ATTACK PELH30A User manual

Appendix Nr.1
PELLET BURNER
PELH30A
MANUAL FOR ATTENDANCE
Manual for installation and start-up
EN - 01.07.2010

1
Content
2 Important information
3 Technical description
4 Dimensions / Range of delivery
5 Technical data
6 Description of function
7 How to use pellet burner
8 Menu buttons and their function
9 Texts on display
10 Texts of menu
11 Production settings
12 How to change production settings
13 How to install pellet burner
14 Burner start
14 Burner stop
14 Emergency stop
15 Cleaning and maintenance
16 Troubleshooting
17 Possible causes of faults
18 Decomposed view
19 Spare parts and codes
20 Scheme of connection
21 Endings and connections, fuses
22 Accessories
23 Contact person and electrotechnician
23 Service record
24 Extended menu
28 Record about installation for warranty execution (copy for customer)
29 Record about installation for warranty execution (please, send to producer)

2
Important information
Please, read this manual befor burner start-up. Burner has to be installed by
approved and trained professional.
Keep this instruction for attendance at suitable place in boiler room. We recommend to
keep it in plasstic cover and to hang it on visible place on the wall to be reached by
technician, who will perform service in your boiler room.
Device for pellet burning, PELH30A has to be connected to boiler that is suitable for
heating with solid fuel. Suitable boiler is ATTACK PELLET 30, resp. 30A. Boiler door
and connections between boiler and chimney have to be airtight.
Overpressure in combustion chamber has to be min. 5 Pascal (0,5mm of water column,
resp. 0.05hPa).
The PELH30A appliance is intended for combustion of wood pellets, it cannot be used for
combustion of other fuel types.
The PELH30A device can be installed only in the boiler room, in conformity with
prescriptions of the local fire protection / construction institute.
Warning sign
Warning sign will appear in this manual to prevent possible risk at breaking the
instructions. In this manual, two types of warning signs are used:
WARNING
advises you of dangerous situations by breaking of essential
proceeding
NOTE
advises you of less safe actions that may lead to safety threat or to
damage of property.

3
Technical description
PELH30A is designed on basis of fuel feeding by principle of falling, when the pellet fall
by self-force from pellet feeder through inlet hose and inlet tube on the grate, where the
combustion runs.
PELH30A has electrical ignition that automatically ignites pellets fallen on the grate.
Ignition begins only after the thermostat gives instruction to burner.
PELH30A has own built-in thernmostat (for the case that there is no boiler/external
thermostat installed, resp. combined connection with room thermostat). Its temperature
sensor has to be inserted into suitable case in water jacket of the boiler. The on- and off-
temperature is adjustable via menu buttons of the burner. Information about actual
operation data is given on display.
NOTE: Head for boiler temperature sensor must not be treated with contact liquid or
paste.
PELH30A has production pre-set range of output 14-30 kW and three degrees of output:
1 (14 kW), 2 (22 kW) and 3 (30 kW).
Selected output degree is projected on display during operation. It is possible to change
output via menu buttons of burner and information on dipslay. It possible to change range
of output in two levels - from 8 to 12kW and from 14 to 30kW and according to this there
are three degrees of output from 8 to 12 kW or from 14 to 30kW in the extended menu.
PELH30A has own self-cleaning grate mechanism. When thermostat reaches adjusted off-
temperature, cycle of burn-out begins and afterwards the grate moves out and it is cleaned
by scraping. This enables longer time of usage, during which it will not be necessary to
remove burner from boiler. Amount of pellets that is possible to combust before the ash is
removed is given by size of the boiler´s ashpan. It is possible to prolong this interval by
automatic ash removal from boiler into ashpan outside of the boiler. Burner is equipped
with control system that regulates gear of the ash removing feeder.
Convectional parts of boiler have to be cleaned in regular intervals to keep high efficiency
of heating.
PELH30A is intended for combustion of wood pellets with diameter of 6-10 mm.
Burner PELH30A is made under industrial norms and prescriptions and it was tested and
approved in conformity with directives about low voltage appliances as well as with
directives about electromagnetic interference.

