
The Laddomat 22 is factory-fitted with a
thermostat No. 1456 which opens at 78 °C.
The thermostat No. 8719 opening at 72 °C is
included in the delivery (placed in the insulation of
the Laddomat 22).
For most installations, best the thermostat 78 °C is
proved. For boilers with a high output / low water
content as well as at systems with long pipe lines /
thin pipes, the thermostat opening at 72 °C may
be preferred. The thermostat cartridge with the
opening temperature of 72 °C should be used at
outputs above 35 kW.
The higher charging temperature gives more
accumulated heat. In addition, the losses in the
boiler after the fuel burns out in the boiler with the
thermostat having the opening temperature of 78
°C will be smaller, because the connection
between boiler and storage tank will be interrupted
sooner than with the use of thermostat having the
opening temperature of 72 °C.
Different amounts of air bubbles in the fresh
water are present in all new systems.
This air releases inside the boiler walls after
heating the water. The more the boiler heats up,
the more air bubbles are released. We therefore
recommend heating the boiler to the highest
temperature when starting it for the first time.
When the air released in such a way accumulates
in the circulation pump, it can cause cessation of
the circulation. At low temperatures the air releases
more slowly and manages to be discharged
through the expansion or venting.
When a lot of air releases in the system, remove
the thermostat cartridge for a short time.
In extreme cases it is appropriate to make some
firings without use of the thermostat cartridge until
the water is free of air. Remove the spring, plunger
and thermostat cartridge and warm up the heating
system with the upper shut-off valve closed.
After the water is repeatedly heated to 85-95 °C
and free of air, remount the thermostat cartridge
into place.
If, despite these measures, there will be faults in
the system operation, check whether lint or other
debris are not in the pump preventing the
circulation. Also check that the system is installed
correctly according to the documentation.
Important at the first start up
Check that the circulation pump is switched off.
Close the three shut-off valves.
Unscrew the cover opposite the pump.
Remove the cover with spring, plunger and
thermostat cartridge from the Laddomat 22 (Fig. 1).
The thermostat cartridge is held in place on the
plunger by an O-ring.
The thermostat cartridge can be easily removed
from the plunger using a screwdriver (see Fig. 2).
Push a new thermostat cartridge into the plunger.
Reinstall all parts into place and tighten.
Open the shut-off valves.
Wait a few minutes before starting the pump to
allow any air to rise and escape from the system.
The device is now ready for operation.
Blocking the check valve
If you, for some reason, need to completely
disconnect the self-circulation, the check valve
must be blocked. The check valve is blocked using
the blocking clip, which is located at the bottom
of the EPP-insulation (Fig. 3), which is fastened
around the check valve axis according to Fig. 4.
To reach the axis, the spring needs to be removed.
Instructions for replacing the
thermostat in the Laddomat 22
Fig. 3
Fig. 1
Fig. 4
Zde je umístěna náhradní
termopatrona a zajišťovací spona
Zajišťovací spona
(zpětná klapka zablokována)
Changing regulation kit / Regelpaket wechseln
Thermostat not included / Thermoelement nicht enthalten
Old version / Alte Version, 212108:
New version / Neue Version, 212115:
22
Kryt - matice
Kryt - matice
Nová verze
Stará verze
Změna regulační sestavy
Neobsahuje termopatronu
Pružina
(prodloužená)
Termopatrona
(termostat)
O-kroužek
pístu
O-kroužek
pístu
Pružina škrtícího
ventilu
Škrtící ventil
Pouzdro ventilu
(plastová trojnožka)
O-kroužek
Pouzdro
ventilu
Fig. 2
Lock
O-ring
Spring
Vlave
housing
Piston
O-ring
Thermostat
cartridge
Here there is a spare thermostat
cartridge and blocking clip
Blocking clip
(check valve blocked)