IN+
COM–
LED–
OUT+
OUT +
IN+ Direction of LED indicated by
mark on outside of moulding
LED –
Terminal 4, Screen
(Functional Earth) Snip along marked lines and
remove this part to lock the
detector to the base
IN & OUT–
Fig.5 Base wiring iagram
Fig.4 TimeSaver IS Base®
©Apollo Fire Detectors Limited 2004–2006/JDR/RHD
fitting rbis detect r heads
When the bases have been installed and the system
wiring tested, the detector circuits can be populated.
Two methods are suggested:
1. Apply power and fit the detectors one by one,
starting at the base nearest the panel and working
towards the end of the circuit. As each detector is
powered up it will enter ‘StartUp’ and flash red (see
Table 1 on page 14). If the LED does not flash,
check the wiring polarity on the base and ensure
there is power across IN+ and COM–. If the LED is
flashing yellow the detector is not operating correctly
and may require maintenance or replacing (see
DirtAlert and SensAlert®below and the section
‘Servicing’ on page 18).
2. Fit all detectors to the circuit, apply power and
check detectors by observing the LED status of each
device. The StartUp feature lasts for 4 minutes so it
may be necessary to reset or de-power the circuit to
allow all detectors to be observed. The LED status is
the same as method 1.
Screen
(Functional
Earth)
LED –
COM –
IN +
OUT +
1
23
4
LED –
COM –
IN +
OUT +
1
23
4
LED –
COM –
IN +
OUT +
1
23
4
Safety
barrier
Control
panel
Note: the earth terminal in the base is provided for convenience where
continuity of a cable sheath or similar is required. It is not necessary for the
correct operation of the detector nor is it provided as a termination point for a
safety earth.
If screened cable is used screen continuity should be maintained and the
screen should be earthed only at one point. The earthing point should
preferably be close to the safety barrier.
The system complies with the requirements of the CPD only if wired using
screened cable. For details of cable connections see BSEN60079–14, section
12.2.2.
–
+
Safety
barrier
© Apollo Fire Detectors Limited 2004–2006/JDR/RHD
Fig.6 3 bases wire with a common LED
Screen
(Functional
Earth)
LED –
COM –
IN +
OUT +
1
23
4
LED –
COM –
IN +
OUT +
1
23
4
LED –
COM –
IN +
OUT +
1
23
4
Safety
barrier
Control
panel
Note: the earth terminal in the base is provided for convenience where
continuity of a cable sheath or similar is required. It is not necessary for the
correct operation of the detector nor is it provided as a termination point for a
safety earth.
If screened cable is used screen continuity should be maintained and the
screen should be earthed only at one point. The earthing point should
preferably be close to the safety barrier.
The system complies with the requirements of the CPD only if wired using
screened cable. For details of cable connections see BSEN60079–14, section
12.2.2.
–
+
Safety
barrier
© Apollo Fire Detectors Limited 2004–2006/JDR/RHD