4
Dimensions / range of delivery
PELH30A is delivered in paper box filled with polysthyrene to improve stability. If the box
is damaged, check burner for possible damage by transport. Reclamation of damage by
transport has to be recorded by spediteur.
Paper box shoul content these parts:
1 pc. Burner PELH30A
1 pc. Inlet tube with emergency thermostat of back-burning
1 pc. External thermal sensor for boiler temperature

5
Technical data
Model PELH30A
Fuel Wood pellets, 6-10 mm
Regime 8 – 12 kW; 14 – 30 kW
Scale of output 8 - 30 kW, graduated by 2 kW
For boilers with heat chamber up to 3 m²
Weight 22 kg
Main voltage Main current Hz
~230V 10A fuse 50
WARNING
Electrical installation has to be done by certified
electrotechnician. Main cables can be replaced only by eletrotechnician approved by us.
Voltage and energy consumption
Component Mains/Volt Min./Max.
Voltage Fuse
Display 5V DC 1 W ---------
Ventilator 230V~ 15-58W 800mA
Circuit plate 230V~ –-------
Grate cleaning 24V DC 10-50W Being
switched
Ignition 230V~ 600W 6.3A
External pellet
feeder 230V~ 15-220W 1A
Ash removing 230V~ 15-220W 1A

6
Description of function
NOTE:
PELH30A works only by usage of boiler thermostat or built-in digital
thermostat, resp. with additional room thermostat. In both cases the burner has to be
connected through fuse against boiler overheating.
Normal start-up
When the thermostat gives instruction to burner, ventilator starts and fotocell controls fire.
If there is no fire, comes instruction to blow the burner through. Afterwards, pellets start to
fall into burner during period stated by control system, then is ignition activated.
When is the phase of fuel feeding for ignition finished, control system waits for fire
signalisation from the photocell.
When the photocell recognizes fire, small amounts of pellts fall during transition
period. Duration of it depends on output level set on the burner. Pellet inlet is gradually
increased, until the necessary fuel amount for required output.
This amount is further delivered into burner until operation thermostat gives
instruction to stop.
This signal stops pellet inlet, while ventilator continues to air inlet into burner.
When photocell recognizes burn-out of pellets, the blow-through of burner begins.
According to adjusted delay, after burn-out of fuel is the burner cleaned - grate moves
out towards scraper and ash with unburned elements falls through fron wall of the burner´s
bottom into the ashpan.
After the grate shifted, the burner waits for new signal from thermostat.
NOTE:
unit for grate moving is very strong and it might cause a threat. Never
put any body parts or foreign articles into burner, while it is working.
Normal start-up, when there is still fire in the burner
If the photocell recoginzes fire during beginning phase (e.g. after short-time current
shortage), control system directly begins the transition-phase and pellet burner continues to
operate as by normal start. (see above)
Normal start-up, when control system does not recognize fire
Normal start-up process followas, also when control system does not receive the fire signal.
Shortly after, system begins new start-up try with reduced fuel amount for ignition to cca
45% and it can be reduced within the whole ignition period. These parameters are
adjustable in service menu, only by the trained person. If the second try fails, all functions
are turned off and alarm is turned on. This alarm is indicated on display.
NOTE:
Make sure, that sufficient flue gas temperature was reached. It has to
be at least 60°C - one meter under the chimney top. If is the temperature lower, consult it
with your chineyer. Flue gas temperature lower than 60°C during combustion process
increases risk of chimney damage by condensation.

7
How to use pellet burner
Pellet burner needs air for combustion, so the boiler room has to have air channel. Air
channel for air inlet must jave at least same surface as chimney and it must be opened.
Pellet burner must not be started, until it is safely approved that smoke can freely go
through boiler and chimney into the enviroment air.
Pellets are feeded into PELH30A from external feeder connected to pellet container. For
better function and the most balanced feeding, the feeder should be leant under angle of
45°. Feeder should be able to feed at least cca 10kg of pellets per hour of continuous
operation / demand for pellet feeding.
Pellets have to be stored in well ventilated room without moisture or in specially adjusted
container.
NOTE:
PELH30A consists from components of high quality that must not be
replaced with spare parts of lower quality. If the components are replaced with other than
original spare parts, the validity of warranty expires.
Menu buttons and their functions
Funtions of burner are set per menu buttons under display. (see also options of settings
under Production settings, below).
How to change settings of pellet burner:
„M“ Menu/Enter: For activation of further records and ENTER/SAVE of changes.
„–„ For comeback in menu and reduction of adjustable values.
„+“ For advance in menu and increasing of adjustable values.
„E“ Exit/Escape: For exit form menu without saving of new values.

