D U P L E X E A S Y
Compact ventilation units
with heat recovery and EC fans
Residential ventilation and heating – issue 01/2016
Intended use
The new heat recovery units DUPLEX Easy are supplied in
three sizes:
=DUPLEX 250 Easy
=DUPLEX 300 Easy
=DUPLEX 400 Easy
The units are intended for the comfort ventilation of all types of
residential and civil premises. They are particularly suitable for
low-energy and passive houses and flats in apartment buildings
with a decentralized ventilation system.
General description
The casing of the unit is made of environmentally friendly EPP
(expanded polypropylene), which is also characterized
byminimal moisture absorption and stability over a wide range
of temperatures. The basic version of DUPLEX Easy unit
consist of EPP housing, counter-flow heat exchanger made
ofplastic (efficiency up to 93 %), two free wheel type fans with
electronic EC control, G4 (optionally F7) supply and exhaust air
filters upstream the heat recovery exchanger. Depending the
type oncontrol system, the unit can be equipped with several
different functions and accessories (see the chart on page 4).
The Construction of the unit provides high variability, and the
same unit can be installed in 5 different positions (2 floor-
standing, 2underceiling and 1 floor-standing flat). Condensate
outlets on DUPLEX Easy are ready for all possible mounting
positions. Connecting ports are of a circular type for flexible
orrigid ducts with thermal bridging reduction.
Advantages of DUPLEX Easy units
=High efficient EC fans
=High heat recovery efficiency of the counter flow heat
exchanger
=Great thermal and mechanical parameters of the housing
=Very flat unit (280 mm) suitable for underceiling
installation
=An option of the mirror-wise change of the right hand /
left hand side position
=Light weight of the unit
=Ease of filter changing
=Frost protection (optionally built-in)
=Bypass with actuator (optionally built-in)
=Four types of control systems (see page 4)
C
ounter-flow heat exchanger
with efficiency up to 93 %
EC fans
Bypass damper with actuator
Air filters G4 or F7
Circular port
EPP housing
1
2
3
4
5
6
touch screen
controller CPA (CS2)
22
6
3
1
4
5
5
5
5
4
controller CPB (CS1)
alter.
A
DUPLEX Easy
RE S I D E N T I A L V E N T I L A T I O N & H E A T I N G
ATREA s.r.o., Čs. armády 32
Fax: +420 483 368 112
w w w . a t r e a . e u
E-mail: atrea@atrea.eu
Tel.: +420 483 368 111
Czech Republic
466 05 Jablonec n. Nisou
TECHNICAL DATA – DUPLEX EASY
H E A T R E C O V E R Y E F F I C I E N C Y E A S Y
T E C H N I C A L D A T A E A S Y
DUPLEX Easy
250
300
400
Supply air – max.
3
m /h
280
330
430
Extract air – max.
3
m /h
280
330
430
Max. heat recovery efficiency
%
93
93
93
Max. power consumption of fans
W
120
120
220
Width B
mm
660
820
820
Dimension D
mm
425
435
435
Diameter of connecting ports
mm
 160
 160
 160
Weight
kg
20
21
21
By-pass
–
optional
Voltage
V
230 / 50 Hz
Supply air filter class
–
G4 (alter. F7)
Condensate drain
mm
6x  14 (depending on position)
Heat recovery efficiency (%)
100
90
70
95
80
75
85
3
Volume flow rate (m /h)
050
Possible condensation region M = M
i e
150
100 200 250 350300 400 450
250 Easy
300 Easy
400 Easy
P E R F O R M A N C E P A R A M E T E R S E A S Y
Legend:
Pressure reserve with filter G4*
Qref Reference flow rate
Qmax Maximum flow rate
* Max. pressure reserve curve is shown
* Electrical power consumption is shown (both fans and control system)
Pressure reserve p (Pa)
st
3
Volume flow rate (m /h)
D U P L E X 2 5 0 E A S Y
300
0
100
0 150 200
200
10050
400
600
300250 350
500
Pressure reserve p (Pa)
st
D U P L E X 3 0 0 E A S Y
300
0
100
0 150 200
200
10050
400
600
300250 350
500
Pressure reserve p (Pa)
st
D U P L E X 4 0 0 E A S Y
300
0
100
0 150 200
200
10050
500
900
300250 450
700
350 400
600
800
400
D I M E N S I O N A L D I A G R A M E A S Y
850
280 4545
CM
210
100
190
20
80
22,5
22,5B - 45
805 100
190
20
80
135
120
65
165
198
165
K1 K1
K2
K3
K2 K2 K2
K1 K1 K1 K3, K4
K1
K2K2
K3
B
K4
90
D
K3, K4
K4
K1 ... Condensate drain for floor-standing position
K2 ... Condensate drain for underceiling position
K3 ... Condensate drain for floor-standing flat position
K4 ... Condensate drain for floor-standing flat position
* For both floor-standing and underceiling position use only one appropriate
condensate drain.
** For floor-standing flat use both condensate drains.
To achieve acceptable acoustic values it is necessary to install air distribution with guaranteed acoustic attenuation.
* Approximately it is possible to reduce sound power on outlet e , i to following values:
2 2
=L = 52 dB (A) – using 1 m of soundproofed pipe
w
=L = 43 dB (A) – using 2 m of soundproofed pipe
w
=L = 37 dB (A) – using 3 m of soundproofed pipe
w
** Acoustic values of the units with SK cover – see accessories
A C O U S T I C P O W E R L A N D A C O U S T I C P R E S S U R E L
W P
Type
Working point
Acoustic power L [dB(A)]
w
Acoustic pressure L [dB(A)]
p
at distance of 3 m
inlet e1
inlet i1
outlet e2
outlet i2
unit
DUPLEX 250 Easy
3
200 m /h (100 Pa)
53
53
74*
74*
60 / 54**
40 / 33**
DUPLEX 300 Easy
3
250 m /h (100 Pa)
51
51
74*
74*
61 / 54**
40 / 34**
DUPLEX 400 Easy
3
300 m /h (100 Pa)
50
50
75*
75*
62 / 55**
42 / 35**
A
A
A
1) All types of control system that are built in within the unit commonly include at
