Armstrong Air BCE7E Series User manual

507838-01 Issue 1813 Page 1 of 19
Save these instructions for future reference
INSTALLATION INSTRUCTIONS
BCE7E Series Air Handler
(P) 507838-01
*P507838-01*
This manual must be left with the homeowner for future reference.
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in
manuals, be alert to the potential for personal injury or death.
Table of Contents
General Information.....................................................4
Shipping and Packing List ...........................................4
Requirements ..............................................................4
Installing the Unit.........................................................4
Brazing Connections ...................................................7
Installing the Condensate Drain ..................................8
Inspecting and Replacing Filters .................................9
Sealing the Unit ...........................................................9
Measuring Static Pressure ..........................................9
Adjusting Blower Speed ............................................10
Blower Data...............................................................11
Making Electrical Connections ..................................13
Homeowner Maintenance..........................................16
Professional Maintenance .........................................16
Repairing or Replacing Cabinet Insulation ................16
Check-out Procedures...............................................17
Use of Air Handler During Construction.....................17
NOTE: Special procedures are required for cleaning the all-aluminum coil in this unit. See Page 16 in this instruction
for information.
IMPORTANT INFORMATION FOR INSTALLER
D
CHECK FOR AND REMOVE THESE ITEMS BEFORE OPERATING UNIT.
D
DRIP SHIELD. (USED FOR -060 UNITS, HORIZONTAL
APPLICATIONS ONLY.) (SEE PAGES 5-6.) SHOWN
INSTALLED ON DRAIN PAN IN -060 UNIT.
REFRIGERANT LINE PLUGS
(SEE PAGE 6)
HORIZONTAL DRAIN PAN
(SEE PAGES 5-6)
TOP CAP SHIPPING
BRACKET (REPLACE
SCREWS IN TOP CAP
AFTER REMOVAL)
BLOWER HOUSING
SUPPORT PAD
215 Metropolitan Drive
West Columbia, SC 29170

507838-01Issue 1813Page 2 of 19
BCE7E Common Dimensions - inches (mm)
Dim. -018/-024 -030/-036 -042/-048 -060
A49-1/4 (1251) 51 (1295) 58-1/2 (1486) 62-1/2 (1588)
B21-1/4 (540) 21-1/4 (540) 21-1/4 (540) 21-1/4 (540)
C20-5/8 (524) 22-5/8 (575) 24-5/8 (625) 24-5/8 (625)
D19-3/4 (502) 19-3/4 (502) 19-3/4 (502) 19-3/4 (502)
E19 (483) 21 (533) 23 (584) 23 (584)
F20 (508) 20 (508) 20 (508) 20 (508)
G24-5/8 (625) 26-3/8 (670) 27-7/8 (708) 27-7/8 (708)
H24-5/8 (625) 24-5/8 (625) 30-5/8 (778) 34-5/8 (879)
BCE7E Upow and Downow Unit Dimensions - inches (mm)
Downflow Position
Upflow Position
OPTIONAL
ELECTRIC HEAT
(FIELD-INSTALLED)
AIR
FLOW
LIQUID
LINE
SUCTION
LINE
SUPPLY AIR
OPENING
RETURN AIR
FILTER
LOW VOLTAGE
INLETS (TOP AND
RIGHT SIDE)
RETURN AIR
TOP VIEW
FRONT VIEW SIDE VIEW
BLOWER
PIPING PLATE DETAIL
(FOR UP-FLOW AND DOWN-FLOW POSITIONS)
A
CB
11‐1/16 (281)
D
FE
LIQUID LINE
SUCTION LINE
CONDENSATE DRAINS
(2) (HORIZONTAL)
COIL
3/4 (19)
3/4 (19)
5/8 (16) )52(1)61(8/5
5/8 (16)
1‐3/4 (44)
2
(51)
1‐1/8 (29) 4‐3/8 (111)
2‐3/4
(70)
5‐3/8
(137)
3‐1/2 (89)
OPTIONAL
ELECTRIC HEAT
(FIELD-INSTALLED) AIR FLOW
LIQUID
LINE
SUCTION
LINE
Return
Air Opening
SUPPLY
AIR
FILTER
SUPPLY AIR
TOP VIEW
FRONT VIEW
SIDE VIEW
BLOWER
A
B
C
11‐1/16 (281)
F
D
E
COIL
5/8 (16)
5/8 (16)
5/8 (16)
5/8 (16)
5/8 (16)
LOW VOLTAGE
(RIGHT SIDE)
LINE VOLTAGE
(LEFT SIDE)
1 (25)
CONDENSATE DRAINS
(2) (UP-FLOW AND
DOWN-FLOW)
FILTER ACCESS
FILTER ACCESS
H
G
H
G
LINE VOLTAGE
INLETS (TOP
AND LEFT SIDE)
5/8 (16)
5/8 (16)