8
Values that can be set by user are given in the following schedule:
MENU Explanation
EFFECT ADJ. Required output degree (1, 2 or 3)
PELLET-TRIM Setting of feeded pellet ration
LOG Record of faults for control purposes
FINAL COMBUST. Instruction to burner for burn-out
MENU/ ADVANCED
Access into service menu via code

9
Indications on display
Emergency regime
Nothing in the burner is started, burner waits for start signal
from thermostat.
Thermostat starts.
Step 1 Test blow-through Fan starts to operate and when the photocell recognizes
value under 5%, program continues.
Step 2 Fuel ration for heating up
Fuel ration for heating up is feeded into burner and program
waits for „fire“ signal from photocell.
Step 3 Transition phase Transition phase begins, when photocell and control system
recognize the fire. Small, gradually increasing amounts of
pellets are feeded into burner, until required pellet ration is
achieved.
Step 4 Combustion Combustion phase runs, until it is interrupted by
thermostat.
Step 5 Burn-out Thermostat interrupted combustion phase and burner
begins the phase of burning-out.
Step 6 Cleaning Grate moves out and when it is out completely, fan runs at
full rotations, until the grate moves back.
Step 7 Ash removal After expiration of the set period (e.g.6 hours), the burner
starts auger for ash removing for adjusted time (e.g. 3
minutes).
Step 8: Comeback into standby regime.
PAUS.
OFF FC: 0 %
TEST BLOWING
ON FC: ? %
IGNITION 1
ON FC: ? %
TRANS. PHASE ??KW
ON FC: ? %
COMBUST. ??KW
ON FC: ? %
FINAL-COMBUST.
OFF FC: ? %
SCRAPING
OFF FC: 0 %
ASH AUGER
OFF FC: 0 %

10
Menu Indications
Burner is in standby regime.
Press the”M” button.
Here you can change burner output. Level 1 = 8 (14)kW, 2
= 10 (22)kW, 3 = 12 (30)kW.
Range and Levels of Output are adjustable in advanced
menu.
Press the ”+”button.
Here you can set feeded pellet amount. It is not necessary, if
correct pellet weight was set in Pellet dosing in service
menu.
Press the ”+”button.
If you wish to clean the burner or interrupt operation from
other reasons, press the „M“ button, and the burn-out
regime begins. For burner restart after ash removing, press
„M.“
Press the ”+”button.
This internal setting can be helpful by trobleshotting, if
burner stops and starts alarm. Last 10 different error codes
are recorded. For more information about error codes, see
the „Troubleshooting“.
Press the ”+”button.
To enter into advanced menu you need password (code) and
it is necessary to know program functions of burner.
PAUS.
OFF FC: 0 %
EFFECT LEVEL
ENTER
EXIT
PELLET-TRIM
ENTER
EXIT
FINAL-COMBUST
ENTER
EXIT
LOG
ENTER
EXIT
MENU/ADVANCED
ENTER EXIT

11
Production settings
Before delivery was burner set in the following way:
Generally available menu:
Menu Settings Option Adjustable
Effect level 1 = 14 kW 1, 2, 3 8-30 kW
Pellet-trim 95 % 50-200 % 50 – 200 %
Final combustion 90 sec. 10-600 sec.
Log 10 – 26 Not adjustable
Not
adjustable
Advanced menu Random number + 5 Not
adjustable
” Log ” means, that control system saves last 10 error codes. See also „Troubleshotting“.
Advanced menu
Advanced menu Production
settings Min. – max. Unit
Effect adj. 1, 2, 3,
8, 10, 12,
14, 22, 30,
8 – 12
14 - 30
kilowatt
kilowatt
Ignition setting 90% 50 – 300 % %
Test-blow time 15 0-60 sec.
Transition phase 240-480 60 - 600 sec.
Transition pellet-trim 15 10-50 %
Clean-blow time 45 10 - 600 sec.
Ash auger Run
Interval
3
6 0 – 10
1 - 200 Min.
Hour
Max. comb. time 360 0 - 1080 Min.
Anti-cycling 10 0 - 60 Min.
Modulation effect
∆T
75
10 0 – 100
1 - 100 %
K
Photocell (sensibility) 50 40-80 %
Thermostat External Extern./Intern./Comb.
with room thermostat
Cleaning active
Start if thermostat
1
Turns off 0, 1
Turns on/off
Language *) ENGLISH
Effect span 1 0 (8-12), 1 (14-30)
Stoker adj. heat.
amount 46
1100 45-50
0 - 2000 10xkwh/kg
g/6 min.
Fan factor 95 10 - 500 %
Stoker time 0 hod.
Menu/ Test Auto/Manual

12
Menu/ Settting See Extended
Menu / Log Saves error codes
See Extended
* ) Languages: Slovak, English, German, Italian, French, Polish.

