure in the hazardous area.
Figures 1, 2 and 3 show how to connect a conventional and an addressable
IS circuit safely using the Apollo enclosure.
! !
! !
Barrier Hazardous
Area
DIN-Rail
Safe Area
50mm
© Apollo Fire Detectors Limited/J.Roughton/2004
Fig 1 Conventional IS configuration
Barrier Hazardous
Area
DIN-Rail
Safe Area
50mm
© Apollo Fire Detectors Limited/J.Roughton/2004
Fig 1 Conventional IS configuration
Barrier Hazardous
Area
DIN-Rail
Safe Area
50mm
© Apollo Fire Detectors Limited/J.Roughton/2004
Fig 1 Conventional IS configuration
Barrier Hazardous
Area
DIN-Rail
Safe Area
50mm
© Apollo Fire Detectors Limited/J.Roughton/2004
Fig 1 Conventional IS configuration

For further information relating to Apollo IS products, please refer to Apollo
publications PP2028 (Series 60) and PP1095 (XP95).
Apollo Fire Detectors Ltd, 36 Brookside Road, Havant, Hants, PO9 1JR, England
Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754
Email: techsales@apollo-fire.co.uk Website:www.apollo-fire.co.uk
©Apollo Fire Detectors Ltd 2004
–
123
456
78 9
1110 12
Galvanic
Barrier
Protocol
Translator
Hazardous
Area
DIN-Rail
+
Output
Loop
50mm
(Minimum)
Safe Area
Part no: 29600-098
Part no: 55000-855
–
+
–
+
–
+
©
Apollo Fire Detectors Limited/J.Roughton/2004
Fig 2 Analogue addressable IS configuration for 29600-239
123
456
78 9
1110 12
Galvanic
Barrier
Protocol
Translator
Hazardous
Area
DIN-Rail
–
+
50mm
(Minimum)
Safe Area
Part no: 29600-098
Part no: 55000-856
–
+
–
+
–
+
123
456
78 9
1110 12
Galvanic
Barrier
+–
–
+–
+
©
Apollo Fire Detectors Limited/J.Roughton/2004
Fig 3 Analogue addressable IS configuration for 29600-240
For further information relating to Apollo IS products, please refer to Apollo
publications PP2028 (Series 60) and PP1095 (XP95).
–
123
456
78 9
1110 12
Galvanic
Barrier
Protocol
Translator
Hazardous
Area
DIN-Rail
+
Output
Loop
50mm
(Minimum)
Safe Area
Part no: 29600-098
Part no: 55000-855
–
+
–
+
–
+
©
Apollo Fire Detectors Limited/J.Roughton/2004
Fig 2 Analogue addressable IS configuration for 29600-239
Apollo Fire Detectors Ltd, 36 Brookside Road, Havant, Hants, PO9 1JR, England
Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754
Email: techsales@apollo-fire.co.uk Website:www.apollo-fire.co.uk
©Apollo Fire Detectors Ltd 2004
Apollo Fire Detectors Ltd, 36 Brookside Road, Havant, Hants, PO9 1JR, England
Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754
Email: techsales@apollo-fire.co.uk Website:www.apollo-fire.co.uk
©Apollo Fire Detectors Ltd 2004
123
456
78 9
1110 12
Galvanic
Barrier
Protocol
Translator
Hazardous
Area
DIN-Rail
–
+
50mm
(Minimum)
Safe Area
Part no: 29600-098
Part no: 55000-856
–
+
–
+
–
+
123
456
78 9
1110 12
Galvanic
Barrier
+–
–
+–
+
©
Apollo Fire Detectors Limited/J.Roughton/2004
Fig 3 Analogue addressable IS configuration for 29600-240
For further information relating to Apollo IS products, please refer to Apollo
publications PP2028 (Series 60) and PP1095 (XP95).
For further information relating to Apollo IS products, please refer to Apollo
publications PP2028 (Series 60) and PP1095 (XP95).
Apollo Fire Detectors Ltd, 36 Brookside Road, Havant, Hants, PO9 1JR, England
Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754
Email: techsales@apollo-fire.co.uk Website:www.apollo-fire.co.uk
©Apollo Fire Detectors Ltd 2004
–
123
456
78 9
1110 12
Galvanic
Barrier
Protocol
Translator
Hazardous
Area
DIN-Rail
+
Output
Loop
50mm
(Minimum)
Safe Area
Part no: 29600-098
Part no: 55000-855
–
+
–
+
–
+
©
Apollo Fire Detectors Limited/J.Roughton/2004
Fig 2 Analogue addressable IS configuration for 29600-239
123
456
78 9
1110 12
Galvanic
Barrier
Protocol
Translator
Hazardous
Area
DIN-Rail
–
+
50mm
(Minimum)
Safe Area
Part no: 29600-098
Part no: 55000-856
–
+
–
+
–
+
123
456
78 9
1110 12
Galvanic
Barrier
+–
–
+–
+
©
Apollo Fire Detectors Limited/J.Roughton/2004
Fig 3 Analogue addressable IS configuration for 29600-240
–
123
456
78 9
1110 12
Galvanic
Barrier
Protocol
Translator
Hazardous
Area
DIN-Rail
+
Output
Loop
50mm
(Minimum)
Safe Area
Part no: 29600-098
Part no: 55000-855
–
+
–
+
–
+
©
Apollo Fire Detectors Limited/J.Roughton/2004
Fig 2 Analogue addressable IS configuration for 29600-239
123
456
78 9
1110 12
Galvanic
Barrier
Protocol
Translator
Hazardous
Area
DIN-Rail
–
+
50mm
(Minimum)
Safe Area
Part no: 29600-098
Part no: 55000-856
–
+
–
+
–
+
123
456
78 9
1110 12
Galvanic
Barrier
+–
–
+–
+
©
Apollo Fire Detectors Limited/J.Roughton/2004
Fig 3 Analogue addressable IS configuration for 29600-240
This manual suits for next models
1
Table of contents
Other Apollo Enclosure manuals
Popular Enclosure manuals by other brands

Ravcore
Ravcore GOLIATH Instructions for use

Rockford Fosgate
Rockford Fosgate Element Ready RFX317-FSE Installation & operation

MGF
MGF MINI BOX KIT Operating & maintenance instruction manual

Positron
Positron BRX-XLR-24 quick start guide

EMC
EMC CX200-Series Hardware reference

Vantec
Vantec Vantec HX user manual