507838-01 Issue 1813 Page 3 of 19
BCE7E Horizontal Left- and Right-Hand Discharge Unit Dimensions - inches (mm)
LIQUID
LINE
SUCTION
LINE
Supply
Air
Opening
FILTER
LOW VOLTAGE
INLETS (BOTTOM
AND RIGHT
SIDE)
TOP VIEW
FRONT VIEW
BLOWER
H
B
C
D
LIQUID
LINE
SUCTION
LINE
CONDENSATE
DRAINS (2)
(UP-FLOW
AND
DOWN-FLOW)
CONDENSATE
DRAINS (2)
(HORIZONTAL)
Coil
3/4 (19)
3/4 (19)
1‐1/2
(38)
1‐3/4
(44)
5‐3/4
(46)
2
(51)
1‐1/8
(29)
RETURN AIR
OPENING
F
E
5/8 (16)
5/8 (16)
5/8 (16)
END VIEW
AIR
FLOW
OPTIONAL ELECTRIC
HEAT (FIELD-INSTALLED)
11‐1/16
(281)
LINE VOLTAGE
INLETS (TOP
AND RIGHT
SIDE)
5‐3/8
(137)
4‐3/8
(111)
LIQUID
LINE
SUCTION
LINE
Supply
Air Opening
FILTER
LOW VOLTAGE
INLETS (TOP AND
LEFT SIDE)
END VIEW
BLOWER
B
C
D
Coil
3/4 (19)
3/4 (19)
3/4 (19)
Return
Air Opening
F
E
5/8 (16)
5/8 (16)
5/8 (16)
END VIEW
Air Flow
OPTIONAL ELECTRIC
HEAT (FIELD INSTALLED)
LINE VOLTAGE INLETS
(BOTTOM AND LEFT SIDE)
Horizontal Position
(Right‐Hand Air
Discharge)
FILTER ACCESS
FILTER ACCESS
5‐3/4
(146)
1‐1/2 (38)
1‐3/4
(44)
CONDENSATE DRAINS (2)
(HORIZONTAL)
A
5/8 (16)
G
H
A
5/8 (16)
G
1 (25)
1 (25)
11‐1/16
(281)
PIPING PLATE
DETAIL
LIQUID
LINE
SUCTION LINE
2
(51)
1‐1/8
(29)
5‐3/8
(137)
4‐3/8
(111)
PIPING PLATE
DETAIL
Horizontal Position
(Left‐Hand Air
Discharge)
TOP VIEW
FRONT VIEW
3/4 (19)
END VIEW
FOR DIMENSIONS “A” THROUGH
“H”, SEE CHART ON PAGE 2.

507838-01Issue 1813Page 4 of 19
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer or
equivalent, service agency, or the gas supplier.
WARNING
The Clean Air Act of 1990 bans the intentional venting
of refrigerant (CFCs, HCFCs and HFCs) as of July
1, 1992. Approved methods of recovery, recycling or
reclaiming must be followed. Fines and/or incarceration
may be levied for noncompliance.
IMPORTANT
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves
and protective clothing.
CAUTION
General Information
The BCE7E series air handler with all-aluminum coil is
designed for installation with optional eld-installed electric
heat and a matching HFC-410A outdoor unit.
This instruction is intended as a general guide and does
not supersede local or national codes in any way. Consult
authorities having jurisdiction before installation.
Shipping and Packing List
Package 1 of 1 contains:
1 – Assembled air handler unit
1 – Horizontal drip shield (BCE7E-060 only)
1 – Pipe nipple (Sch 80, 3/4” I.D. x 5”)
1 – Warranty card
NOTE: For downow applications, order kit number
83M57.
Check the air handler for shipping damage; if found,
immediately contact the last carrier.
Requirements
This unit must be matched with an indoor coil as
specied in the product specication sheets. Coils
previously charged with HCFC-22 must be ushed.
IMPORTANT
In addition to conforming to manufacturer’s installation
instructions and local municipal building codes, installation
of air handler units (with or without optional electric heat),
shall conform with the following National Fire Protection
Association (NFPA) standards:
• NFPA No. 90A - Standard for Installation of Air
Conditioning and Ventilation Systems
• NFPA No. 90B - Standard for Installation of Residence
Type Warm Air Heating and Air Conditioning Systems
This unit is approved for installation clearance to
combustible material as stated on the unit rating plate.
Accessibility and service clearances must take precedence
over combustible material clearances.
Installing the Unit
These units are factory-congured for upow and
horizontal right-hand discharge installation. For downow
or horizontal left-hand discharge, certain eld modications
are required.
Disassemble/Reassemble Air Handler Units
The air handler units consists of two factory-assembled
sections. It may be necessary to disassemble the sections
when positioning the unit for installation.
To disassemble:
1. Remove access panels.
2. Remove both blower and coil assemblies. This will
lighten the cabinet for lifting.
3. Remove one screw from the left and right posts inside
the unit. Remove one screw from each side on the
back of the unit. Unit sections will now separate.
To reassemble:
1. Align cabinet sections together.
2. Reinstall screws.
3. Replace blower and coil assemblies.
4. Replace access panel.

507838-01 Issue 1813 Page 5 of 19
Upow Application
Use the following procedures to congure the unit for
upow operations:
1. Remove access panels.
2. Remove and discard the horizontal drip shield (-060
model, used only on horizontal applications) and
the corrugated padding between the blower and coil
assembly.
3. The horizontal drain pan must be removed when the
coil blower is installed in the upow position. Removing
the horizontal drain pain will allow proper air ow and
increased efciency.
4. After removing the horizontal drain pan, place the
unit in the desired location. Set unit so that it is level.
Connect return and supply air plenums as required
using sheet metal screws as illustrated in Figure 1.
5. Install units that have no return air plenum on a stand
that is at least 14” from the oor to allow for proper air
return. An optional upow unit stand is listed in Table
1.
Model Kit Number
All Sizes 45K32
Table 1. Optional Side-Return Unit Stand
(Upow Only)
HORIZONTAL DRAIN PAN
(MUST BE REMOVED)
UP-FLOW /
DOWN-FLOW
DRAIN PAN
Figure 1. Upow Conguration
Horizontal Right-Hand Discharge Application
Use the following procedures to congure the unit for
horizontal right-hand discharge operations:
NOTE: For horizontal applications, a secondary drain pan
is recommended. Refer to local codes.
1. Before operating the unit, remove access panels
and the horizontal drip shield (-060 model) and the
corrugated padding between the blower and coil
assembly. Discard the corrugated padding.
2. Install the horizontal shield on the front edge of the
horizontal drain pan as illustrated in Figure 2.
3. No further adjustment is necessary. Set unit so that it
is sloped 1/4” towards the drain pan end of the unit.
4. If the unit is suspended, the entire length of the cabinet
must be supported. If you use a chain or strap, use a
piece of angle iron or sheet metal attached to the unit
(either above or below) to support the length of the
cabinet. Use securing screws no longer than 1/2” to
avoid damaging the coil or lter as illustrated in Figure
3. Use sheet metal screws to connect the return and
supply air plenums as required.
UP-FLOW / DOWN-FLOW
DRAIN PAN
HORIZONTAL DRIP SHIELD (-060 MODELS)
DOWN-FLOW RAIL
HORIZONTAL DRAIN
PAN
NO ADJUSTMENT IS NECESSARY
Figure 2. Right-Hand Discharge Conguration
Horizontal Right-Hand Discharge Application in
High-Humidity Areas
For horizontal applications in high humidity areas, remove
the downow rail closest to the drain pan.
To remove rail:
1. Remove the screws from the rail at the back of unit
and at the cabinet support rail.
2. Remove the downow rail then replace screws.
3. Seal around the exiting drain pipe, liquid line, and
suction line to prevent humid air from inltrating into
the unit.
FRONT VIEW END VIEW
ANGLE IRON OR
SHEET METAL
ELECTRICAL INLET CLEARANCE 4"
(102 mm)
1/2" SCREWS MAXIMUM
Figure 3. Suspending Horizontal Unit