13
How to change production settings
To change settings, select required menu/parameters. By pressing of the „+“ button, change
actual values. O: ...shows actual temperature, N:...can be changed to new value.
It is possible to increase vaues by „+“ and decrease them by „-“. By the „M“ button is
change confirmed and saved. If you do not wish to save the values, press „E“ button
(Exit/Escape).
Please, do not make any changes, until you have not read this manual.
Example:
Comeback to production settings
To reset production settings, select extended menu and enter password (code number after
„O“+5). Then, select Menu/Setup and press the „M“ button. This starts reset of the
production settings.
Here you can also save your own settings, in the following way: by pressing of „+“
button go to „Save settings?“ and save your settings by „M“ button. Exit menu by „E“
button.
Regulation of pellet dosing
Before starting-up of burner, it is necessary to set pellet feeding through parameter of
„Stoker Adj.“ in Advanced menu. Thermostat cannot start heating during setting.
First, set parameter of „heat value“ to value given by your pellet supplier. If supplier gives
4,8kWh/kg, set parameter to 48, etc.
Now, put plastic bag around opening of the pellet feeder. Then, confirm by „M“
button and keep the instructions. Weigh pellets fallen into the plastic bag, put their weight
in gramms via „+/-“ buttons and press „M“ to save values. This setting has to be done
within 15 minutes, otherwise the burner switches to emergency regime. Weigh pellets very
exactly!
After setting of above mentioned parameters, the control system automatically sets all
parameters relative to pellet feeding.
EFFECT ADJ.
O: 1
N: 2

14
How to install pellet burner
Pellet burner PELH30A can be installed only by qualified, specifically skillfull personnel.
Burner door are from production mounted to boiler.
Put the burner on door screws and fasten it by nuts (B). Connect inlet pipe to pellet feeder
under the required angle. Fix inlet pipe into stable position and fasten clamping screws.
Install pellet container and pellet feeder. There should be height gap between feeder´s
opening and inlet pipe of min. 400mm. In horizontal position there should be gap between
inlet pipe and feeder´s opening of min. 1500mm (i.e. not vertically aligned).
Fill container with pellets and connect feeder into mains socket (230V~). Let feeder run,
until you reach continual pellet feeding. We recommend to fix plastic bag to feeder´s
opening to collect falling pellets. Disconnect feeder from mains socket. Install inlet hose
between feeder´s opening inlet pipe and set length of the hose.
Hose should not be straight, nor too incurbed, to prevent pellets from stucking and
cumulating. Connect feeder into burner´s socket.

15
Burner start
By turning the boiler´s main switch on is the burner automatically turned into emergency
regime. Burner is put into operation by turning the burner´s switch on and by turning
boiler´s thermostat into position adequate to required boiler temperature. Following
demand for heat supply is the burner ignited and burns pellets, until the thermostat gives
instruction to stop.
Burner is alternatively controled by thermal boiler sensor connected to TS1 inlet on the
right upper side of the circuit board. Make sure, that connection is fixed into one position.
Burner stop
Burner turnes off by turn-off-signal of the boiler thermostat, by turning off the burner´s
switch (emergency regime, or via Burn-down = Final combust. ) initiated per menu.
Emergency stop
NOTE:
In case of emergency can be burner turned off by the main boiler switch and by plugging-
out of the boiler´s mains cord from mains socket.

16
Cleaning and maintenance
It is necessary to clean the burner after every consumption of 2000kg of pellets. It is based
on presumption, that boiler accepts appropriate amount of ash and quality pellets are being
burned.
Moreover, it is recommended to sweep exchanger´s parts of the boiler at least twice
a month.
1. Clean pellet inlet into burner by brush for bottles or other suitable tool.
2. Scrape the ignition board and the grate and clean holes in the grate.
NOTE:
Keep ash in closed containers from uninflammable material.
Maintenance once a year or in case of need (by qualified person)
Start burn-down by menu buttons and wait, until the fuel in burner burns-out. Turn the
burner off by burner switch and by the main switch, plug out mains cord of the boiler from
mains socket. Open door with burner to cca 90°.
1. Put down burner cover and wipe photocell by rag and soft abrasive agent (tooth paste)
Be carefull by flat cable of display and buttons!
2. Clean air wings of the fan. Most suitable is to blow them with compressed air.
3. Screw out the scrape and ignition board.
4. Clean space behind the ignition board.
5. Scrape ignition board and scraper.
6. Brush grate utterly and clean holes in the grate.
5. Mount all parts back.
6. Clean container and pellet feeder from dust and small dirt.
7. Check state of inlet hose for pellets.
8. Put pellet feeder into operation by plugging of feeder´s mains cord into mains socket
(230V~) to fill it with pellets.
9. Set feeded amount of pellets.