least two inputs, so the electrical signals from human operation of lights or other
equipment, that automatically control the performance of the unit, can be
connected. These inputs or other types of sensors must always be connected
(e.g. CO , VOC, rH etc.)
2
2) Maximum flow rate at 100 Pa
3) The value is at reference flow rate it means 70 % of maximum flow rate
and50Pa
4) Acoustic values of the units with SK cover – see accessories
48 W
112 W
58 W
126 W
87 W
218 W
DUPLEX EASY
Note: DUPLEX Easy units are supplied for versatile position mounting – the unit can be installed in all positions (floor-standing, underceiling and floor-standing
flat). The ”right hand” and ”left hand” position according to the figure above is selected simply by relocating the operating sensor and by reconnecting unit fans.
M O U N T I N G P O S I T I O N S
F L O OR -S T A N D I N G U N D ER CE I L I N G F L O OR -S T A N D I N G F L A T
L E G E N D
e Fresh outdoor air suction
1
e Fresh filtered air outlet
2
i Exhaust air suction
1
i Exhaust air outlet
2CM Control module
e1
e2
i2
i1
RM i2
e1i1
RM
e2
e1
e2
i2
i1
RM
i2
e1i1
RM
e2
i1
i2
e2
e1
RM
K1 K1
K2 K2
K3K4
I N S T A L L A T I O N
DUPLEX Easy – underceiling position
New DUPLEX Easy units have a very flat design that allows installing
them into even very low suspended ceilings. The minimum
requirements for suspended ceiling void height is 305 mm.
A plasterboard lid is fitted below the unit.
X
Hmin. 25
12
DUPLEX Easy
removable door
C O N D E N S A T E D R A I N
Condensate drainage
During heat recovery – heat regaining – moisture is condensated during the cooling of exhaust air. Water condensates on the walls of the
heat recovery exchanger, further increasing heat recovery efficiency. Condensate runs out of the heat recovery exchanger in the direction
of air being extracted and is drained from the DUPLEX unit into a sewer system. For correct functioning and drainage the unit must be
separated from the sewer system using a siphon of asufficient height, the recommended minimum being 150 mm. Small condensation
drain pumps may be used. The unit must be installed within the specified gradient for each position.
e1
e2
i2
i1
RM
min. 150
min. 150
HL 21
Inlet into
sewer
K1
F L O O R - S T A N D I N G U N D E R C E I L I N G
min 150
min 150
HL 21
Inlet into
sewer
K2
F L O OR -S T A N D I N G F L A T
min. 150
HL 21
Inlet into
sewer
min. 150
K3
K4
i2
i1
i23° = 25 mm
10° = 75 mm
12° = 100 mm
3° = 25 mm
CONTROLS
Type Description Controller
„Without control
system“
All electrical components are wired to a junction box
inside the unit. This solution is suitable for applications
with computer-based control system (BMS) installed in
buildings that controls and monitors the building’s
mechanical and electrical equipment.
=Without controller
=Frost protection – fan disballance
=Automatic by-pass with servo drive
“CS1“ controls This is the starting level of the DUPLEX Easy control
system that gives basic functions of controlling of the
unit. CS1 version comes with an installed controller.
“RD5“ controls This ATREA proprietary control system meets all
requirements for high-demand controlled ventilation.
The great advantage is the integrated web server as
standard.
S U M M A R Y O F D U P L E X E A S Y C O N T R O L S Y S T E M S
“CS2“ controls This version meets higher requirements and is fully
ready for modern comfort living. This level of our control
system comes with a touch screen controller.
=Volume flow
=Frost protection – preheater (EPO-PTC) or fan
disballance
=Reheating (EPO-PTC)
=Automatic by-pass with servo drive
=Analogue input (0–10 V) for air quality sensor
=Minimum and maximum
speed preselection
=Inlet and outlet shut-off damper
control
=Automatic or manual mode
=Frost protection – preheater (EPO-PTC) or fan
disballance
=Reheating (EPO-PTC)
=Analogue input (0–10 V) for air quality sensor
=Inlet and outlet shut-off damper control
=Manual or weekly program
=Room temperature display
=Party mode, holiday mode
=Filter change notice
=Minimum and maximum
speed preselection
=Frost protection – preheating
(EPO-PTC) or fan disballance
=Optional constant flow function
=Modbus TCP
=Analogue / digital input
=Right or left configuration just through
the controller setting
=Weekly programming
=A ventilation run-down and delay time option
=Boost and party mode
=Combined heating and preheating (EPO-PTC) –
electrical or water based
• Used as a preheater to preheat fresh air, to be
installed in ducts on fresh air inlet
• Used as an afterheater to reheat supply air, to
be installed in ducts after the unit
• Integrated PTC (Positive Temperature
Coefficient) heating elements
• Housing includes a terminal board
and internal wiring
• Includes two protection thermostats –
areversible one and a safety irreversible one
• Contains an interference-free SSR relay
asstandard
• Perforated metal filter to protect heater from
gross particles (easily cleanable)
• Galvanized sheet metal housing
E L E C T R I C H E A T E R S E P O - P T C
 D
(mm)
Voltage
(V)
Power input
(kW)
EPO-PTC 160 / 0,4 kW
 160
1x 230 V~
0,4
EPO-PTC 160 / 0,7 kW
 160
1x 230 V~
0,7
EPO-PTC 160 / 1,7 kW
 160
1x 230 V~
1,7
SK / 250
Special two-piece cover made of galvanized metal sheet (silver color) for better
acoustic parameters
of the DUPLEX Easy.
SK / 300
O P T I O N A L A C C E S S O R I E S – S K C O V E R