507838-01Issue 1813Page 6 of 19
When removing the coil, there is possible danger of
equipment damage and personal injury. Be careful
when removing the coil assembly from a unit installed
in right- or left-hand applications. The coil may tip into
the drain pan once it is clear of the cabinet. Support the
coil when removing it.
IMPORTANT
Horizontal Left-Hand Discharge Application
NOTE: For horizontal applications, a secondary drain pan
is recommended. Refer to local codes.
90º
BEND
CABINET
SUPPORT
COIL SHOWN IN UPFLOW POSITION FOR EASY CONVERSION
TOP CAP SCREWS
DRAIN PAN
REINSTALLED
HERE
DRIP
SHIELD
DRAIN PAN
SHIPPING
LOCATION
TOP CAP ROTATED TO
CORRECT POSITION
———— DRAIN PLUGS ————
REINSTALLED HERE REMOVED FROM HERE
BACK COIL END SEAL
TOP
CAP
90º
BEND
ALIGN HOLES WITH
HOLES IN COIL END
PLATE. STARTING WITH
THE ROUND HOLES ON
THIS END.
Figure 4. Field Modication for Left-Hand Discharge
Use the following procedures to congure the unit for
horizontal left-hand discharge operations:
1. Before operating the unit, remove access panels
and the horizontal drip shield (-060 model) and the
corrugated padding between the blower and coil
assembly. Discard the corrugated padding.
2. Pull the coil assembly from unit. Pull off the horizontal
drain pan.
3. Remove the drain plugs from back drain holes on
horizontal drain pan and reinstall them on front holes.
After removal of drain pan plug(s), check drain hole(s)
to verify that drain opening is fully open and free of any
debris. Also check to make sure that no debris has
fallen into the drain pan during installation that may plug
up the drain opening.
IMPORTANT
4. Rotate drain pan 180º front-to-back and install it on the
opposite side of the coil.
5. Remove screws from top cap. Remove horizontal drip
shield screw located in the center of the back coil end
seal as illustrated in Figure 4.
6. Rotate horizontal drip shield 180º front-to-back.
7. Remove plastic plug from left hole on coil front end seal
and reinstall plug in back hole. Reinstall horizontal drip
shield screw in front coil end seal. Drip shield should
drain downward into horizontal drain pan inside coil.
HORIZONTAL DRIP SHIELD (-060 MODEL)
DOWN-FLOW RAIL FRONT EDGE OF HORIZONTAL
DRAIN PAN
Figure 5. Left-Hand Discharge Conguration
8. Rotate top cap 180º front-to-back and align with
unused screw holes. Holes must align with front and
back coil end plates. The top cap has a 45º bend on
one side and a 90º bend on the other. The 90º bend
must be on the same side as the horizontal drain pan
as illustrated in Figure 4.
NOTE: Be very careful when reinstalling the screws
into the coil end plate engaging holes. Misaligned
screws may damage the coil.
9. From the upow position, ip cabinet 90º to the left
and set into place. Replace blower assembly. Secure
coil in place by bending down the tab on the cabinet
support rail as illustrated in Figure 4 and Figure 5.
10. Install the horizontal shield (-060 model only) on the
front edge of the horizontal drain pan as illustrated in
Figure 5.
NOTE: For horizontal applications in high humidity
areas, remove the downow rail closest to the drain
pan. To remove rail, remove screw from rail at back
of unit and at cabinet support rail. Remove downow
rail then replace screws. Also, seal around the exiting
drain pipe, liquid and suction lines to prevent inltration
of humid air.

507838-01 Issue 1813 Page 7 of 19
11. Knock out drain seal plate from access door. Secure
plate to cabinet front ange with screw provided.
12. Flip access door and replace it on the unit.
13. Set unit so that it is sloped 1/4ʺ toward the drain pan
end of the unit. Connect return and supply air plenums
as required using sheet metal screws.
14. If suspending the unit, it must be supported along the
entire length of the cabinet. If using chain or strap,
use a piece of angle iron or sheet metal attached to
the unit (either above or below) so that the full length
of the cabinet is supported. Use securing screws no
longer than 1/2ʺ to avoid damage to coil or lter, as
illustrated in Figure 3. Connect return and supply air
plenums as required using sheet metal screws.
Downow Application
NOTE: If downow application is required, separately
order kit number 83M57 and install per kit’s instructions.
Also use metal or class I supply and return air plenums.
Use the installation instruction provided with the downow
kit.
If electric heat section with circuit breakers (AEHK) is
installed in a BCE7E unit in a downow application, the
circuit breakers must be rotated 180° to the UP position.
See AEHK installation instructions for more details.
IMPORTANT
Brazing Connections
To prevent the build-up of high levels of nitrogen when
purging, it must be done in a well-ventilated area.
Purge low-pressure nitrogen (1 to 2 psig) through
the refrigerant piping during brazing. This will help to
prevent oxidation and the introduction of moisture into
the system.
IMPORTANT
All coils are equipped with a factory-installed, internally
mounted check/expansion valve.
Model Liquid
Line
Vapor
Line Line Sets
-018
-024
-030
-036 3/8ʺ
(10mm)
3/4ʺ
(19mm) L15 line set sizes are
dependant on unit match-
up.
-042
-048 7/8”
(22mm)
-060 Field fabricated
Table 2. Refrigerant Line Sizes
Danger of explosion!
Can cause equipment damage, injury, or
death.
When using a high pressure gas such as
dry nitrogen to pressurize a refrigeration or
air conditioning system, use a regulator that
can control the pressure down to 1 or 2 psig
(6.9 to 13.8 kPa).
IMPORTANT
AIR HANDLER UNIT
SUCTION LINE
LIQUID LINE
Figure 6. Brazing Connections
NOTE: BCE7E series air handlers use nitrogen or dry
air as a holding charge. If there is no pressure when the
rubber plugs are removed, check the coil for leaks before
installing. After installation, pull a vacuum on the line set
and coil before releasing the unit charge into the system.
NOTE: See outdoor unit instructions on how to ow
nitrogen through line sets.
1. Remove access panel.
2. Remove the refrigerant line caps from the refrigerant
lines.
3. Use a wet rag to protect TXV sensing bulb (or remove
it) when brazing suction line connections.