17
Trobleshooting
Burner turned off.
Check, which alarm was indicated on display.
If display is black and without text, check thermal fuse of the boiler. If there is no error,
probably is only the burner´s thermal fuse turned off. To start again, turn energy supply into
burner off, remove cover and press small button between overheating fuse connections.
Thermal fuse is placed directly in the fuel-inlet tube. After restart, mount the cover back
and turn on the energy supply. Thermal fuse of the burner is switched off at the temperature
of 93°C.
Signal text on display Explanation Error code at
recording
ERROR: IGNITION FAILED 10
ERROR: LOST FIRE IN COMBUSTION Extinction at heating, restart failed 11
ERROR: fire sensor Faulty photocell, abnormal light 12
ERROR: CIRCUIT BOARD
OVERHEATED Temperature under cover is too
high 13
ERROR: TEMPERATURE SENSOR
„TOO LOW“ Faulty thermal sensor of built-in
operation thermostat 14
ERROR: TEMPERATURE SENSOR
„TOO HIGH“ Faulty thermal sensor of built-in
operation thermostat 15
ERROR: OPTO-SWITCH Faulty circuit board 16
ERROR: FAN ALWAYS ON Ventilator rotates, when it is not
supposed to 18
ERROR: FAN STOP Ventilator is stopped, when it is not
supposed to be 19
ERROR: FAN SLOW Ventilator rotates too slowly 20
ERROR: IGNITION 1 First ignition trial failed 21
ERROR: STOCKER Pellet feeder is not connected to the
burner 22
ERROR: BURN-DOWN FAILED Photocell recognizes signal also 15
minutes after setting „Burn-down“ 23
ERROR: LIGHT LOST DURING
BURNING Photocell does not recognize fire,
restart failed 24
ERROR: SCRAPER NOT OPERATING Fault in circuit board of scraper or
in grate gear 25
ERROR: SCRAPER JAMMED Grate moves too slowly 26

18
Possible causes of faults
Error
code Possible cause Actions to correction
10 Feeder does not supply enough of
pellets.
Empty pellet container.
Faulty ignition fuse.
Faulty ignition spiral.
Photocell needs to be cleaned.
Set pellet ration.
Fill the container.
Replace fuse. (6.3A).
Replace spiral. (48 Ώ+/- 5%).
Clean photocell.
11 Feeder does not supply enough of
pellets.
Empty pellet container.
Faulty ignition fuse.
Faulty ignition spiral.
Photocell needs to be cleaned..
Set pellet ration.
Fill the container.
Replace fuse. (6.3A).
Replace spiral. (48 Ώ+/- 5%).
Clean photocell.
12 Short circuit or other fault of
photocell. Replace photocell.
13 Too high temperature in boiler
room. Prevent from heat leakage.
14 Faulty sensor of thermostat Replace sensor.
15 Faulty sensor of thermostat Replace sensor.
16 Faulty circuit board Replace circuit board.
18 Ventilator runs, while the burner
is in pause regime. Replace circuit board.
19 Ventilator does not run, when it
should. Change ventilator fuse (800mA); check
connections; replace ventilator
20 Ventilator runs too slowly Clean ventilator; replace ventilator
21 First ignition trial failed Set pellet ration.
22 Pellet feeder missing Connect pellet feeder
23 Incorrect pellet feeding Set pellet ration.
24 Incorrect amount of pellets
feeded.
Faulty photocell
Set pellet ration.
Replace photocell.
25 Cleaning does not work Check connection between circuit board of
scraper and main circuit board.
26 Cleaning is slow Clean grate

19
Decomposed view
Other manuals for PELH30A
1
Table of contents
Popular Burner manuals by other brands

Riello Burners
Riello Burners PRESS 60 N 616 M Installation, use and maintenance instructions

Riftek
Riftek RF096-440 Series user manual

Baxi
Baxi HELIS MI 900 manual

ACV
ACV BMV Series Installation, operation and maintenance instructions

Cuenod
Cuenod NC12 B117 operating instructions

Riello
Riello RLS 68/E MX Installation, use and maintenance instructions

KitchenAid
KitchenAid KBZU242TSS00 parts list

Smeg
Smeg BQ6030 Instructions for the installer

Lamborghini Caloreclima
Lamborghini Caloreclima LMB LO 1300 Use and maintenance manual

Beckett
Beckett NX Series manual

CIB UNIGAS
CIB UNIGAS PG30 Manual of installation - use - maintenance

Unigas
Unigas HP91A Manual of installation - use - maintenance