This manual suits for next models

3

Other ATREA Fan manuals

ATREA DUPLEX RA5 User manual

ATREA

ATREA DUPLEX RA5 User manual

ATREA DUPLEX EC Series User manual

ATREA

ATREA DUPLEX EC Series User manual

Popular Fan manuals by other brands

Sonnenkonig Dinky instruction manual

Sonnenkonig

Sonnenkonig Dinky instruction manual

Vornado PIVOTC user manual

Vornado

Vornado PIVOTC user manual

SNOWJOE SUNJOE 24V-MSTFAN-LTE-RM Operator's manual

SNOWJOE

SNOWJOE SUNJOE 24V-MSTFAN-LTE-RM Operator's manual

Helios SlimVent Series Installation and operating instructions

Helios

Helios SlimVent Series Installation and operating instructions

NSA SFC-200B instruction manual

NSA

NSA SFC-200B instruction manual

Rubine RCF-Mercury-5BL instruction manual

Rubine

Rubine RCF-Mercury-5BL instruction manual

Nordic Home FT-771 user manual

Nordic Home

Nordic Home FT-771 user manual

Casablanca M8515-01 installation manual

Casablanca

Casablanca M8515-01 installation manual

Vortice VORT QUADRO MEDIO I EP AC Instruction booklet

Vortice

Vortice VORT QUADRO MEDIO I EP AC Instruction booklet

Ortech OD22025 manual

Ortech

Ortech OD22025 manual

Kendal Lighting AC-24246 installation instructions

Kendal Lighting

Kendal Lighting AC-24246 installation instructions

Costway ES10234US manual

Costway

Costway ES10234US manual

Maico WS 160 Flat Installation, commissioning and maintenance instructions

Maico

Maico WS 160 Flat Installation, commissioning and maintenance instructions

getAir SmartFan Installation and operating instructions

getAir

getAir SmartFan Installation and operating instructions

Lifebreath RNC10 installation instructions

Lifebreath

Lifebreath RNC10 installation instructions

Fanimation Evanesce FP2700 Series owner's manual

Fanimation

Fanimation Evanesce FP2700 Series owner's manual

Casablanca Isotope owner's manual

Casablanca

Casablanca Isotope owner's manual

Sterling F-29A instructions

Sterling

Sterling F-29A instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.