507838-01Issue 1813Page 8 of 19
4. Place a wet rag against piping plate and around the
suction line connection. The wet rag must be in place
to guard against damage to the paint.
5. With the wet rag in place, position a eld provided
elbow tting to the air handler’s suction line and line
set. Start nitrogen ow before brazing.
6. After the procedure is completed then remove the wet
rag.
7. Place wet rag against piping plate and around the
liquid line connection. Position liquid line elbow to air
handler’s suction line and to line set. Start nitrogen
ow and begin brazing both connections and after
procedure is completed then remove both wet rags.
8. Refer to instructions provided with outdoor unit for leak
testing, evacuating and charging procedures.
9. Install access panel.
Installing the Condensate Drain
Main Drain
Connect the main drain and route downward to drain line
or sump. Do not connect drain to a closed waste system.
See Figure 7 for typical drain trap conguration.
Overow Drain
It is recommended that the overow drain is connected to
an overow drain line for all units. If overow drain is not
connected, it must be plugged with provided cap.
For downow orientation, the overow drain MUST be
connected and routed to a overow drain line. See Figure
8 for main and overow drain locations based on coil
orientation.
ABOVE
FINISHED
SPACE?
OVERFLOW DRAIN LINE
ALWAYS RUN AN OVERFLOW DRAIN LINE. IF NOT POSSIBLE TO
ROUTE OVERFLOW DRAIN LINE, INSTALL LOW VOLTAGE
OVERFLOW SWITCH KIT. WIRE KIT TO SHUT DOWN
COMPRESSOR PER INSTRUCTIONS.
NO
YES
CAT #
X3169 CLEAN OUT
VENT
PRESS IN
(DO NOT GLUE)
VENT MUST EXTEND
ABOVE HEIGHT OF
COIL DRAIN PAN BY
TWO INCHES (51MM)
1” X 3/4” X 3/4”
REDUCING
TEE WITH
PLUG
1P-TRAP
49P66, J-TRAP #
91P90 OR ANY
PVC SCH 40 P- OR
J-TRAP 3/4”
OVERFLOW
DRAIN
AIR HANDLER DRAIN PAN
WHEN A COIL IS LOCATED ABOVE A FINISHED SPACE, A
3/4” (19.1MM) SECONDARY DRAIN LINE MUST BE:
CONNECTED TO SECONDARY DRAIN PAN
OR
CONNECTED TO THE OVERFLOW DRAIN OUTLET OF
THE AIR HANDLER DRAIN PAN.
TRAPS MUST BE DEEP ENOUGH TO OFFSET MAXIMUM STATIC DIFFERENCES —
GENERALLY, TWO INCHES (51MM).
DRAIN LINE SHOULD
SLOPE A MINIMUM OF
ONE INCH PER 10
FEET (25MM PER 3
METERS)
NOTE — WHEN A AIR HANDLER IS LOCATED
ABOVE A FINISHED SPACE THE SECONDARY
DRAIN PAN MUST HAVE A LARGER FOOTPRINT
THAN THE AIR HANDLER.
MAIN
DRAIN
TO APPROVED
DRAIN
FOR NEGATIVE PRESSURE COILS (BLOWER
AFTER COIL) TRAPS ARE REQUIRED ON ALL
DRAIN LINES CONNECTED TO COIL.
COMPACT OVERFLOW SWITCH WITH 3/4” FEMALE SLIP INLET
AND MALE ADAPTER, TWO PART DESIGN FOR USE WHERE
OBSTRUCTIONS PREVENT DIRECT THREADING
SECONDARY
DRAIN PAN
2”
(51MM)
TRAP DEPTH
1P-TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J-TRAP 91P90.
2PIPE NIPPLE PROVIDED IN BAG ASSEMBLY - SCH 80, 3/4” I. D. X 5” - 34K7401 (1): CUT THE PIPE IN HALF AND USE IT TO ROUTE THE MA IN DRAIN.
MAIN
DRAIN
PROVIDED
PIPE NIPPLE 2
CUT TO
REQUIRED
LENGTH
SIDE VIEW
Figure 7. Typical Main and Overow Drain

