
23833A047 11/08/12 2
WARNING: Risk of electric shock. This pump
is supplied with a grounding conductor and
grounding-type attachment plug. To reduce
the risk of electric shock, be certain that it is
connected only to a properly grounded, grounding-
type receptacle.
CALIFORNIA PROPOSITION 65 WARNING:
This product and related
accessories contain chemicals known to the
State of California to cause cancer, birth
defects or other reproductive harm.
Pumps can be installed with ABS, PVC or
polyethylene plastic pipe, or galvanized or copper
pipe. Proper adapters are required to connect plastic
pipe to pump.
The discharge is threaded for 1-1/2" pipe. NOTE: DO
NOT OVERTIGHTEN DISCHARGE PIPE INTO PUMP
PLASTIC DISCHARGE FITTING.
A CHECK VALVE MUST BE USED IN THE
DISCHARGE LINE FOR ALL PUMPS. A shut-off valve
should be used. Always install check valve with arrow
on body in direction of flow.
AIR LOCKING
A sump pump is said to be air locked if water
traps air in the pump and it cannot get out, thus
preventing pump from operating.
ALL MYERS SUMP PUMPS HAVE A SMALL AIR
VENT HOLE IN THE IMPELLER CHAMBER TO
LET OUT TRAPPED AIR. IF THIS HOLE BECOMES
PLUGGED, PUMP MAY AIR LOCK. THIS USUALLY
HAPPENS ON PUMPS THAT ARE USED MAINLY IN
THE WET SEASONS. IN SUMMER MONTHS, THE
PUMP MAY BE TURNED OFF AS SUMP WATER
DRIES UP. WHEN PUMP IS TURNED ON AGAIN
AND WATER COMES UP IN THE SUMP, THE AIR
WILL TRAP IN PUMP IF NOT VENTED.
AS A SECONDARY PRECAUTION IN INSTALLATIONS
OF THIS TYPE, 1/8" HOLE SHOULD BE DRILLED IN
THE DISCHARGE PIPE BELOW THE CHECK VALVE.
THE CHECK VALVE SHOULD BE 12 TO 18" ABOVE
PUMP DISCHARGE. DO NOT PUT CHECK VALVE
DIRECTLY INTO PUMP DISCHARGE OPENING.
STARTING PUMP – (Automatic)
1. These pumps have an integral mechanical
(mercury free) ball float switch. Some models may
have a vertical actuated cylinder float.
2. Plug cord into a 115 volt GROUNDED
RECEPTACLE.
3. Run water into sump until pump starts.
4. Allow pump to operate through several on-off
cycles to be sure operation is satisfactory.
5. If shut-off valve is used in discharge line, be sure
valve is open.
6. Tether length of switch cord on ball float must be
minimum of 3-5/8".
STARTING PUMP – (Manual)
USING MFS SWITCH
1. Secure ball float to discharge pipe with minimum
3-1/2" between float and cable tie.
2. Plug MFS switch cord series plug into proper
voltage GROUNDED RECEPTACLE.
3. Plug pump cord plug into back of switch cord
series plug.
4. Run water into sump until pump starts.
5. Be sure gate valve in discharge line is open.
6. Run pump through several on-off cycles.
7. Tether length of switch cord on ball float must be
minimum of 3-5/8".
WARNING: Sump basin must be vented in
accordance with local plumbing codes. These
pumps are not designed for and CANNOT be
installed in locations classified as hazardous
in accordance with the National Electric Code
ANSI/NFPA 70.
USING THE SUMP PUMP FOR
MANUAL OPERATION
The pump cord for these units can be plugged directly
into proper GROUNDED RECEPTACLE for continuous
pump operation.
CAUTION: THIS TYPE OF OPERATION SHOULD BE
USED ONLY FOR EMERGENCY USE OR WHERE
A LARGE VOLUME OF WATER IS TO BE PUMPED,
SUCH AS FLOODED BASEMENT.
PUMP MUST NOT BE RUN CONTINUOUSLY OUT
OF WATER.
DO NOT USE WITH EXTENSION CORD.
AUTOMATIC/MANUAL MODEL
Some sump pumps can be changed from one style,
automatic or manual, to the other by interchanging
only the plug ends of the float control with the manual
plug. The ball floats must be tethered with a cable
clamp. DO NOT REMOVE THE MOTOR CAP.