507838-01 Issue 1813 Page 9 of 19
BCE7E Filter Size – In. (mm)
-018, -024, -030, -036 20” x 20” (508mm x 508mm)
-042, -048, -060 20” x 24” (508mm x 610mm)
Table 3. Filter Dimensions
Sealing the Unit
There must be an airtight seal between the bottom of
the air handler and the return air plenum. Use berglass
sealing strips, caulking, or equivalent sealing method
between the plenum and the air handler cabinet to
ensure a tight seal. Return air must not be drawn from a
room where this air handler or any gas-fueled appliance
(i.e., water heater), or carbon monoxide-producing
device (i.e., wood replace) is installed.
WARNING
Seal the unit so that warm air is not allowed into the cabinet.
Warm air introduces moisture, which results in water blow-
off problems. This is especially important when the unit is
installed in an unconditioned area.
Make sure the liquid line and suction line entry points are
sealed with either the provided exible elastomeric thermal
insulation, or eld provided material (e.g. Armaex,
Permagum or equivalent). Any of the previously mentioned
materials may be used to seal around the main and
auxiliary drains, and around open areas of electrical inlets.
Measuring Static Pressure
1. Measure tap locations as shown in Figure 9.
MANOMETER
SUPPLY RETURN
UNIT SHOWN IN
HORIZONTAL DISCHARGE LEFT POSITION
Figure 9. Static Pressure Test
2. Punch a 1/4ʺ (6mm) diameter hole in supply and return
air plenums. Insert manometer hose ush with inside
edge of hole or insulation. Seal around the hose with
Permagum. Connect the zero end of the manometer to
the discharge (supply) side of the system. On ducted
systems, connect the other end of manometer to the
return duct as above. For systems with non-ducted
returns, leave the other end of the manometer open to
the atmosphere.
LEFT-HAND AIR
DISCHARGE
MAIN DRAIN ON
RIGHT
OVERFLOW
DRAIN ON LEFT
UP-FLOW OR
DOWN-FLOW
RIGHT-HAND AIR
DISCHARGE
Figure 8. Main and Overow Drain Locations Based
on Coil Orientation
Best Practices
The following best practices are recommended for the
condensate removal process:
• Main and overow drain lines should NOT be smaller
than both drain connections at drain pan.
• Overow drain line should run to an area where
homeowner will notice drainage.
• It is recommended that the overow drain line be
vented and a trap installed. Refer to local codes.
• Condensate drain lines must be congured or provided
with a cleanout to permit the clearing of blockages and
for maintenance without requiring the drain line to be
cut.
Inspecting and Replacing Filters
Filter access panel must be in place during unit
operation. Excessive warm air entering the unit may
result in water blow-off problems.
IMPORTANT
Filters may be duct-mounted or installed in the cabinet. A
lter is installed at the factory. Note that lter access door
ts over access panel. Air will leak if the access panel is
placed over the lter door.
Filters should be inspected monthly and must be cleaned or
replaced when dirty to assure proper air handler operation.
Reusable lters supplied with some units can be washed
with water and mild detergent. Some units are equipped
with standard throw-away type lters which should be
replaced when dirty.
To replace lter:
1. Loosen the thumbscrews holding the lter panel in
place. Remove the dirty lter.
2. Insert new lter and replace panel.

507838-01Issue 1813Page 10 of 19
3. With only the blower motor running and the evaporator
coil dry, observe the manometer reading. Adjust blower
motor speed to deliver the air desired according to the
job requirements.
4. For best air performance external static pressure drop
must not exceed 0.5” W.C. (1.2 kPa). Refer to blower
data tables for CFM and external static.
5. Seal around the hole when the check is complete.
Adjusting Blower Speed
Motor Speed Taps
NOTE: Motor is programmed for a 45-second delayed OFF
on all speed taps except TAP #1 (continuous fan speed).
Table 4 lists the recommended factory blower speed tap
selections for BCE7E series units.
Operation BCE7E Outdoor Unit Tap
Cooling
All Sizes
Air conditioner 3
Heat pump 3
Heating*
Air conditioner with electric
heat only 4
Heat pump with electric
heat 4
* Minimum setting for heat
Table 4. Recommended Blower Speed Tap Selection
These settings are for nominal tonnage match-ups with
the BCE7E units. When matched with other sizes, it is
recommended that the CFM be adjusted to approximately
400 CFM per ton.
To change blower motor speed tap remove the speed
tap from Y2 on the terminal strip and insert the desired
speed tap. Use the Blower Data tables for the desired CFM
setting.
The high-efciency programmable motor features
programmed electronic braking. The integral control
brakes the motor near the end of the supply blower
operation, allowing the motor to maintain a more
controlled ramping shut-down.
IMPORTANT
Tap Operation Remarks
1
Continuous or low-
speed fan (for two-
speed heat pumps
or AC units)
Continuous fan speed is
energized (24V input to G)
when either G or Y1 has a
24V signal (24V input from
Y1 passes through the room
thermostat’s Fan Automatic
contacts to the G terminal).
2
Low-speed
operation on high-
static system
CFM set at 1/2 ton less than
nominal of unit (e.g. 3-ton set at
1000 CFM).
3Cooling speed
setting
CFM set at 400 cfm per nominal
ton at ARI minimum static
allowed, as follows:
1.5 to 2.0 ton - 0.10
2.5 to 3.5 ton - 0.15
4 to 5 ton - 0.20
4Heat pump with
electric heat
CFM set at 400 cfm per nominal
ton at .4 static. Energized when
electric heat element has a call
for heat.
5High-static
applications
CFM set at 400 cfm per nominal
ton at .8 static.
Table 5. Motor Speed Taps

507838-01 Issue 1813 Page 11 of 19
BCE7E-018 Blower Performance
External
Static
Pressure
in. w.g.
Air Volume and Motor Watts
Tap 1 Tap 2 Tap 3 Tap 4 Tap 5
cfm watts cfm watts cfm watts cfm watts cfm watts
.10 717 66 707 63 735 74 781 81 959 133
.20 596 58 570 54 636 70 737 91 922 144
.30 473 56 430 48 603 77 697 101 877 150
.40 402 61 335 54 540 81 651 105 846 161
.50 358 67 302 60 492 92 607 117 811 173
.60 295 74 248 63 434 94 561 121 769 179
.70 262 79 202 72 399 103 507 131 727 187
.80 N/A N/A N/A N/A 348 108 459 137 695 196
Blower Data
BCE7E-024 Blower Performance
External
Static
Pressure
in. w.g.
Air Volume and Motor Watts
Tap 1 Tap 2 Tap 3 Tap 4 Tap 5
cfm watts cfm watts cfm watts cfm watts cfm watts
.10 767 78 753 75 826 88 957 131 1095 189
.20 662 68 648 66 791 100 937 142 1063 199
.30 615 76 612 77 750 108 895 149 1040 211
.40 561 83 539 83 711 116 861 160 1010 226
.50 522 87 507 89 681 126 821 172 970 230
.60 450 96 438 93 628 134 778 175 944 237
.70 419 100 411 103 584 142 750 186 905 248
.80 365 110 358 108 521 147 702 194 864 256
BCE7E-030 Blower Performance
External
Static
Pressure
in. w.g.
Air Volume and Motor Watts
Tap 1 Tap 2 Tap 3 Tap 4 Tap 5
cfm watts cfm watts cfm watts cfm watts cfm watts
.10 1061 115 1104 126 1169 154 1212 166 1278 200
.20 941 103 973 118 1070 144 1157 173 1241 210
.30 789 90 848 104 1019 151 1121 185 1201 223
.40 640 83 789 111 991 165 1077 199 1169 233
.50 525 93 728 118 946 175 1038 209 1124 244
.60 469 101 629 128 900 181 1006 215 1100 256
.70 434 104 581 139 851 194 956 230 1051 268
.80 365 116 521 155 754 208 915 237 1000 275

507838-01Issue 1813Page 12 of 19
BCE7E-036 Blower Performance
External
Static
Pressure
in. w.g.
Air Volume and Motor Watts
Tap 1 Tap 2 Tap 3 Tap 4 Tap 5
cfm watts cfm watts cfm watts cfm watts cfm watts
.10 1074 134 1099 147 1264 206 1343 240 1498 340
.20 962 121 1027 143 1222 220 1291 253 1467 344
.30 887 126 989 153 1192 234 1269 266 1433 364
.40 852 136 944 164 1144 242 1224 280 1391 378
.50 791 150 894 172 1111 257 1194 286 1365 383
.60 717 160 820 186 1067 266 1153 297 1320 398
.70 649 168 745 202 1037 270 1118 309 1290 407
.80 606 183 697 213 999 284 1081 317 1247 422
BCE7E-042 Blower Performance
External
Static
Pressure
in. w.g.
Air Volume and Motor Watts
Tap 1 Tap 2 Tap 3 Tap 4 Tap 5
cfm watts cfm watts cfm watts cfm watts cfm watts
.10 1282 177 1346 201 1497 261 1489 261 1723 396
.20 1143 159 1278 204 1475 281 1461 273 1690 408
.30 1067 162 1233 209 1447 297 1427 290 1656 434
.40 1024 175 1199 223 1406 315 1407 305 1639 436
.50 920 189 1154 235 1376 320 1360 324 1599 462
.60 923 197 1099 252 1345 338 1328 336 1573 473
.70 838 204 1022 267 1294 358 1303 351 1541 485
.80 815 218 1003 375 1238 375 1228 373 1494 515
BCE7E-048 Blower Performance
External
Static
Pressure
in. w.g.
Air Volume and Motor Watts
Tap 1 Tap 2 Tap 3 Tap 4 Tap 5
cfm watts cfm watts cfm watts cfm watts cfm watts
.10 1359 190 1509 257 1718 362 1773 401 1903 511
.20 1238 174 1473 273 1690 380 1758 419 1899 515
.30 1135 172 1453 289 1658 397 1707 434 1868 535
.40 1090 180 1450 290 1619 412 1687 449 1830 553
.50 1032 195 1374 315 1588 431 1660 465 1801 558
.60 980 204 1336 331 1561 440 1618 472 1770 582
.70 929 223 1295 339 1510 457 1593 493 1733 600
.80 867 235 1227 363 1488 473 1552 508 1703 618
BCE7E-060 Blower Performance
External
Static
Pressure
in. w.g.
Air Volume and Motor Watts
Tap 1 Tap 2 Tap 3 Tap 4 Tap 5
cfm watts cfm watts cfm watts cfm watts cfm watts
.10 1404 206 1704 340 1886 453 1928 481 2268 800
.20 1295 194 1658 349 1849 467 1905 510 2228 829
.30 1256 204 1631 365 1806 489 1869 525 2192 830
.40 1199 217 1594 386 1784 505 1842 546 2169 856
.50 1145 236 1549 394 1751 523 1799 548 2136 870
.60 1091 248 1508 413 1720 534 1775 569 2106 894
.70 978 270 1474 433 1683 549 1741 592 2089 907
.80 946 279 1440 453 1655 566 1709 611 2050 925

507838-01 Issue 1813 Page 13 of 19
Making Electrical Connections
Run 24V Class II wiring only through specied low
voltage opening. Run line voltage wiring only through
specied high voltage opening. Do not combine voltage
in one opening.
WARNING
USE COPPER CONDUCTORS ONLY.
CAUTION
This unit is provided with knock-outs for conduit. Refer to
Figure 11 for unit wiring diagram, which includes all eld
wiring. Separate openings have been provided for 24V low
voltage and line voltage. Refer to the dimension illustration
on Page 2 or Page 3 for specic location.
Wiring must conform to the current National Electric Code
ANSI/NFPA No. 70, or Canadian Electric Code Part I,
CSA Standard C22.1, and local building codes. Refer to
following wiring diagrams. See unit nameplate for minimum
circuit ampacity and maximum overcurrent protection size.
Select the proper supply circuit conductors in accordance
with tables 310-16 and 310-17 in the National Electric
Code, ANSI/NFPA No. 70 or tables 1 through 4 in the
Canadian Electric Code, Part I, CSA Standard C22.1.
The motor speed is set by the speed tap connection to the
low voltage terminal strip in the control section. The speed
can be increased by swapping wires as shown in Figure
11.
Wiring Connections
1. Install line voltage power supply to unit from a properly
installed circuit breaker.
2. Ground unit at unit disconnect switch or to an earth
ground.
NOTE: Connect conduit to the unit using a proper
conduit tting. Units are approved for use only with
copper conductors. A complete unit wiring diagram is
located on the back side of the unit’s access panel.
3. Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit.
NOTE: For proper voltages, select thermostat wire
gauge per the following chart:
Wire Run Length AWG# Insulation / Core Types
Less than 100’ (30m) 18 Color coded, temperature
rating 95°F (35°C)
minimum, solid core
More than 100’ (30m) 16
Table 6. Run Length (Class II Rated Wiring)
circuit connections are made in
the control panel.
Install room thermostat (ordered separately) on an inside wall
approximately in the center of the conditioned area and 5 feet (1.5m)
from the floor. It should not be installed on an outside wall or where it
can be affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
NOTE - 24 VAC, Class II
Ground unit at disconnect switch or to an earth ground.
NOTE - Units are approved for use only with copper conductors.
Figure 10. Thermostat Installation

507838-01Issue 1813Page 14 of 19
Figure 11. Typical System Wiring Diagram

507838-01 Issue 1813 Page 15 of 19
Figure 12. Typical System Wiring Diagram - 460V, Single- and Three-Phase Units (-036, -048, and -060 only)

507838-01Issue 1813Page 16 of 19
Homeowner Maintenance
Do not operate system without a lter. A lter is required
to protect the coil, blower, and internal parts from
excessive dirt and dust. The lter is placed in the return
duct by the installer.
IMPORTANT
• Inspect air lters at least once a month and replace or
clean as required. Dirty lters are the most common
cause of inadequate heating or cooling performance.
• Replace disposable lters. Cleanable lters can be
cleaned by soaking in mild detergent and rinsing with
cold water.
• Install new/clean lters with the arrows on the side
pointing in the direction of air ow. Do not replace a
cleanable (high velocity) lter with a disposable (low
velocity) lter unless return air system is properly
sized for it.
• If water should start coming from the secondary drain
line, a problem exists which should be investigated
and corrected. Contact a qualied service technician.
Professional Maintenance
Failure to follow instructions will cause damage to the
unit.
This unit is equipped with an aluminum coil. Aluminum
coils may be damaged by exposure to solutions with
a pH below 5 or above 9. The aluminum coil should
be cleaned using potable water at a moderate pressure
(less than 50psi). If the coil cannot be cleaned using
water alone, it is recommended to use a coil cleaner
with a pH in the range of 5 to 9. The coil must be rinsed
thoroughly after cleaning.
In coastal areas, the coil should be cleaned with potable
water several times per year to avoid corrosive buildup
(salt).
NOTICE
Repairing or Replacing Cabinet Insulation
DAMAGED INSULATION MUST BE REPAIRED OR
REPLACED before the unit is put back into operation.
Insulation loses its insulating value when wet, damaged,
separated or torn.
IMPORTANT
Matte- or foil-faced insulation is installed in indoor equipment
to provide a barrier between outside air conditions
(surrounding ambient temperature and humidity) and the
varying conditions inside the unit. If the insulation barrier is
damaged (wet, ripped, torn or separated from the cabinet
walls), the surrounding ambient air will affect the inside
surface temperature of the cabinet. The temperature/
humidity difference between the inside and outside of the
cabinet can cause condensation on the inside or outside
of the cabinet which leads to sheet metal corrosion and
subsequently, component failure.
Repairing Damaged Insulation
Areas of condensation on the cabinet surface are an
indication that the insulation is in need of repair.
If the insulation in need of repair is otherwise in good
condition, the insulation should be cut in an X pattern,
peeled open, glued with an appropriate all-purpose glue
and placed back against the cabinet surface, being careful
to not overly compress the insulation so the insulation can
retain its original thickness. If such repair is not possible,
replace the insulation. If using foil-faced insulation, any
cut, tear, or separations in the insulation surface must be
taped with a similar foil-faced tape.
Electric Shock Hazard.
Can cause injury or death.
Foil-faced insulation has conductive
characteristics similar to metal. Be sure
there are no electrical connections within
1/2ʺ of the insulation. If the foil-faced
insulation comes in contact with electrical
voltage, the foil could provide a path for
current to pass through to the outer metal
cabinet. While the current produced may
not be enough to trip existing electrical
safety devices (e.g., fuses or circuit
breakers), the current can be enough
to cause an electrical shock hazard that
could cause personal injury or death.
IMPORTANT
1. CUT INSULATION IN X PATTERN
2. APPLY GLUE
3. PRESS GLUED TABS AGAINST CABINET
GLUE - Make sure there is
full coverage of glue on the
metal or insulation so there
are no areas where air
pockets may form which
can lead to sweating.
Figure 13. Repairing Insulation

507838-01 Issue 1813 Page 17 of 19
Check-out Procedures
During installation, service or maintenance, make sure
that copper tubing does not rub against metal edges
or other copper tubing. Care should also be taken to
ensure that tubing does not become kinked. Use wire
ties to secure tubing to prevent movement.
Do not secure electrical wires to tubing that carries
hot refrigerant gas. Heat from the tubing may melt the
wiring insulation, causing a short circuit.
IMPORTANT
NOTE: Refer to outdoor unit installation instructions for
system start-up instructions and refrigerant charging
instructions.
Pre-Start-Up Checks
• Is the air handler properly and securely installed?
• If horizontally congured, is the unit sloped up to 1/4
inch toward drain lines?
• Will the unit be accessible for servicing?
• Has an auxiliary pan been provided under the unit
with separate drain for units installed above a nished
ceiling or in any installation where condensate
overow could cause damage?
• Have ALL unused drain pan ports been properly
plugged?
• Has the condensate line been properly sized, run,
trapped, pitched, and tested?
• Is the duct system correctly sized, run, sealed, and
insulated?
• Have all cabinet openings and wiring been sealed?
• Is the indoor coil factory-installed TXV properly sized
for the outdoor unit being used?
• Have all unused parts and packaging been disposed
of?
• Is the lter clean, in place, and of adequate size?
• Is the wiring neat, correct, and in accordance with the
wiring diagram?
• Is the unit properly grounded and protected (fused)?
• Is the thermostat correctly wired and in a good
location?
• Are all access panels in place and secure?
Check Blower Operation
• Set thermostat to FAN ON.
• The indoor blower should come on.
Check Cooling Operation
• Set thermostat to force a call for cooling (approximately
5ºF lower than the indoor ambient temperature).
• The outdoor unit should come on immediately and the
indoor blower should start between 30 - 60 seconds
later.
• Check the air ow from a register to conrm that the
system is moving cooled air.
• Set the thermostat 5ºF higher than the indoor
temperature. The indoor blower and outdoor unit
should cycle off.
Check Electric Heat (If Used)
• Set thermostat to call for auxiliary heat (approximately
5°F above ambient temperature). The indoor blower
and auxiliary heat should come on together. Allow a
minimum of 3 minutes for all sequencers to cycle on.
• Set the thermostat so that it does not call for heat.
Allow up to 5 minutes for all sequencers to cycle off.
Use of Air Handler During Construction
It is not recommended to use this air handler unit during any
phase of construction. Very low return air temperatures,
harmful vapors and operation of the unit with clogged or
misplaced lters will damage the unit.
Air handler units may be used for heating (heat pumps)
or cooling of buildings under construction, if the following
conditions are met:
• A room thermostat must control the air handler. The
use of xed jumpers is not allowed.
• Air lter must be installed in the system and must be
maintained during construction.
• Air lter must be replaced upon construction
completion.
• The air handler evaporator coil, supply fan assembly
and duct system must be thoroughly cleaned following
nal construction clean-up.
• All air handler operating conditions must be veried
according to these installation instructions.

507838-01Issue 1813Page 18 of 19
1
Duct
System
Filter
Integrated Control
Electric Heat Amps
Duct Static
5
Line Voltage
3
RETURN
AIR
SUPPLY
AIR
Temperature
8
Blower Motor Amps
6
7
Thermostat
9
2
4Drain Line
Disconnect
Switch
ELECTRIC HEAT AMPS____________
8
8
7
5
DUCT SYSTEM
SUPPLY AIR DUCT
Sealed
Insulated (if necessary)
Registers Open and Unobstructed
RETURN AIR DUCT
Sealed
Filter Installed and Clean
Registers Open and Unobstructed
INTEGRATED CONTROL
Jumpers Configured Correctly (if applicable)
Appropriate Links in Place (if applicable)
VOLTAGE CHECK
Supply Voltage ___________
Electrial Connections Tight
1
2
3
DRAIN LINE
Leak Free
4
TOTAL EXTERNAL STATIC (dry coil)
Supply External Static ______ ______
TEMPERATURE DROP (Cooling Mode)
Return Duct Temperature ___________
THERMOSTAT
Adjusted and Programmed
Return External Static ______ ______
Total External Static = ______ ______
6
Supply Duct Temperature − ___________
Temperature Drop = ___________
TEMPERATURE RISE (Heating Mode)
Return Duct Temperature __________
Supply Duct Temperature − __________
Temperature Rise = __________
Operation Explained to Owner
9
Explained Operation of System to Homeowner
Technician’s Name:_______________________Date Start−Up & Performance Check Completed__________
Installing Contractor’s Name_______________________
Installing Contractor’s Phone_______________________
Job Address____________________________________
Installing Date_______________________________
Air Handler Model #___________________________
INDOOR BLOWER AMPS___________
INDOOR BLOWER CFM____________
Low Voltage _____________
dry coil wet coil
Figure 14. Start-Up and Performance Checklist (Upow Conguration)

507838-01 Issue 1813 Page 19 of 19
RETURN
AIR SUPPLY
AIR
2
Duct Static
5
Line Voltage
3
4Drain Line
ELECTRIC HEAT AMPS____________
8
8
7
5
Filter
Blower motor Amps
DUCT SYSTEM
SUPPLY AIR DUCT
Sealed
Insulated (if necessary)
Registers Open and Unobstructed
RETURN AIR DUCT
Sealed
Filter Installed and Clean
Registers Open and Unobstructed
INTEGRATED CONTROL
Jumpers Configured Correctly (if applicable)
Appropriate Links in Place (if applicable)
VOLTAGE CHECK
Supply Voltage ___________
Electrial Connections Tight
1
2
3
DRAIN LINE
Leak Free
4
TOTAL EXTERNAL STATIC (dry coil)
Supply External Static ______ ______
TEMPERATURE DROP (Cooling Mode)
Return Duct Temperature ___________
THERMOSTAT
Adjusted and Programmed
Return External Static ______ ______
Total External Static = ______ ______
6
6
Supply Duct Te mperature − ___________
Temperature Drop = ___________
TEMPERATURE RISE (Heating Mode)
Return Duct Temperature __________
Supply Duct Te mperature − __________
Temperature Rise = __________
Operation Explained to Owner
9
Electric Heat Amps
7
Explained Operation of System to Homeowner
Technician’s Name:_______________________Date Start−Up & Performance Check Completed__________
Installing Contractor’s Name_______________________
Installing Contractor’s Phone_______________________
Job Address____________________________________
Installing Date_______________________________
Air Handler Model #__________________________
_
Thermostat
9
11
8
INDOOR BLOWER AMPS___________
Temperature
Duct System
Duct System
Integrated
Control
Disconnect
Switch
INDOOR BLOWER CFM____________
Low Voltage _____________
dry coil wet coil
Figure 15. Start-Up and Performance Checklist (Horizontal Conguration)
This manual suits for next models
7
Table of contents
Other Armstrong Air Air Handler manuals
Popular Air Handler manuals by other brands

Daikin
Daikin Modular L Pro Installation, use and maintenance manual

Hitachi
Hitachi RPIL-0.4FSRE Installation & operation manual

System air
System air Topvex TR09 HWL Installation instruction

Envision
Envision Air Handler installation manual

System air
System air SAVE VSR 200/B installation manual

Comfort Star
Comfort Star AHU18-SG2 installation manual